TP − 3 to 5 Ton R−22 Heat Pump Outdoor Units
LOW AMBIENT CONTROL Option
(Down to 0°F)
Order one each: Speed Control Kit, Weatherproof Kit, Outdoor Fan Motor and Capacitor
Model No.
TPA036S2
TPA048S2
TPA060S2
Speed Control Kit
X5867
S
S
S
Weatherproof Kit
56N41
S
S
S
Outdoor
Fan Motor
1/2 HP − 230V
69H75
S
S
S
Fan Motor
460V
69H76
S
S
S
Capacitor
with mounting bracket
53H06
S
S
S
INSTALLATION CLEARANCES − INCHES (MM)
See
NOTES
See NOTES
See NOTES
See
NOTES
CONTROL
BOX
NOTES:
Service clearance of 30 in. (762 mm) must be maintained on one of
the sides adjacent to the control box.
Clearance to one of the other three sides must be 36 in. (914 mm)
Clearance to one of the remaining two sides may be 12 in. (305 mm)
and the final side may be 6 in. (152 mm).
A clearance of 24 in. (610 mm) must be maintained between two units.
48 in. (1219 mm) clearance required on top of unit.
OUTDOOR SOUND DATA
1
Unit
Model No
Octave Band Sound Power Levels dBA, re 10
−12
Watts
Center Frequency − HZ
1
Sound
Rating
Model No.
125
250
500
1000
2000
4000
8000
Rating
Number (dB)
TPA036S2
69.5
70.5
71.5
69.5
68.5
62.5
60.5
76
TPA048S2
75.5
74.5
75
73.5
70
66.5
63.5
80
TPA060S2
76
76.5
76.5
74.5
69.5
66
61.5
80
NOTE − the octave sound power data does not include tonal correction.