Page 30
Intake Piping (FIGURE 25 and FIGURE 26)
The ML196UHE furnace may be installed in either direct
vent or non-direct vent applications. In non-direct vent ap
-
plications, when intake air will be drawn into the furnace
from the surrounding space, the indoor air quality must be
considered and guidelines listed in Combustion, Dilution
and Ventilation Air section must be followed.
Follow the next two steps when installing the unit in Di
-
rect Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct vent
applications (outdoors).
1 -
Use transition solvent cement or a sheet metal screw
to secure the intake pipe to the inlet air connector.
2 - Route piping to outside of structure. Continue with
installation following instructions given in general
guidelines for piping terminations and intake and
exhaust piping terminations for direct vent sections.
Refer to TABLE 13 for pipe sizes.
Follow the next two steps when installing the unit in
Non-
Direct Vent applications
where combustion air is taken
from indoors and flue gases are discharged outdoors.
1 -
Use field-provided materials and the factory-
provided air intake screen to route the intake piping
as shown in FIGURE 27 or FIGURE 28. Maintain
a minimum clearance of 3” (76mm) around the
air intake opening. The air intake opening (with
the protective screen) should always be directed
forward or to either side in the upflow position, and
either straight out or downward in the horizontal
position.
The air intake piping must not terminate
too close to the flooring or a platform. Ensure
that the intake air inlet will not be obstructed by
loose insulation or other items that may clog the
debris screen.
2 - If intake air is drawn from a ventilated attic (FIGURE
29) or ventilated crawlspace (FIGURE 30) the
exhaust vent length must not exceed those listed
in TABLE 14. If 3” diameter pipe is used, reduce
to 2” diameter pipe at the termination point to
accommodate the debris screen.
3 - Use a sheet metal screw to secure the intake pipe
to the connector, if desired.
TYPICAL AIR INTAKE PIPE CONNECTIONS
UPFLOW NON−DIRECT
VENT APPLICATIONS
INTAKE
DEBRIS
SCREEN
(Provided)
NOTE
- Debris screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
Min 2”
FIGURE 27
TYPICAL AIR INTAKE PIPE CONNECTIONS
HORIZONTAL NON−DIRECT VENT APPLICATIONS
(Horizontal Right−Hand Air Discharge Application Shown)
INTAKE
DEBRIS
SCREEN
(Provided)
OR
NOTE
- Debris screen may be positioned straight out
(preferred) or with an elbow rotated to face down.
coupling
PVC pipe
Min 2”
FIGURE 28
Summary of Contents for ML196UH030XE36B