TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units 

/ Page 10

ARI RATINGS 

ARI Standard 210/240 Ratings

Capacity − Btuh

Efficiency

Total Watts

COP

I d

U it M d l N

Expansion

Cooling

High

Temp

Low

Temp

HSPF

Cool

High Low High Low

Indoor Unit Model No.

Expansion
Device

Cooling Temp.

Heating

Temp.

Heating SEER EER

IV

V

Cool

High

Heat

Low

Heat

High

Heat

Low

Heat

TPA036S2

3 TON

Air Handlers

Air Handlers

34,400 33,600 20,800 13.00 11.00 7.70 6.75 3150 2825 2695 3.48 2.26

3

 CB30M−41 (Multi−Position)

Factory TXV

34,400 33,600 20,800 13.00 11.00 7.70 6.70 3155 2830 2710 3.48 2.24

3

 CB30U−41/46 (Up−Flow)

Factory TXV

34,400 34,000 21,200 12.20 10.40 7.70 6.70 3245 2925 2755 3.40 2.26

3,6

 CB29M−46 (Multi−Position)

Factory TXV

34,600 33,600 20,800 13.00 11.00 7.70 6.80 3130 2790 2670 3.52 2.28

3

 CB30M−46 (Multi−Position)

Factory TXV

34,600 34,200 21,600 12.00 10.30 7.50 6.60 3350 3045 2840 3.24 2.22

3

 CB29M−51 (Multi−Position)

Factory TXV

34,800 33,400 20,800 13.00 11.00 7.70 6.80 3125 2765 2650 3.54 2.30

4

 CB31MV−41 (Multi−Position)

Factory TXV

34,800 33,200 20,600 13.50 11.00 7.70 6.70 3165 2705 2570 3.60 2.34

CB27UH−036 (Up−Flow / Horizontal)

Factory TXV

35,200 33,800 21,000 13.00 11.00 7.70 7.10 3165 2760 2515 3.58 2.44

5

 CB26UH−036 (Up−Flow/Horiz.)

Factory TXV

36,400 33,000 20,400 14.00 12.00 7.70 6.70 3035 2700 2505 3.58 2.38

CB27UH−042 (Up−Flow / Horizontal)

56J19

Up−Flow Indoor Coils + Furnaces

Up−Flow Coils + Furnaces

34,200 33,200 20,600 13.00 11.00 7.70 6.80 3080 2875 2610 3.38 2.32 C33−36B

4

 G60UHV−36B−090

2

 

56J19

34,200 33,200 20,600 13.00 11.00 7.70 6.75 3065 2885 2615 3.38 2.30 C33−36C

4

 G61MPV−36C−090

2

 

56J19

34,200 33,200 20,600 13.00 11.00 7.70 6.80 3080 2875 2610 3.38 2.32 C33−42B

4

 G60UHV−36B−090

2

 

56J19

34,400 33,200 20,800 13.00 11.00 7.70 6.80 3100 2865 2615 3.40 2.32 C33−36C

4

 G61MPV−60C−090

2

 

56J19

34,600 33,200 20,600 13.00 11.00 7.70 6.85 3085 2840 2590 3.42 2.32 C33−36C

4

 G60UHV−60C−110

2

 

56J19

34,600 33,200 20,800 13.00 11.00 7.70 6.80 3095 2850 2605 3.42 2.34 C33−36C

4

 G61MPV−60C−110

2

 

56J19

Down−Flow Indoor Coils + Furnaces

Down−Flow Coils + Furnaces

34,600 33,400 20,800 13.00 11.00 8.20 7.20 3060 2675 2425 3.66 2.52 CR33−30/36B−F

4

 G60DFV−36B−090

2

 

56J19

34,600 33,400 20,800 13.00 11.00 8.20 7.20 3075 2695 2435 3.64 2.50 CR33−30/36C−F

4

 G61MPV−36C−090

2

 

56J19

34,600 33,200 20,600 13.00 11.00 7.70 7.05 3060 2760 2495 3.52 2.42 CR33−48B−F

4

 G60DFV−36B−090

2

 

56J19

34,800 33,600 20,800 13.00 11.00 8.20 7.20 3105 2680 2440 3.68 2.50 CR33−30/36C−F

4

 G61MPV−60C−090

2

 

56J19

35,000 33,600 20,800 13.00 11.00 8.20 7.25 3100 2665 2430 3.70 2.50 CR33−30/36C−F

4

 G61MPV−60C−110

2

 

56J19

Horizontal Indoor Coils + Furnaces

Horizontal Coils + Furnaces

34,000 33,200 20,800 13.00 11.00 7.70 7.00 3075 2785 2510 3.50 2.42 CH23−41

4

 G60UHV−36B−090

2

 

56J19

34,000 33,200 20,800 13.00 11.00 7.70 7.00 3065 2795 2510 3.48 2.42 CH23−41

4

 G61MPV−36C−090

2

 

56J19

34,400 33,400 20,800 13.00 11.00 7.70 7.05 3090 2765 2505 3.54 2.44 CH23−41

4

 G61MPV−60C−110

2

 

56J19

34,600 33,200 20,600 13.00 11.00 7.70 6.80 3075 2835 2625 3.44 2.30 CH33−36C−2F

4

 G61MPV−36C−090

2

 

56J19

34,800 33,400 20,800 13.00 11.00 7.70 6.80 3100 2810 2625 3.48 2.32 CH33−36C−2F

4

 G61MPV−60C−090

2

 

56J19

35,000 33,400 20,800 13.00 11.00 7.70 6.85 3100 2800 2615 3.50 2.32 CH33−36C−2F

4

 G61MPV−60C−110

2

 

56J19

NOTE − These are the only approved system match−ups. For other matches, contact the Lennox Applications Department.
NOTE − Ratings for C33 coils include all cased and uncased coils.
NOTE − When used with gas furnaces, a dual−fuel control (i.e. FM21) or a control system with dual−fuel capabilities (i.e. Harmony III, LZP−2 or LZP−4) must be used (ordered extra).

1

Certified in accordance with USE certification program which is based on ARI Standard 210/240 with 25 ft. (7.6 m) of connecting refrigerant lines;

Cooling Ratings − 

95

_

F (35

_

C) outdoor air temperature and 80

_

F (27

_

C) db/67

_

F (19

_

C) wb entering indoor coil air.

High Temperature Heating Ratings − 

47

_

F (8

_

C) db/43

_

F (6

_

C) wb outdoor air temperature and 70

_

F (21

_

C) db entering indoor coil air.

Low Temperature Heating Ratings − 

17

_

F (−8.3

_

C) db/15

_

F (−9.4

_

C) wb outdoor air temperature and 70

_

F (21

_

C) db entering indoor coil air.

2

Factory installed expansion valve or RFC on indoor unit MUST be replaced with valve specified (if equipped).

3

Blower must be capable of time−off blower delay. Indoor Blower Off Delay Relay (

58M81

) is recommend for field installation.

4

Blower control must be set for a time−off blower delay.

5

Most popular air handler combination.

Summary of Contents for TPA036S2

Page 1: ...NTIFICATION T P A Y 1 036 S 4 2 n Major Design Sequence A 1st Generation B 2nd Generation Brand Family T T Classt Product Line Unit Type P Heat Pump Outdoor Unit Nominal Cooling Capacity Tons 036 3 To...

Page 2: ...f Designed for applications with remotely located indoor air handler units See Air Handlers tab section for unit data Units shipped completely factory assembled piped and wired Each unit is test opera...

Page 3: ...th uniform suction flow constant discharge flow and high volumetric efficiency and quiet operation Compressor consists of two involute spiral scrolls matched together to generate a series of crescent...

Page 4: ...requiring input for indicator lights Outdoor Thermostat Kit An outdoor thermostat can be used to lock out some of the electric heating elements on indoor units where two stage control is applicable Ou...

Page 5: ...Accessories For Touchscreen Thermostat Locking cover clear C0MISC15AE1 1 Remote sensors for C0STAT02AE1L can be applied in the following combinations 1 C0SNZN01AE1 2 C0SNZN73AE1 2 C0SNZN01AE1 and 1 C...

Page 6: ...91 50 123 49 5 Power Factor 96 88 96 87 96 88 Outdoor Fan Motor Full Load Amps 1 1 55 1 7 82 1 8 9 Fan Motor Locked Rotor Amps 1 9 1 1 4 1 2 2 2 9 2 3 OPTIONAL ACCESSORIES must be ordered extra Compr...

Page 7: ...es adjacent to the control box Clearance to one of the other three sides must be 36 in 914 mm Clearance to one of the remaining two sides may be 12 in 305 mm and the final side may be 6 in 152 mm A cl...

Page 8: ...3 4 70 A ELECTRICAL INLETS LIQUID LINE CONNECTION TOP VIEW BASE SECTION 4 3 8 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed B C A OPTIONAL U...

Page 9: ...3 19A 2 CX34 25A 6F C33 25A 2 CX34 25B 6F C33 25B 2 CX34 30A 6F C33 30A 2 CX34 30B 6F C33 30B 2 CX34 30C 6F C33 30C 2 CX34 31A 6F C33 31A 2 CX34 31B 6F C33 31B 2 CX34 36A 6F C33 36A 2 CX34 36B 6F C33...

Page 10: ...25 3 66 2 52 CR33 30 36B F 4 G60DFV 36B 090 2 56J19 34 600 33 400 20 800 13 00 11 00 8 20 7 20 3075 2695 2435 3 64 2 50 CR33 30 36C F 4 G61MPV 36C 090 2 56J19 34 600 33 200 20 600 13 00 11 00 7 70 7 0...

Page 11: ...ls Furnaces Down Flow Coils Furnaces 49 000 47 500 30 200 13 00 11 00 7 70 7 50 4400 3685 3440 3 78 2 58 CR33 50 60C F 4 G60DFV 60C 110 2 56J20 49 000 47 500 30 400 13 00 11 00 7 70 7 40 4450 3760 351...

Page 12: ...50 CR33 50 60C F 4 G60DFV 60C 090 2 56J20 54 000 55 000 35 600 13 00 11 00 7 70 6 70 4910 4670 4145 3 46 2 52 CR33 60D F 4 G60DFV 60D 135 2 56J20 Horizontal Indoor Coils Furnaces Horizontal Coils Fur...

Page 13: ......

Page 14: ......

Page 15: ...REVISIONS Sections Description of Change Ratings Revised TPA060 ratings...

Page 16: ...tment to quality Specifications Ratings and Dimensions subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pro...