background image

9

pump has been installed, it must be checked to 

ensure proper operation. This check is part of the 

start­up process which must be done by the installing 

contractor.

IMPORTANT

Drain should have a slope of at least ¼ inch per foot and 

should be approved corrosion-resistant pipe. You must 

confirm operation of every drain and pump in the system 

as part of the commissioning procedure.

CORRECT 

Make sure there are no 

kinks or dent in drain 

hose to ensure proper 

drainage.

Figure 17. Condensate Line

Outdoor Unit Installation

Placement Considerations

Consider the following when positioning the unit:

•  In coastal areas or other places with salty atmosphere 

of sulfate gas, corrosion may shorten the life of the 

unit. In coastal areas, the coil should be cleaned with 

potable water several times per year to avoid corro­

sive buildup (salt).

•   Some localities are adopting sound ordinances based 

on the unit’s sound level registered from the adja­

cent property, not from the property where the unit is 

installed. Install the unit as far as possible from the 

property line.

•  When possible, do not install the unit directly outside 

a window. Glass has a very high level of sound trans­

mission.

•  Install unit level.

Ground

Level

Building Structure

Figure 18. Install Unit Level

•  Choose a place solid enough to bear the weight and 

vibration of the unit, where the operation noise will not 

be amplified.

•  Choose a location where the hot air discharged from 

the unit or the operation noise will not be a nuisance 

to neighbors.

•  Avoid installing the outdoor unit near a bedroom or 

other places where noise may cause a problem.

• 

There must be sufficient space to carry the unit into 

and out of the site.

• 

There  must  be  unobstructed  air  flow  around  the  air 

inlet and the air outlet.

• 

The unit must not be installed in areas where a flam

­

mable gas leak may occur.

•  Install the outdoor unit a minimum of 3 feet (1m) away 

from any antenna, power cord (line), radio, telephone, 

security  system,  or  intercom.  Electrical  interference 

and radio frequencies from any of these sources may 

affect operation.

•  Since water drains from the outdoor unit during vari­

ous stages of operation, do not place anything which 

may be damaged by moisture under the unit.

Direct Sunlight, Rain and Ice Protection

•  If the outdoor unit is subjected to prolong exposure to 

direct sunlight with temperatures over 100°F (38°C) a 

canopy is recommended as illustrated in “Figure 19. 

Outdoor Unit on Pedestal and Protective Canopy”or 

“Figure 20. Dog House­Style Shelter” on page 9.

12 in

305 mm

Air Inlet

Air Outlet

24 in

610 mm

Side View

Front View

Protective canopy

Protective canopy

Pedestal

(stand)

Pedestal

(stand)

Figure 19. Outdoor Unit on Pedestal and Protective 

Canopy

12 in

305 mm

24 in

610 mm

24 in

610 mm

12 in

305 mm

NOTE - Minimum clearances shown.

Figure 20. Dog House-Style Shelter

Summary of Contents for MWHA009S4-1L

Page 1: ...unit assembly must be thoroughly cleaned following final construction clean up All mini split operating conditions must be verified ac cording to these installation instructions MHA Series Units SING...

Page 2: ...umbers Table 2 Component Catalog Number Cross Reference Product Capacity Voltage Lennox Model Number Catalog Numbers Wall Mounted Indoor Unit 9K 115V MWHA009S4 1L 17K07 Wall Mounted Indoor Unit 12K 11...

Page 3: ...bility properties with mineral based oil and POE oil Polyolester it is not recommended to mix PVE oil with any other type of refrigerant oil Model Number Identification M WH A 009 S 4 1 P Unit Type WH...

Page 4: ...1 2 13 1 2 13 MHA009S4S BOTTOM VIEW FRONT VIEW SIDE VIEW SIDE VIEW 12 5 8 322 11 1 4 286 2 3 8 60 3 5 8 92 DRAIN HOLE bottom of unit 11 3 4 298 Figure 2 9K Outdoor Unit Dimensions Inches mm BOTTOM VIE...

Page 5: ...425 9 1 8 232 5 127 31 5 8 803 7 1 2 191 11 3 4 298 1 3 4 44 Figure 7 12K Indoor Unit Wall Plate Dimensions Inches mm MHWA018S4 Left Rear Hole 2 1 2 in 64 mm diameter Right Rear Hole 2 1 2 in 64 mm d...

Page 6: ...m 10 254 Minimum 10 254 Minimum AIR FLO W AIR FLO W CLEARANCE NOTES FOR MULTIPLE UNITS If the height of the wall C is less than or equal to the height of the smallest unit A the distance from the unit...

Page 7: ...cient space around unit for proper operation and maintenance Install unit a minimum of 3 feet 1m away from any antenna power cord line radio telephone security system or intercom Electrical interferen...

Page 8: ...ded refrigerant piping connections and field provided flexible condensate piping are long enough to enable final field connections after unit is installed on wall mounting plate use field provided tap...

Page 9: ...and vibration of the unit where the operation noise will not be amplified Choose a location where the hot air discharged from the unit or the operation noise will not be a nuisance to neighbors Avoid...

Page 10: ...the outdoor unit as illustrated in Figure 24 Avoid Defrost Water Ice Hazard Air Inlet Air Outlet Figure 22 Outdoor Unit on Brackets above Snow Line Air Outlet Air Inlet 12 in 305 mm 79 in 2007 mm Fig...

Page 11: ...oor Unit to Hanging Brackets If the outdoor unit is installed on field provided wall mounting brackets use lag bolts or equivalent to secure the outdoor unit to the bracket Minimum rear clearance can...

Page 12: ...ections Male to Female Connection Table 5 Refrigerant Piping and Indoor Unit Connection Sizes Size Btuh Liquid Line in Suction Line in 9K 1 4 3 8 12K 1 4 1 2 18K 1 4 1 2 24K 3 8 5 8 A B CANT ON THE OU...

Page 13: ...s Cooling or heating efficiency drops Moisture in the refrigerant circuit may freeze Water may lead to corrosion of parts in the refrigera tion system The line set between the indoor and outdoor units...

Page 14: ...tween indoor and outdoor units Outdoor Unit Refer to unit nameplate for minimum circuit ampacity and maximum over current protection size Make all electrical power wiring connections at the outdoor un...

Page 15: ...AC 4 16AWG 16A 20A Outdoor to Main Power L N and GND 09K 115VAC 3 16AWG 16A Indoor to Outdoor Wiring Communication Power 1 2 3 and GND 12K 115VAC 4 Stranded and unshielded 16AWG 15A 20A Outdoor to Mai...

Page 16: ...4 Note Th e progra mmable wired controlle r and L VM use the sam e port CN4 03 CN 2 C N201 NOTE COMPONENT IN DASH LINE IS OPTIONAL OR FIELD WIRING CN402 S5 FOR REMOTE ON OF FACTORY SETTING MODE REMOTE...

Page 17: ...CN 1 CN 2 CN 16 CN 50 CN 30 CN 29 CN 28 OUTDOOR CONTROL TP T5 T3 T4 Figure 37 12K 115VAC Outdoor Unit Wiring Diagram 4 WAY VALVE OU TDOOR FAN CN 7 3 6 CN 31 PAN HEATER CN 15 CN 60 CRANKCASE HEATER CN...

Page 18: ...nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has been corrected 7 Refer to the included user guide to operate the system using...

Page 19: ...ireless remote Double Check Line Set Connections During operation the pressure of the refrigerant circuit will increase This may reveal leaks that were not present during your initial leak check Take...

Page 20: ...20...

Reviews: