background image

Page 20

Burner Start−Up

 1 − Set thermostat for heating demand and turn on electri-

cal supply to unit.

 2 − Open all shut−off valves in the oil supply line to the

burner.

 3 − While the ignition is on, press and release the reset

button on the burner control (hold 1/2 second or less).

 4 − Bleed the pump until all froth and bubbles are purged.

The bleed port is located on the bottom of the fuel
pump. To bleed, attach a clear plastic hose over the
vent plug. Loosen the plug and catch the oil in an
empty container. Tighten the plug when all the air has
been purged.

NOTE − A two−line fuel system will normally bleed itself
by forcing air back to the tank through the return line.
This type of bleeding procedure is not necessary.

 5 − If burner fails to start within the set time, the burner

control will lock out operation. Press the reset button to
reset the control as in step 3. See figure 2 for burner
parts arrangement.

CAUTION

Do not push the reset button on the primary control
more than one time.

 6 − Repeat steps 4 and 5, if necessary, until pump is fully

primed and oil is free of bubbles. Then, terminate the
call for heat. The burner control will resume normal op-
eration

Fuel Pump Pressure Adjustment

Measure fuel pump pressure with unit off. Attach pressure
gauge to pump outlet. Turn unit on and check pressure and
compare to table 9. Adjust if necessary.

Temperature Rise Adjustment

To measure temperature rise, place plenum thermometers
in warm air and return air plenums. Locate thermometer in
warm air plenum where thermometer will not see" the heat
exchanger to prevent it from picking up radiant heat. Set
thermostat to its highest setting to start unit. After plenum
thermometers have reached their highest and steadiest
readings, subtract the readings. The difference in tempera-
tures in the supply and return air plenums should approxi-
mate the temperatures listed in table 8 and on the ap-
pliance rating plate.

If the temperature rise is not within the range listed, check
the following items:

D

Make sure that properly sized nozzle has been
used (table 9).

D

Make sure that fuel pump pressure is correct.

D

If furnace is in cutback mode, check for:
Dirty filters,
Dirty indoor coil,
Restricted ducts, closed registers, etc.

Table 8

Temperature Rise

Unit

Temperature Rise °F

SLO183BV101

65 − 75

SLO183BV114

70 − 80

SLO183BV135

65 − 75

SLO183BV150

70 − 80

Limit Control

Limit Control  Do not adjust from factory setting.

Burner Adjustment

The following instructions are essential to the proper op-
eration of SLO183BV series oil furnaces. To prevent soot-
ing, these instructions must be followed in sequence:

1.

Draft

This test should be taken at the breach be-

tween the outlet of the vent connector and the baro-
metric draft control. Generally a 1/4" hole will need to
be drilled for the draft gauge to be inserted into the vent
connector.
A minimum of 0.03 draft must be established without
the burner in operation. With the burner in operation,
the draft should be 0.04 to 0.05. This is VERY critical to
the flame retention head burners.
Oil furnace installations also require careful inspection
to make sure the chimney is in good shape and can ac-
commodate the products of combustion. The tempera-
ture in the unconditioned space will also affect the draft
if long vent connectors are allowed to get too cold.

2.

Overfire Draft

This test should be taken with the

burner in operation. Remove the plug from the center
of the inspection port. Insert your draft gauge into the
hole.
A reading of the overfire draft should be 0.02 less than
the reading found in the vent connector. If a positive
reading is seen at this point, the combustion fan is
pumping too much air into the heat exchanger. Make
the necessary adjustments with the air shutter or air
band.

Summary of Contents for SLO183BF101/114V42

Page 1: ...O183BV Start Up Performance Check List 2 SLO183BV Unit Parts Arrangement 3 SLO183BV AFG Burner Parts Arrangement 3 Requirements 4 Combustion and Ventilation Air 5 Locate Level Unit 6 Nozzle Adjustment...

Page 2: ...1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 SLO183BF135 150V60 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406 SLO183BR135 150V60 22 1 2 572 37 940 52 1 2 1334 27 686 21 x...

Page 3: ...eat Exchanger Blower Control A54 Not Visible Located on blower housing Clean Out Port SLO183BV AFG Burner Parts Arrangement ESCUTCHEON PLATE MAIN HOUSING HEAT SHIELD BURNER CONTROL with Reset Button O...

Page 4: ...is strongly recommended especially in new homes Refer to table 1 or the unit plate for specific combus tion air opening dimensions Table 1 Combustion Air Opening Dimensions Model No Combustion Air Ope...

Page 5: ...a basement or large equipment room with a volume greater than 50 cubic feet 1 4 cubic meters per 1 000 Btu 293 W per hour of the combined input rating of all appliances installed in that space This s...

Page 6: ...rs will have 20 to 25 per cent free area and metal louvers and grilles will have 60 to 75 percent free area Louvers and grilles must be fixed in the open position or interlocked with the equipment so...

Page 7: ...114 and 150 units Inspect the spark transformer leads also to en sure they are still attached to the electrodes The burner assembly is attached to the vestibule panel by three nuts Slots are provided...

Page 8: ...rd ing to the requirements of the National Fire Protection Asso ciation The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector Make sure the chim...

Page 9: ...not be less than the area of the largest vent or vent connection plus 50 of the area of the additional vent or vent con nection Chimney must be able to sufficiently vent all appliances operating at th...

Page 10: ...hting instruction on the unit place the appliance being inspected in operation Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been det...

Page 11: ...edures that should be followed when installing the supply air plenum 1 Use sealing strips of fiberglass 2 In all cases the plenum should be secured to furnace or evaporator cabinet with sheet metal sc...

Page 12: ...ings IMPORTANT Both oil supply and return pipes must be submerged in oil in the supply tank Table 4 Two Pipe Maximum Pipe Length H R Lift H 3450 RPM 3 GPH 11 4 LPH 3 8 10 mm OD Tubing 1 2 12 mm OD Tub...

Page 13: ...een the tank shut off valve and the burner Locate filter close to but at least 3 feet away from the burn er for easy maintenance Table 6 lists the filters for the SLO183B furnace Consult the burner ma...

Page 14: ...hrough specified high voltage opening Do not com bine voltage in one opening CAUTION Use copper conductors only IMPORTANT If using a programmable thermostat be sure to use a type of thermostat that re...

Page 15: ...ams 1 Heat 1 Cool ComfortSense 7000 L7724U 1 Heat 2 Cool ComfortSense 7000 L7724U 1 Heat 1 Cool ComfortSense 7000 L7724U with Thermostat Dehumidification Mode 1 Heat 2 Cool ComfortSense 7000 L7724U wi...

Page 16: ...age Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7724U with Dual Fuel Control Mode Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7...

Page 17: ...de mand is satisfied OFF CALL 100 82 Y 60 sec 7 5 minutes 82 y Y Cool Demand Present y Cool Demand Satisfied When the demand for cool is met the blower ramps down to 82 CFM for 60 seconds then turns...

Page 18: ...times the light may appear to flicker or glow This takes place when the control is communicating with the motor be tween cycles This is normal operation After the CFM for each application has been de...

Page 19: ...1600 755 1200 565 N A N A Same as NORM N A N A Same as NORM 1700 800 1530 720 1360 640 1020 480 NOTE Continuous Fan air volume is 50 of COOL speed Blower Control A54 Figure 18 16 PIN PLUG BOARD TO MOT...

Page 20: ...n tempera tures in the supply and return air plenums should approxi mate the temperatures listed in table 8 and on the ap pliance rating plate If the temperature rise is not within the range listed ch...

Page 21: ...hings which might affect combustion Those things which might affect combustion can then do so without causing the unit to start sooting smoking Things which might affect combustion include a nozzle go...

Page 22: ...rossover tube CAUTION Do not attempt to clean the combustion chamber It can be easily damaged 5 Replace the clean out caps and flue access elbow Make sure locking screws are secure 6 Brush out and vac...

Page 23: ...f as long as the button is held Enables pump priming After the reset button has been held for 15 seconds The button can then be clicked during the next ignition sequence to enter pump prime mode Run i...

Page 24: ...oft lockout reset oil primary control allows second ignition attempt Primary control enters hard lockout after second ignition failure 15 sec onds without flame being sensed Push reset but ton on prim...

Page 25: ...speed ramps down Circulat ing fan shuts off after 60 seconds Thermostat begins call for fan G terminal is energized Indoor blower is energized immediately at 50 of cool speed ST9103A may be factory co...

Page 26: ...ect the flame detector wires at the primary control If the burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false...

Page 27: ...from unit Inspect the nozzle for plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray pattern Nozzle strainer plugged Poor o...

Page 28: ...ter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbalan...

Page 29: ...wheel dirty Clean blower wheel Wrong motor rotation Replace motor Restrictions in return or supply air system Correct cause of restriction Power If voltage fluctuates fault is in the power source Rech...

Page 30: ...ed heat exchanger Clean heat exchanger Readjust burner Insufficient overfire draft Increase draft Incorrect nozzle assembly depth Set to 1 13 Too little combustion air Increase combustion air High sta...

Reviews: