background image

12

Table 4.  Flaring Pipe 

Pipe Diameter

Flare Dimension 

A (mm)

Flare Shape

Min

Max

1/4”

8.3

8.7

R0.4~0.8

A

45°

90

°

4

-+

3/8”

12.0

12.4

1/2”

15.4

15.8

5/8”

18.6

19.1

3/4” (22.9)

22.9

23.3

8. 

After  flaring  the  pipe,  temporarily  sealed  pipe  ends 

with adhesive tape to avoid contaminants from 

entering the pipes.

9.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or water from getting into the 

refrigerant piping before it is connected.

10. 

CAREFULLY

 adjust refrigerant piping connections to 

suit the application.

11. 

Slowly  loosen  one  of  the  flare  nuts  to  release  the 

factory nitrogen charge from the indoor units only.

12. 

Remove  the  flare  nuts  from  the  connections  on  the 

unit and discard the seal from each of the piping 

connections.

13. 

Slide the flare nuts onto the ends of the field-provided 

refrigerant piping before using a suitable flaring tool to 

flare the end of the copper pipe.

14. Apply recommended HFC­410A refrigerant lubricant 

to the outside of the flared refrigerant lines. 

15. Align the threaded connections with the 

flared  refrigerant  lines.  Tighten  the  flare  nuts 

lightly  at  first  to  obtain  a  smooth  match  as 

illustrated in “Figure 30. Making Connections 

 

(Male to Female Connection)”.

Table 5.  Refrigerant Piping and Indoor Unit 

Connection Sizes

Size 

(Btuh)

Liquid Line 

in.

Suction Line 

in.

9K

1/4

3/8

12K

1/4

1/2

18K

1/4

1/2

24K

3/8

5/8

A

B

CANT ON THE OUTSIDE OF

THE FLARE

MALE FLARE

CONNECTION

Figure 30. Making Connections  

(Male to Female Connection)

16. 

Once  snug,  continue  another  half-turn  on  each  nut 

which should create a leak­free joint. A torque wrench 

may be used to tighten flare nuts using “Table 6. Flare 

Nut Torque Recommendations”. 

17. After refrigerant piping has been installed and checked 

for leaks, apply insulation over all flared connections.

IMPORTANT

Always use two wrenches when tightening flare nuts to 

avoid twisting refrigerant piping. DO NOT over-tighten 

flare nuts.

TORQUE WRENCH

TO INDOOR

UNIT

TO OUTDOOR UNIT

BACKUP

WRENCH

Figure 31. Tighten Flare Nut

Table 6.  Flare Nut Torque Recommendations

Outside 

Diameter

Recommended 

Torque

No torque wrench available 

Finger tighten and use an 

appropriately sized wrench to 

turn an additional:

Inches

1/4

15 ft.­lb. (20 N)

1/4 turn

3/8

26 ft.­lb. (35 N)

1/2 turn

1/2

41 ft.­lb. (56 N)

7/8 turn

5/8

48 ft.­lb. (65 N)

1 full turn

IMPORTANT

Do not allow for excess length of line sets to be left 

rolled up as part of the required, or in general. This will 

also cause additional performance issues.

IMPORTANT

Do  not  over-tighten  a  flared  joint.  Flared  connections 

should always be accessible and must be insulated to 

prevent condensation.

Summary of Contents for MWHA009S4-1L

Page 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Page 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Page 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Page 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Page 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Page 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Page 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Page 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Page 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Page 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Page 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Page 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Page 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Page 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Page 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Page 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Page 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Page 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Page 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Page 20: ...20...

Reviews: