background image

18

4-WAY

DC- FAN

CN 414

3

PAN 

HEATER

CN

 19

CN 
60

CRANKCASE 

HEATER

CN

 16

AM

BI

EN

T T

EMP

. SE

NS

OR

DIS

CHAR

GE

 TEMP

. SENSO
R

CN 17

.

Y/G

BLUE

BROWN  1

BLACK 3

3

2

L1L2

RED

BLUE  L2

1

Y/G

Y/G

CN 3

Y/G

Y/G

 COMPRESSOR

Y/G

U V

W

BLUE

RED

BLACK

L1 L2

S

White

Red

Blue

CN 6 CN 7 CN 8 CN 2

CN 

21

W

V

U

OUTDOOR CONTROL

TP/

T5

Figure 39. 24K - 208/230VAC Outdoor Unit Wiring Diagram 

Unit Start-Up

IMPORTANT

Units should be energized 24 hours before unit start­up 

to prevent compressor damage as a result of slugging.

1. 

Inspect all factory- and field-installed wiring for loose 

connections.

2.  Verify that the manifold gauge set is connected.
3.  Add additional refrigerant charge if required before 

opening valves and while system is still under a 

vacuum.

4. 

Open  the  liquid  and  suction  line  service  valves  to 

release the refrigerant charge contained in outdoor 

unit into the system.

5.  Replace the stem caps and tighten to the value listed 

in “Table 3. Torque Requirements” on page 7.

6.  Check voltage supply at the outdoor unit terminal strip. 

The voltage must be within the range listed on the 

unit’s nameplate. If not, do not start the equipment 

until you have consulted with the power company and 

the voltage condition has been corrected.

7.  Refer to the included user guide to operate the system 

using the provided remote control.

8.  Visually check for binding of both indoor and outdoor 

fans.

Troubleshooting

Table 10. Indoor Unit Error Codes

Display Error Information

E0

Indoor unit EEPROM parameter error

E1

Indoor / outdoor units communication error

E2

Zero-crossing signal detection error

E3

The indoor fan speed is operating outside of the normal 

range

E4

Indoor room temperature sensor T1 is in open circuit or 

has short circuited

E5

Evaporator coil temperature sensor T2 is in open circuit or 

has short circuited

EC

Refrigerant leak detected

F0

Overload current protection

F1

Outdoor ambient temperature sensor T4 open circuit or 

short circuit

F2

Condenser coil temperature sensor T3 is in open circuit or 

has short circuited

F3

Compressor discharge temperature sensor TP open circuit 

or short circuit

F4

Outdoor unit EEPROM parameter error

F5

The outdoor fan speed is operating outside of the normal 

range

p0

IPM malfunction or IGBT over-strong current protection

p1

Over voltage or over low voltage protection

p2

High temperature protection of IPM module

Summary of Contents for MWHA009S4-1L

Page 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Page 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Page 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Page 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Page 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Page 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Page 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Page 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Page 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Page 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Page 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Page 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Page 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Page 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Page 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Page 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Page 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Page 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Page 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Page 20: ...20...

Reviews: