NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE

Venting Requirements

Approved Vent Systems:

Lennox Hearth Products  Co-linear Chimney Liner Kit Recommended:

•  The Flex Kit, Cat. No. H0909 includes one 35 feet flex liner and four 

gear clamps.

•  The Termination Kit, Cat. No. TKDVI includes the termination cap with two 

co-linear collars for 3 inches (76 mm) flex attachments and flashing.

•  The Flex and Termination Kit, Cat. No. DV3FK35 includes two flex liners, 

termination cap and four gear clamps.

 Secure Vent™ Co-Linear Chimney Liner Kit Recommended:

 •  Direct-Vent Vertical Termination Kit (includes Vertical Termination      

Cap gas/Connector, Flashing, Qty 2 of 25 feet (7.6 M) length of 3 inches 

(76 mm) Aluminum Flex, Clamps and Sealant) #DV3FK25

 •  Direct-Vent Vertical Termination Kit (includes Vertical Termination Cap/

Connector, Flashing, Qty 2 of 35 feet length of 3 inches Aluminum  

Flex, Clamps and Sealant) #DV3FK35

Standard Simpson Dura-vent Co-linear Chimney Liner Kit recom-

mended:

 •  Direct-Vent Vertical Termination Cap #991

 •  Liner Termination Kit

   

(includes termination connector and flashing) #923GK

 •  3" x 35 feet (76 mm x .91 M) Alum Flex #2280

Selkirk/Metalbestos Direct-Temp Co-Linear Chimney Liner Kit recom-

mended

 •  Direct-Vent Vertical Termination Cap #4DT-VC   

 •   Liner Termination Kit 

   

(includes termination connector and flashing) #4DT-CTB

 •  3” x 35’ (76 mm x .91 M) Aluminum Flex #AF3-35L

Amerivent Direct Co-Linear Chimney Liner Kit recommended

 •  Direct-Vent Vertical Termination Cap #4DVC

 •  Co-Linear Adaptor #4DCAT33

 •  Flashing #4DF or #5DF

 •  3” x 35’ Aluminum Flex #3AFL-35

        

WARNING

Do not substitute the heat-rated flex liner (UL1777) for the 

exhaust with any other type liner or a fire may result caus-

ing property damage, personal injury or loss of life.

Positive Flue Connection

Masonry and Factory Built Fireplaces

A qualified installer should evaluate the existing fireplace to determine 

the best method for achieving a positive flue connection between the vent 

and intake liners and the chimney.

Air Inlet Liner (for combustion air) When 

terminating the air inlet liner at this point, a 

positive flue connection is required (to ensure 

combustion air is drawn down the chimney 

only).

Exhaust 3" (75mm) UL 

1777. A full length liner 

is required from the 

exhaust outlet on appli-

ance to center collar of 

termination cap.

Positive Flue Con-

nection (sealing 

fireplace throat 

using a noncombus-

tible seal-off plate 

or insulation).

The outside air inlet does not 

require a full reline (if intake 

liner is terminated in chimney 

and a positive flue connection 

is achieved as specified).

Ai

r I

nl

et

Ex

ha

us

t

Ai

r I

nl

et

Existing Fireplace Flue

(chimney)

Masonry and Factory Built Fireplaces

Figure 6a - Terminating Air Inlet in Chimney 

Vertical Cap

Termination 

Connector

Exhaust

Intake

Combustion Air Intake

The  existing  fireplace  chimneys  may  take 

various contours which the flexible liners will 

accommodate. However, keep the flexible liner 

as STRAIGHT as possible, avoid unnecessary 

bending.

Liner Requirements:

Vertical Height Min. = 10 ft. (3.05 M)

Vertical height Max. = 35 ft. (10.67 M)

Use 3" (76 mm) diameter listed gas 

vent liner (UL1777 ONLY) for the 

EXHAUST

Use 3" (76 mm) diameter listed 

liner (UL 181 or UL1777) for the 

AIR INTAKE.

The flexible vent pipe 

must NOT be allowed to 

sag behind  insert or in 

fireplace flue.

The standard cap 

in Termination Kit, 

TKDVI,  is  a  high 

wind cap

Make sure that both liners will pass through existing damper area. Remove 

or lock damper to allow the passage of the flexible liners. If the damper 

will not allow the passage of both liners, DO NOT PROCEED FURTHER.  

(If fireplace is masonry) Consult a local mason for removal of the damper 

without risk of structural damage or leakage (if the fireplace is factory 

built) The appliance may NOT be installed into the fireplace.

Figure 6b

NOTE: Terminating the air intake liner as shown here may not be 
allowed by some local codes.  Check with the authority having jurisdic-
tion for your area.

Summary of Contents for SHRL 33 DV INS

Page 1: ...uctions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindie L installation et l entretien doivent tre assur s par un installateur ou un service d entretie...

Page 2: ...e 29 Replacement Parts List Page 30 Part Identification Page 31 Optional Accessories Page 36 Safety Listing Label Page 39 Lighting Instructions Label Page 40 Warranty and Product Reference Information...

Page 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Page 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Page 5: ...nician if you decide to change orifices Theuseofotherfuelsorcombinationoffuelswilldegradetheperformance of this system and may be dangerous Orifice Size Altitude Adjustment These appliances are tested...

Page 6: ...tallation requirements These appliances must be vented directly to the outside in accordance with the current edition of the National Fuel Gas Code NFPA 54 in U S A and CAN CSA B149 1 in Canada and mu...

Page 7: ...centimeters in length The individual manual shut off must be a T handle type valve Massachusetts Horizontal Vent Requirements IntheCommonwealthofMassachusetts horizontalterminationsinstalled less tha...

Page 8: ...Unit To Intake Collar 7 7 8 200 N O D Width Small 3 pc Flange 36 5 8 930 N O D Width Large 3 pc Flange 41 1041 O O D Height Small 3 pc Flange 25 7 8 657 O O D Height Large 3 pc Flange 28 711 P O D Wi...

Page 9: ...rfaces to combustible construction etc above the appliance Paint or lacquer used to finish the mantel must be heat resistant in order to avoid discoloration Minimum Clearances to Combustibles Hearth F...

Page 10: ...tible une fois la conduite de gaz en place IMPORTANT Wheninstallingtheseappliancesintoafactorybuiltfireplace or heat form the air flow within and around the fireplace shall not be altered by the insta...

Page 11: ...ethod for achieving a positive flue connection between the vent and intake liners and the chimney Air Inlet Liner for combustion air When terminating the air inlet liner at this point a positive flue...

Page 12: ...seal See Table 5 for the minimum vertical termination height requirements Vertical Termination Height Minimum Factory Built and Masonry Fireplaces The vent air intake termination clearances above the...

Page 13: ...ocationsontheupperlatchassembly You can then tighten the screws down by turning the wrench or T Handle clockwise SNUG ONLY DO NOT OVERTIGHTEN See Figure 12 4 Figure 13 shows the insert with the door i...

Page 14: ...refractory brick panels and log set theinsertshouldbeinstalledinthefireplace the venting attached the gas line connected and tested for leaks and the initial burner operation checked Figure 15 Figure...

Page 15: ...of carbon monoxide CO a colorless orderless toxic gas The size and position of the log set is critical to achieve a safe reliable and attractive flame pattern Any attempt to use a different log set i...

Page 16: ...ctory in front See Figure 24 C B F pin 5 Locate groove in center log B and place the top of the right log D in groove with the bottom end of the log resting against the right refractory panel See Figu...

Page 17: ...of its final location Surround Kits Models SHR33 SHR40 Part Cat Description Dimensions 75387 Small 3 sided Flange 36 5 8 W x 25 7 8 H 75385 Small 4 sided Flange 36 5 8 W x 29 3 16 H 75388 Large 3 side...

Page 18: ...in Picture C Turning the ball screw counter clockwise as you are look ing at it will give you less tension and turning the ball screw clockwise will give you more tension when opening and closing the...

Page 19: ...ometer and check the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution and retighten if necessary If the pressure i...

Page 20: ...thermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfourn...

Page 21: ...d call your service technician or your gas sup plier 8 After pilot is lit turn gas control counterclockwise to ON Knob can only be turned ON if the knob has popped out 9 To turn burner on turn ON OFF...

Page 22: ...To Turn Off Gas To Appliance above Gas Control Knob Pilot On Off Flame Height Control Knob Hi Lo Piezo Igniter WARNINGS Improper installation adjustment alteration service or maintenance can cause inj...

Page 23: ...ry while adjusting flame appearance Theairshuttershouldneverbesetsoastomake the tips of the flames sooty or create sooting on the viewing glass logs or heat exchanger If sootbeginstoformafterburning t...

Page 24: ...t is used Fire the fireplace insert four suc cessive times for ten minutes each time with a five minute cool down between each firing to cure the paint and burn off lubricants used in the manufacturin...

Page 25: ...manufacturers instructions could result in a malfunction Pay special attention to the thermostat location require ments If the location requirements are not adhered to the appliance erratic operation...

Page 26: ...roperly size the flames The flames should directly contact the thermopile and extend across the main burner ports Be careful not to back the screw out of its threads Replace the cover and check for ga...

Page 27: ...the inside of the glass this condensation and fog will usually disappear in a few minutes This can cause lint dust and other airborne particles to cling to the glass surface Initialcuringofthehightemp...

Page 28: ...chnician Perform the appropriate appliance checkout procedure detailed in this manual Replacing Rockwool Ember Materials Homeowner Qualified Service Technician Remove old ember materials and vacuum th...

Page 29: ...efective igniter no spark at electrode Defective or misaligned electrode at pilot spark at electrode Check gas supply To purge hold in gas cock on valve for 1 2 minutes and try again Check for spark a...

Page 30: ...ector 26 H5751 Blower Ducting 27 H5752 Wire Grommets 28 H5753 Burner Support 29 H5754 Front Leveling leg Assembly 30 H5755 Gasket kit 31 H5756 Surround Hinge 32 H5757 Ball Screw Assembly 33 H5758 Ball...

Page 31: ...26 25 27 2 30 PART IDENTIFICATION Item Description 2 Air Intake Assembly 3 Blower Box Assembly 4 Flue Collar Assembly 5 Blower Snap Switch Assembly 23 Brick Panel Brackets 24 Surround Hanging Brackets...

Page 32: ...LE Item Description 8 Burner Assembly 9 Pilot Assembly w Shield 10 Main Orifice 11 Bulkhead Assembly 12 Cassette Plate Assembly 13 Valve Assembly 14 Air Shutter Assembly 15 Cassette Assembly 30 Gasket...

Page 33: ...T TO SCALE 8 PART IDENTIFICATION Item Description 2 Air Intake Assembly 3 Blower Box Assembly w Blower 6 Rear Leveling Leg Assembly 7 Outer Bottom Assembly 8 Burner Assembly 27 Wire Grommets 29 Front...

Page 34: ...N 22 Ceramic Log Set Item Description 8 Burner Assembly 16 Louver Assembly 17 Blower Rheostat 18 Control Panel Valve Cover 19 On Off Switch Item Description 20 Igniter w nut 21 Door Assembly 22 Cerami...

Page 35: ...e Surround Assembly Item Description 31 Surround Flange Hinge 32 Ball Screw Assembly 33 Ball Screw Catch Assembly 34 Surround Spacer Kit Small 35 Surround Spacer Kit Large 36 Extrusion Kit 3 Piece Sma...

Page 36: ...ng the hand held remote control transmitter Screen Panel Kit This screen panel kit can be installed over the glass enclosure panel to help protect from making direct contact with the hot glass surface...

Page 37: ...piece Small 75388 SHR SP 3P LG Surround Panel Kits 3 piece Large Width Height Cat No Model Description H7987 SHR BRK STD Brick Panel Set Tan H7988 SHR BRK RED Brick Panel Set Red H7989 SHR BRK ARCHSTO...

Page 38: ...er Kit DVI 3 X 35 requires 2 one for exhaust and one for intake TKDVI TKDVI Termination Kit DVI termination cap and flashing DV3FK35 DV3FK35 Flex Liner and Termination Kit 3 X 35 includes 2 flex liner...

Page 39: ...devant G le foyer H Distance verticale de la base de H l appareil aux combustibles Note Extension d tre fabriqu avec 1 minimum de mat riaux non combustible ou quivalent poss dant un facteur k de 0 84...

Page 40: ...ion suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d vacuation vous pourr...

Page 41: ...41 NOTES...

Page 42: ...anufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the follow...

Reviews: