NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

6

12

X

Roof Pitch is X/12

2 FT
MIN.

2 FT MIN.

Lowest

Discharge

Opening

H*

*H = MINIMUM HEIGHT FROM ROOF TO

LOWEST DISCHARGE OPENING OF VENT

TERMINATION HEIGHTS FOR VENTS ABOVE

FLAT OR SLOPED ROOFS

Horizontal Overhang

Vertical

Wall

Vent

Termination

Storm Collar

Concentric

Vent Pipe

Flashing

1 inch (25.4 mm) Minimum
Clearance to Combustibles

The vent/air intake termination clearances 
above the high side of an angled roof is as 
follows:

Roof Pitch ................. Feet 

Meters

Flat to 6/12 ................ 1.0 

0.3

6/12 to 7/12 ............... 1.25 

0.38

7/12 to 8/12 ............... 1.5 

0.46

8/12 to 9/12 ............... 2.0 

0.61

9/12 to 10/12 ............. 2.5 

0.76

10/12 to 11/12 ........... 3.25 

0.99

11/12 to 12/12 ........... 4.0 

1.22

12/12 to 14/12 ........... 5.0 

1.52

14/12 to 16/12 ........... 6.0 

1.83

16/12 to 18/12 ........... 7.0 

2.13

18/12 to 20/12 ........... 7.5 

2.29

21/12 to 21/12 ........... 8.0 

2.44

Figure 4

Figure 3

MANUFACTURED (MOBILE) HOME 
REQUIREMENTS

These models may be installed in an after-
market permanently located, manufactured 
home, where not prohibited by local codes. 
When installed in Manufactured Housing 
the following supplemental requirements 
must be met:

•   The appliance must be secured to the fl oor 

(i.e. use (4) 1/4" x 2-3/4" bolts and nuts or 
equivalent. Note: Not included) for securing 
appliance to the manufactured home fl oor.

•  The appliance must be grounded to the 

chassis of the manufactured home. Use a 
No. 8 or heavier copper wire at least 18” in 
length.

•   The structural integrity of the manufactured 

home fl oor, walls, ceiling and roof must be 
maintained.

•  A manufactured (mobile) home installation 

must conform with the Manufactured Home 
Construction and Safety Standard, Title 24 
CFR, Part 3280, or, when such a stan-dard 
is not applicable, the Standard for Manufac-
tured Home Installations, ANSI / NCSBCS 
A225.1, or standard for Gas equipped 
Recreational Vehicles and Mobile Housing, 
CSA Z240.4.

Horizontal Vent Termination Clearances

The horizontal vent termination must have 
a minimum of 3" (76 mm) clearance to any 
overhead combustible projection of 2-1/2" (64 
mm) or less. See 

Figure 4

.  For projections 

exceeding 2-1/2" (64 mm), For additional vent 
location restrictions refer to 

Figure 5

.

VENT TERMINATION CLEARANCES

Vertical Vent Termination  Clearances

These instructions should be used as a 
guideline and do not supersede local codes in 
any way. Install vent according to local codes, 
these instructions, the current National Fuel 
Gas Code (ANSI-Z223.1) in the USA or the 
current standards of CAN/CGA-B149.1 and 
-B149.2 in Canada.

Side Elevation View

QUESTIONS TO ASK LOCAL BUILDING 
OFFICIAL

This appliance must be installed per manu-
facturers’ instructions.

Installations must conform to appropriate 

local codes and applicable state and federal 
requirements.  Familiarity with these require-
ments before installation is essential.  Some 
important considerations to discuss with 
local building offi cials include: 

1. Applicable codes (i.e. Uniform Mechanical 

Code, State or Regional Gas Codes, National 
Fuel Gas Code)

2. Local amendments
3.  Recognized testing lab: OMNI-Test Labora-

tories Inc.; Beaverton, Oregon

4.  Is a permit required - cost?
5.  In some states or municipalities, a licensed 

gas fi tter or plumber may be required to 
install this appliance.  Check with your local 
building offi cial for requirements in your area 
(i.e. Is a license required for installation of 
gas supply line)?

6. Maximum amount of gas pipe without a 

pressure test - type of test required?

7.  Are below grade penetrations of the gas line 

allowed?

8.  Is concealed gas piping allowed?
9. Specifi c requirements of concealed fi t-

tings?

10. Is rigid pipe to appliance required?
11. Allowed piping materials?
12. Shut-off valve required within 4 feet of the 

fi rebox?

13. May the shut-off valve be concealed?
14. Rooms where the installation is not 

allowed?

In the absence of local codes, installation 
should conform to National Fuel Gas Code, 
ANSI Z223.1 / NFPA 54-Latest Edition in the 
USA or National Fuel Gas Code, CAN/CGA-
B149-Latest Edition in Canada.

3"

(76 mm)

12"

(305 mm)

Horizontal T

Combustible Projection

greater than 2 1/2 inches in length

Horizontal Vent Termination Clearances

Combustible Projection

2 1/2

    

 inches or less in length

18"

(457 mm)

Ventilated

Soffit

Unventilated

Soffit

ermination Kit

3"

(76 m

1"

(25 mm

Note - See vent manufacturer's instructions for recess 
allowances, into exterior walls for the horizontal 
termination caps.

Summary of Contents for SEREFINA CI1500DVF series

Page 1: ...E OU LA MORT POUR VOTRE SÉCURITÉ Ne pas entreposer ni utiliser d essencenid autrevapeursouliquidesinflammablesdans le voisinage de cet appareil ou de tout autre appareil POUR VOTRE SÉCURITÉ Que faire si vous sentez une odeur de gaz Ne pas tenter d allumer d appareil Ne touchez à aucun interrupteur Ne pas vous servir des téléphones se trouvant dans le batiment où vous vous trouvez Evacuez la piéce ...

Page 2: ...used Millivolt appliances are designed to oper ate on natural or propane gas A millivolt gas control valve with piezo ignition system provides safe efficient operation External electrical power is required to operate the optional blower if installed on these units Note Installation and repair should be per formed by a qualified service person The appliance should be inspected annually by a qualifi...

Page 3: ...e appliances and their individual shut off valves must be disconnected from the gas supply piping system during any pressure testing of that system at pressures in excess of 1 2 psig 3 5 kPa These appliances must be isolated from the gas supply piping system by closing their individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or l...

Page 4: ...mm H 40 1016 mm 48 1 2 1232 mm Specifications CI1500DVF CI2500DVF Min Max BTU hr Input NG 17 500 28 000 25 500 38 500 Min Max BTU hr Input LP 20 500 27 000 26 500 34 500 DV Vent Size 4 inner 6 5 8 outer 4 inner 6 5 8 outer Room Fan CFM 150 150 Weight lb 206 290 Efficiencies CI1500DVF CI2500DVF EnerGuide P4 67 NG 65 LP 67 NG 64 LP Steady State Efficiency 85 NG 87 LP 83 NG 85 LP Note Due to Lennox o...

Page 5: ... alcove that allows for the minimum clearances to combustible surfaces Your local building inspector should review your plans prior to installation When installing this appliance provide adequate clearances for the purposes of servicing and proper operation As determined through the safety certification of this unit a minimum clearance to combustible materials must be maintained around specific ar...

Page 6: ...additionalvent location restrictions refer to Figure 5 VENT TERMINATION CLEARANCES Vertical Vent Termination Clearances These instructions should be used as a guidelineanddonotsupersedelocalcodesin anyway Installventaccordingtolocalcodes these instructions the current National Fuel Gas Code ANSI Z223 1 in the USA or the current standards of CAN CGA B149 1 and B149 2 in Canada Side Elevation View Q...

Page 7: ... n i w t n e v e r p o t d e d n e m m o c e r m m 9 2 2 9 n o i t a s n e d n o c w o d n i w t i f f o s d e t a l i t n e v o t e c n a r a e l c l a c i t r e V D l a t n o z i r o h a n i h t i w l a n i m r e t e h t e v o b a d e t a c o l r e t n e c e h t m o r f m m 8 5 4 s e h c n i 8 1 f o e c n a t s i d l a n i m r e t e h t f o e n i l m m 8 5 4 8 1 m m 8 5 4 8 1 t i f f o s d e t a...

Page 8: ...et aside Step5 Page8 Removepackagedmaterials from inside firebox and set aside log set bag of embers and NG to LP conversion kit Step 6 Page 9 Remove cardboard packag ing material from beneath relief door and discard Step 7 Page 9 Install LP Conversion kit if necessary Install any optional accessories excluding firescreens Step 8 Page 9 Install lower access door Step 9 Page 9 Venting System Instal...

Page 9: ...control wiring system of the unit to a 120 volt power supply residential line voltage Thegasvalveissetinplaceandpre wiredatthe factory on both models see Figure 11 SIT Millivolt Wiring Diagram If any of the original wire as supplied must be replaced it must be replaced with Type AWM105 C 18 GA wire Thermopile TH TP TH TP ON OFF Switch Optional Thermostat Remote Control Receiver SWITCH Figure 10 Bl...

Page 10: ...see Figures 13 and 14 SupportBrackets Installventsupportbrack ets as specified in the vent manufacturers instructions and the National Gas Fuel Code USA NFPA 54 ANSI Z223 1 7 6 5 Support ofGasVents Gasventsshallbesupportedand spaced in accordance with their listings and the vent manufacturer instructions General Information These instructions should be used as a guideline and do not supersedelocal...

Page 11: ...ance for Natural Gas and 36 for Propane Gas before the first elbow The horizontal run may extend up to 20 feet 6 meters and include a vertical rise of up to 40 feet 12 meters see Figure 13 Horizontal termination must meet the criteria shown in Figures 4 and 5 Approved vent systems must terminate above and including the heavy line in Figure 13 Two 45 degree elbows may be substituted for each single...

Page 12: ...nversion Kit for 6 I D 1 insulation SV4CCK2 Factory Built Chimney Conversion Kit for 7 I D 1 insulation 8 I D 1 insulation 6 I D 2 insulation SV4CCK3 Factory Built Chimney Conversion Kit for 10 I D 1 insulation 7 I D 2 insulation 8 I D 2 insulation Model Brand SIMPSON DURA VENT Description 934 Masonry Chimney Conversion Kit 931 Factory Built Chimney Conversion Kit A for 6 I D 932 Factory Built Chi...

Page 13: ...Black 904B 24 Pipe Length Black SV4L36 36 Pipe Length Galvanized 903 36 Pipe Length Galvanized SV4LB36 36 Pipe Length Black 903B 36 Pipe Length Black SV4L48 48 Pipe Length Galvanized 902 48 Pipe Length Galvanized SV4LB48 48 Pipe Length Black 902B 48 Pipe Length Black SV4LA 6 Adj Pipe Length Galvanized 908 6 Adj Pipe Length Galvanized SV4LBA 6 Adj Pipe Length Black N A N A SV4LA12 12 Adj Pipe Lengt...

Page 14: ...inlet port fitting Figure 20 Ember Strip Rear Log Figure 21 Left Front Log Figure 22 2 Place the largest log onto the rear log stoppers see Figure 20 Ensure that the grooves on the bottom of the log aligns onto the corresponding places on the rear log stoppers Push the log back so that it is against the back of the rear log stoppers see Figure 21 3 Place the left front log onto the corre sponding ...

Page 15: ...ethefineembermaterial mineral wool into dime sized fluffy pieces b Distribute the pieces over the top of the front burner ports avoiding covering the slots see Figure 29 and filling the area in front of the forward logs Figure 26 Figure 27 Figure 29 VERIFY THAT THE GAS LINE HAS BEEN PURGED OF AIR SEE STEP 10 Figure 25 Left Top Twig Step 12 RE INSTALL FRONT GLASS ENCLOSURE PANEL Reverse instruction...

Page 16: ...d run initial system checkout before closing up the front of the unit Follow the pilot lighting instruc tions provided in the Homeowner s Care and Operation Instructions or pull out the instruction label located in a holder on rear shield of stove For piezo igniter location see Figure 30 Fasten the two latches located beneath the firebox floor to the glass frame vee flange Close both the latches s...

Page 17: ...15 9 mm CI2500DVF 1 2 12 7 mm 5 8 15 9 mm Initially always position the air shutter to the factorysettingasshowninFigure34 adjust mentrodislocatedinthelowercontrolarea This can be done by moving the adjustment rodupordownaccordingly Allowtheburner to operate for at least 15 minutes Observe the flame continuously If it appears weak or sooty as previously described adjust the air shutter to a more o...

Page 18: ...MBRE DE SERIE XXXXX XXXXX IIIIIIIIIIIIIIIIIIII XXXXXXXXXXXXXXXX P N 9 1452A MODEL NO CI1500DVF SERIES MANUFACTURED AT SANTA TERESA NM FOR USE WITH NATURAL GAS EQUIPE POUR GAZ NATUREL ALTITUDE MIN GAS SUPPLY PRESS WC PRESS MIN D ALIMENTATION CE MANIFOLD PRESSURE WC PRESSION CE TUBULURE CE MANUFACTURER S RECOMMENDED ORIFICE SIZE DIMENSION DE L INJECTEUR RECOMMANDE PAR MANUFACTURIER DMS MAX INPUT BTU...

Page 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE ...

Page 20: ...ts P N 775 147M REV D 11 2006 1110 West Taft Avenue Orange CA 92865 Lennox reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information ...

Reviews: