background image

be repaired or the "B" vent must be replaced.

2.

Inspection to ascertain that the vent system is clear
and free of obstructions. Any blockage must be
cleared before installing this furnace.

3.

Cleaning the chimney or "B" vent if previously used
for venting a solid fuel burning appliance or fireplace.

4.

Confirming that all unused chimney or "B" vent
connections are properly sealed.

5.

Verification that the chimney is properly lined and
sized per the applicable codes.

Masonry  Chimney:

This furnace can be common vented into an existing

tile lined masonry chimney provided:
1.

The chimney is currently serving at least one
drafthood equipped appliance.

2.

The vent connectors and chimney are sized in
accordance with the applicable sections of the (U.S.)
National   Fuel   Gas   Code   ANSI   Z223.1/NFPA54,
and/or  CSA   B149.1   Natural   Gas   and   Propane
Installation  Codes.
This furnace must 

NOT

 vented 

ALONE

 into an

existing masonry chimney (either tile lined or unlined)
unless the chimney is also lined with either a type B vent
system or a listed single wall, metal lining system. Both
of these systems must be sized in accordance with the
applicable sections of the (U.S.) National  Fuel Gas  Code
ANSI  Z223.1/NFPA54, and/or  CSA  B149.1  Natural  Gas
and  Propane  Installation  Codes.

Before venting this furnace into a chimney, check the

chimney for deterioration and repair if necessary. This
furnace must not be vented into a chimney serving a
separate appliance designed to burn solid fuel. Type"B"
vent connectors must be used on all installations and it
must be sized per the applicable sections of the (U.S.)
National  Fuel  Gas  Code  ANSI  Z223.1/NFPA54, and/or
CSA B149.1 Natural Gas and Propane Installation Codes.

Type  "B"  Vent:

The furnace is also approved for use with a "B" vent

that terminates through the roof. Refer to the applicable
sections of the (U.S.)  National  Fuel  Gas  Code  ANSI
Z223.1/NFPA54, and/or  CSA  B149.1  Natural  Gas  and
Propane  Installation  Codes for proper sizing and set-up
of this furnace with "B" vent for a dedicated vent system
or a common vented system.

Horizontal  Venting:

This furnace is design certified by CSA International

for horizontal venting through an outside wall by use of
one of the following auxiliary draft inducer kits:

Table 4

AUXILIARY DRAFT INDUCERS

Vent Kit MFR

Model

* Furnace Input

Field Controls Co.

SWG-4G

50000, 75000, 100000 or

125000

Tjernlund Products Inc.

SS1 OR SS1C

50000, 75000, 100000 or

125000

GPAK-J

50000, 75000 or 100000

GPAK-1

100000 or 125000

* See rating label on this furnace for input

Vent Length: Max. 60 ft. - Min. 12 ft.

Vent Diameter: 4 in.

Follow instructions included with venting kit for proper installation and setup.

Location  Requirements  for  Horizontal  Venting:

Locate the vent terminal adhering to the following

minimum clearances:
1.

Vent terminal must be located at least one (1') foot
above the grade or at least one (1') foot above the
normal expected snowfall.

2.

Avoid installing vent terminal above public walkways.
If this is not possible, install the terminal at least
seven (7') feet above the walkway.

3.

Vent terminal should be at least four (4') feet to the
side of and at least one (1') foot above doors and
windows.

4.

Vent terminal should be at least three (3') feet above
any forced air inlet located within ten (10') feet.

5.

Vent terminal should be located at least six (6') feet
from the combustion air intake of another appliance.

6.

Vent terminal should be located at least four (4') feet
above any electric or gas meters, regulators, and
relief equipment.

General  Venting  Requirements:

This furnace may be common vented only with other

Category I appliances. Common venting is allowed as
permitted by National and/or local codes. Refer to the
applicable sections of the (U.S.) National Fuel  Gas  Code
ANSI  Z223.1/NFPA54, and/or  CSA  B149.1  Natural  Gas
and  Propane  Installation  Codes for proper sizing and set
up.

The vent must be terminated with a listed vent cap or

roof assembly. This venting must be installed in
accordance with the vent manufacturer's instructions and
be in accordance with all local codes and/or National
Codes. Follow Figure 9 for vent exit options.

The following requirements are provided for a proper

venting system:
1.

Be sure that the chimney flue is clear of any dirt or
debris.

2.

Be sure that the chimney is not servicing an open
fireplace.

3.

Never reduce the pipe size below the outlet size of
the furnace without checking the applicable sections
of the (U.S.)  National   Fuel   Gas   Code   ANSI
Z223.1/NFPA54, and/or CSA B149.1 Natural Gas and
Propane  Installation  Codes.

20541501

 

Issue 0240

 

      Page 13 of 26

Summary of Contents for MPGA 050 B3

Page 1: ...APPLICATION GUIDE GAS FURNACE Fit s All 80 English 02 2004...

Page 2: ......

Page 3: ...and liquids in the vicinity of this or any other appliance Installation and service must be performed by a qualified installer service agency or the gas supplier Installation by an unqualified person...

Page 4: ...or the detection of leaks to check all connections as specified in The Gas Connection section on page 16 of these instructions 6 Always install furnace to operate within the furnace s intended tempera...

Page 5: ......

Page 6: ...s in place or A C evaporator in place When operating the furnace in the heating mode the static pressure and the temperature rise supply air temperature minus return air temperature must be within tho...

Page 7: ...FURNACE WIRING SPECIFICATIONS 20541501 Issue 0240 Page 5 of 26...

Page 8: ...lson Boulevard Arlington VA 22209 or the Canadian installation codes obtainable from Canadian Standards Association 178 Rexdale Boulevard Etobicoke Ontario Canada M9W 1R3 This furnace is designed for...

Page 9: ...e furnace is to be installed in a crawl space consult local codes Use of a concrete pad 1 to 2 thick is recommended If the furnace is to be suspended from the ceiling it will be necessary to use steel...

Page 10: ...on of gas proper venting and maintenance of ambient temperature at safe limits under normal conditions of use The furnace shall be located so as not to interfere with proper circulation of air In addi...

Page 11: ...000 60 000 80 000 100 000 120 000 140 000 160 000 100 100 100 100 120 140 160 12 12 12 12 13 14 15 EXAMPLE 50 000 Btuh Furnace 10 000 Btuh Water Heater 60 000 Btuh Total Input 12 Dia Round Duct If ve...

Page 12: ...n of rectangular air ducts must not be less than 3 inches Each opening must have a free area of not less than one square inch per 2 000 Btu per hour of total input of all appliances within the Confine...

Page 13: ...re should be at least one 90 air turn between blower and return grille Further reduction in sound can be accomplished by installing acoustical air turning vanes and or lining the inside of the duct wi...

Page 14: ...ace Under no circumstances should the air flow be such that cooled conditioned air can pass over the furnace heat exchanger This will cause condensation in the heat exchanger and possible failure of t...

Page 15: ...use of one of the following auxiliary draft inducer kits Table 4 AUXILIARY DRAFT INDUCERS Vent Kit MFR Model Furnace Input Field Controls Co SWG 4G 50000 75000 100000 or 125000 Tjernlund Products Inc...

Page 16: ...ssure switch tubing from the combustion blower 3 Remove the four 4 screws that secure the combustion blower adaptor plate to the flue collector box taking care to support the blower assembly so that i...

Page 17: ...ny other gas fired burning appliance to their previous conditions of use ELECTRICAL CONNECTIONS When installed the furnace must be electrically grounded in accordance with local codes or in the absenc...

Page 18: ...ifically for the detection of leaks to check all connections A fire or explosion may result causing property damage personal injury or loss of life The furnace and its individual shutoff valve must be...

Page 19: ...20541501 Issue 0240 Page 17 of 26 THEORY OF OPERATION...

Page 20: ...g completed and the furnace has been properly vented the unit should be started and adjusted for proper operation Check off the following steps as they are completed 1 Be sure all electrical power is...

Page 21: ...of gas flow by using the formula provided below or Table 5 Cubic Ft Hr Number of Dial Revolutions x Cubic Foot Revolution x 3600 Time in seconds Required for Number of Timed Revolutions TABLE 5 Gas R...

Page 22: ...ifold pressure The appropriate manifold pressures based on the elevation and the heating value can be found in Table 7 TABLE 7 High Altitude Manifold Pressure Derate with standard 42 orifice Natural 5...

Page 23: ...h The furnace should be allowed to cool off before attempting to reset the switch Failure to follow these instructions could result in injury due to burns The switch located behind the burner access p...

Page 24: ...SEQUENCE OF OPERATION Direct ignition system control 20541501 Issue 0240 Page 22 of 26...

Page 25: ...This will expose both the burner and flue openings of the primary heat exchangers 6 Vacuum the length of each heat exchanger tube using a straight attachment into the burner openings and the flue ope...

Page 26: ...2 screws located in the blower compartment that secure the blower legs to the blower partition panel 7 Slide the blower forward about two 2 inches This will disengage the rear of the blower legs from...

Page 27: ...TROUBLE SHOOTING With LED Indicator Assistance 20541501 Issue 0240 Page 25 of 26...

Page 28: ...WIRING DIAGRAM 20541501 Issue 0240 Page 26 of 26...

Page 29: ...he CSA International symbols on each nameplate is your assurance that your furnace design meets nationally recognized standards for safety and performance Do not store or use gasoline or other flammab...

Page 30: ...dor of gas is present Use only your hand to adjust the gas control switch never use tools If the switch will not move by hand don t try to repair it call a qualified service technician Force or attemp...

Page 31: ...tat dial or lever to select the temperature you would like the system to maintain Fan Operation You may wish to increase your comfort by setting your system for continuous air circulation of the indoo...

Page 32: ...flashlight will be useful for these inspections Make one inspection prior to the beginning of the heating season and another during the middle Should you observe unusual amounts of any of the followi...

Page 33: ...and place back in furnace To clean a permanent filter shake filter to remove excess dirt and or use a vacuum cleaner Wash filter in soap or detergent water and replace after filter is dry Permanent fi...

Page 34: ...ner Blower Motor Blower Door Shield Top Bottom Blower Wheel Orifice Capacitor Ignitor Blower Support Leg Gas Control Sensor ELECTRICAL GROUP HEAT EXCHANGER GROUP INDUCER GROUP Access Door Primary Heat...

Page 35: ...FURNACE MARKINGS IN FRENCH CONSULT WITH YOUR DEALER OR LOCAL DISTRIBUTOR HAVE AVAILABLE THE MODEL NO AND SERIAL NO LOCATED ON THE UNIT RATING PLATE TO INSURE THE CORRECT FRENCH INSTRUCTION PACKET POUR...

Page 36: ......

Page 37: ...510 88 111 Fax 420 2 579 10 393 e mail janka janka cz LENNOX DISTRIBUTION MOSCOW Tel 7 095 933 29 55 Fax 7 095 926 56 50 e mail lennox dist moscow co ru LENNOXSLOVENSKOs r o Tel 421 7 44 87 19 27 Fax...

Reviews: