TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units 

/ Page 11

ARI RATINGS 

ARI Standard 210/240 Ratings

Capacity − Btuh

Efficiency

Total Watts

COP

I d

U it M d l N

Expansion

Cooling

High

Temp

Low

Temp

HSPF

Cool

High Low High Low

Indoor Unit Model No.

Expansion
Device

Cooling Temp.

Heating

Temp.

Heating SEER EER

IV

V

Cool

High

Heat

Low

Heat

High

Heat

Low

Heat

TPA048S2

4 TON

Air Handlers

Air Handlers

46,000 46,000 29,800 11.40 10.00 7.85 7.05 4590 4080 3620 3.30 2.42

3,6

 CB29M−51 (Multi−Position)

Factory TXV

46,500 45,500 29,600 11.60 10.20 7.90 7.10 4530 4020 3560 3.32 2.44

3

 CB29M−65 (Multi−Position)

Factory TXV

49,000 47,500 30,200 13.00 11.00 8.50 7.50 4455 3660 3420 3.80 2.58

CB27UH−060 (Up−Flow / Horizontal)

Factory TXV

49,500 47,500 30,200 13.00 11.00 8.50 7.50 4500 3690 3435 3.78 2.58

4

 CB27UH−048 (Up−Flow / Horizontal)

Factory TXV

49,500 47,500 30,600 13.00 11.00 7.70 7.40 4455 3775 3525 3.68 2.54

3

 CB30M−51 (Multi−Position)

Factory TXV

50,000 47,000 30,000 13.50 11.50 7.70 7.50 4350 3650 3400 3.78 2.58

4

 CB31MV−51 (Multi−Position)

Factory TXV

50,500 47,500 30,600 13.00 11.00 7.70 7.10 4520 4075 3685 3.42 2.44

5

 CB26UH−048 (Up−Flow/Horiz.)

Factory TXV

Up−Flow Indoor Coils + Furnaces

Up−Flow Coils + Furnaces

49,000 47,500 30,600 13.00 11.00 7.70 7.10 4450 4050 3675 3.44 2.44 C33−50/60C

4

 G60UHV−60C−110

2

 

56J20

49,500 47,500 30,600 13.00 11.00 7.70 7.10 4470 4040 3670 3.44 2.44 C33−49C

4

 G61MPV−60C−090

2

 

56J20

49,500 47,500 30,600 13.00 11.00 7.70 7.10 4465 4030 3660 3.46 2.44 C33−49C

4

 G61MPV−60C−110

2

 

56J20

49,500 47,500 30,400 13.00 11.00 7.70 7.10 4455 4030 3655 3.46 2.44 C33−50/60C

4

 G60UHV−60C−090

2

 

56J20

50,000 47,500 30,400 13.00 11.00 7.70 7.15 4430 3975 3620 3.50 2.46 C33−49C

4

 G60UHV−60C−090

2

 

56J20

50,000 47,000 30,400 13.00 11.00 7.70 7.15 4420 3995 3620 3.44 2.46 C33−49C

4

 G60UHV−60C−110

2

 

56J20

50,000 47,000 30,000 13.50 11.00 7.70 7.20 4360 3925 3535 3.50 2.48 C33−60D

4

 G60UHV−60D−135

2

 

56J20

50,000 47,000 30,400 13.00 11.00 7.70 7.20 4410 3965 3585 3.48 2.48 C33−60D

4

 G61MPV−60D−135

2

 

56J20

51,000 47,500 30,400 13.50 11.00 7.70 7.10 4480 4055 3640 3.44 2.44 C33−62C

4

 G60UHV−60C−110

2

 

56J20

51,000 47,500 30,600 13.00 11.00 7.70 7.05 4525 4100 3685 3.40 2.44 C33−62C

4

 G61MPV−60C−090

2

 

56J20

51,000 47,500 30,600 13.00 11.00 7.70 7.05 4520 4095 3680 3.40 2.44 C33−62C

4

 G61MPV−60C−110

2

 

56J20

51,500 47,500 30,400 13.50 11.50 7.70 7.10 4480 4035 3625 3.46 2.46 C33−62C

4

 G60UHV−60C−090

2

 

56J20

Down−Flow Indoor Coils + Furnaces

Down−Flow Coils + Furnaces

49,000 47,500 30,200 13.00 11.00 7.70 7.50 4400 3685 3440 3.78 2.58 CR33−50/60C−F

4

 G60DFV−60C−110

2

 

56J20

49,000 47,500 30,400 13.00 11.00 7.70 7.40 4450 3760 3510 3.70 2.54 CR33−50/60C−F

4

 G61MPV−60C−110

2

 

56J20

49,000 47,500 30,200 13.00 11.00 7.70 7.50 4395 3680 3435 3.78 2.58 CR33−60D−F

4

 G60DFV−60D−135

2

 

56J20

49,000 47,500 30,400 13.00 11.00 7.70 7.50 4395 3705 3455 3.76 2.58 CR33−60D−F

4

 G61MPV−60D−135

2

 

56J20

49,500 47,500 30,400 13.00 11.00 7.70 7.50 4415 3680 3445 3.78 2.58 CR33−50/60C−F

4

 G60DFV−60C−090

2

 

56J20

Horizontal Indoor Coils + Furnaces

Horizontal Coils + Furnaces

50,000 47,500 30,400 13.00 11.00 7.70 7.15 4460 4020 3625 3.46 2.46 CH33−50/60C−2F

4

 G60UHV−60C−110

2

 

56J20

50,000 47,500 30,600 13.00 11.00 7.70 7.10 4505 4065 3670 3.42 2.44 CH33−50/60C−2F

4

 G61MPV−60C−090

2

 

56J20

50,000 47,500 30,600 13.00 11.00 7.70 7.10 4505 4045 3665 3.44 2.44 CH33−50/60C−2F

4

 G61MPV−60C−110

2

 

56J20

50,000 47,000 30,200 13.50 11.00 7.70 7.20 4360 3925 3550 3.50 2.50 CH33−60D−2F

4

 G60UHV−60D−135

2

 

56J20

50,000 47,000 30,400 13.00 11.00 7.70 7.15 4410 3965 3585 3.48 2.48 CH33−60D−2F

4

 G61MPV−60D−135

2

 

56J20

50,500 47,500 30,200 13.50 11.50 7.70 7.65 4365 3530 3355 3.94 2.64 CH23−68

4

 G60UHV−60D−135

2

 

56J20

50,500 47,500 30,200 13.50 11.00 7.70 7.60 4420 3570 3400 3.90 2.60 CH23−68

4

 G61MPV−60D−135

2

 

56J20

50,500 47,500 30,600 13.00 11.00 7.70 7.15 4465 3985 3615 3.50 2.48 CH33−50/60C−2F

4

 G60UHV−60C−090

2

 

56J20

NOTE − These are the only approved system match−ups. For other matches, contact the Lennox Applications Department.
NOTE − Ratings for C33 coils include all cased and uncased coils.
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).

1

Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines;

Cooling Ratings − 

95

_

F (35

_

C) outdoor air temperature and 80

_

F (27

_

C) db/67

_

F (19

_

C) wb entering indoor coil air.

High Temperature Heating Ratings − 

47

_

F (8

_

C) db/43

_

F (6

_

C) wb outdoor air temperature and 70

_

F (21

_

C) db entering indoor coil air.

Low Temperature Heating Ratings − 

17

_

F (−8.3

_

C) db/15

_

F (−9.4

_

C) wb outdoor air temperature and 70

_

F (21

_

C) db entering indoor coil air.

2

Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).

3

Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (

58M81

) is recommend for field installation.

4

Blower control must be set for a time−off blower delay.

5

Most popular air handler combination.

Summary of Contents for TPA036S2

Page 1: ...NTIFICATION T P A Y 1 036 S 4 2 n Major Design Sequence A 1st Generation B 2nd Generation Brand Family T T Classt Product Line Unit Type P Heat Pump Outdoor Unit Nominal Cooling Capacity Tons 036 3 To...

Page 2: ...f Designed for applications with remotely located indoor air handler units See Air Handlers tab section for unit data Units shipped completely factory assembled piped and wired Each unit is test opera...

Page 3: ...th uniform suction flow constant discharge flow and high volumetric efficiency and quiet operation Compressor consists of two involute spiral scrolls matched together to generate a series of crescent...

Page 4: ...requiring input for indicator lights Outdoor Thermostat Kit An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable Ou...

Page 5: ...Accessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1 C...

Page 6: ...91 50 123 49 5 Power Factor 96 88 96 87 96 88 Outdoor Fan Motor Full Load Amps 1 1 55 1 7 82 1 8 9 Fan Motor Locked Rotor Amps 1 9 1 1 4 1 2 2 2 9 2 3 OPTIONAL ACCESSORIES must be ordered extra Compr...

Page 7: ...es adjacent to the control box Clearance to one of the other three sides must be 36 in 914 mm Clearance to one of the remaining two sides may be 12 in 305 mm and the final side may be 6 in 152 mm A cl...

Page 8: ...3 4 70 A ELECTRICAL INLETS LIQUID LINE CONNECTION TOP VIEW BASE SECTION 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed B C A OPTIONAL U...

Page 9: ...3 19A 2 CX34 25A 6F C33 25A 2 CX34 25B 6F C33 25B 2 CX34 30A 6F C33 30A 2 CX34 30B 6F C33 30B 2 CX34 30C 6F C33 30C 2 CX34 31A 6F C33 31A 2 CX34 31B 6F C33 31B 2 CX34 36A 6F C33 36A 2 CX34 36B 6F C33...

Page 10: ...25 3 66 2 52 CR33 30 36B F 4 G60DFV 36B 090 2 56J19 34 600 33 400 20 800 13 00 11 00 8 20 7 20 3075 2695 2435 3 64 2 50 CR33 30 36C F 4 G61MPV 36C 090 2 56J19 34 600 33 200 20 600 13 00 11 00 7 70 7 0...

Page 11: ...ls Furnaces Down Flow Coils Furnaces 49 000 47 500 30 200 13 00 11 00 7 70 7 50 4400 3685 3440 3 78 2 58 CR33 50 60C F 4 G60DFV 60C 110 2 56J20 49 000 47 500 30 400 13 00 11 00 7 70 7 40 4450 3760 351...

Page 12: ...50 CR33 50 60C F 4 G60DFV 60C 090 2 56J20 54 000 55 000 35 600 13 00 11 00 7 70 6 70 4910 4670 4145 3 46 2 52 CR33 60D F 4 G60DFV 60D 135 2 56J20 Horizontal Indoor Coils Furnaces Horizontal Coils Fur...

Page 13: ......

Page 14: ......

Page 15: ...REVISIONS Sections Description of Change Ratings Revised TPA060 ratings...

Page 16: ...tment to quality Specifications Ratings and Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pro...

Reviews: