Page 2
SPECIFICATIONS
Gas
Heating
Performance
Model No.
ML196UH
030XE36B
ML196UH
045XE36B
ML196UH
070XE36B
ML196UH
070XE48B
ML196UH
090XE36C
1
AFUE
96%
96%
96%
96%
96%
Input - Btuh
30,000
44,000
66,000
66,000
88,000
Output - Btuh
29,000
42,800
63,900
63,900
85,600
Temperature rise range - °F
25 - 55
35 - 65
35 - 65
30 - 60
45 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
High static - in. w.g.
0.5
0.5
0.5
0.5
0.5
Energy Star
®
Certified
Yes
Yes
Yes
Yes
Yes
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
3/4
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nom. dia. x width - in.
10 x 8
10 x 8
10 x 8
11-1/2 x 10
10 x 8
Motor Type DC Brushless
DC Brushless
DC Brushless
DC Brushless
DC Brushless
Motor output - hp
1/2
1/2
1/2
3/4
1/2
Tons of add-on cooling
1.5 - 3
1.5 - 3
1.5 - 3
2.5 - 4
1.5 - 3
Air Volume Range - cfm
175 - 1435
520 - 1345
550 - 1380
835 - 1855
460 - 1470
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
6.8
6.8
6.8
8.4
6.8
Maximum overcurrent protection
15
15
15
15
15
Shipping Data
lbs. - 1 package
120
124
129
132
142
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
SPECIFICATIONS
Gas
Heating
Performance
Model No.
ML196UH
090XE48C
ML196UH
090XE60C
ML196UH
110XE60C
ML196UH
135XE60D
1
AFUE
96%
96%
96%
96%
Input - Btuh
88,000
88,000
110,000
132,000
Output - Btuh
85,600
85,600
107,200
127,000
Temperature rise range - °F
50 - 80
35 - 65
45 - 75
45 - 75
Gas Manifold Pressure (in. w.g.)
Nat. Gas / LPG/Propane
3.5 / 10
3.5 / 10
3.5 / 10
3.5 / 10
High static - in. w.g.
0.5
0.5
0.5
0.5
Energy Star
®
Certified
Yes
Yes
Yes
Yes
Connections
in.
Intake / Exhaust Pipe (PVC)
2 / 2
2 / 2
2 / 2
2 / 2
Gas pipe size IPS
1/2
1/2
1/2
1/2
Condensate Drain Trap (PVC pipe) - i.d.
3/4
3/4
3/4
3/4
with furnished 90° street elbow
3/4 slip x 3/4 Mipt
with field supplied (PVC coupling) - o.d.
3/4 slip x 3/4 MPT
Indoor
Blower
Wheel nom. dia. x width - in.
10 x 10
11-1/2 x 10
11-1/2 x 10
11-1/2 x 10
Motor Type
DC Brushless
DC Brushless
DC Brushless
DC Brushless
Motor output - hp
3/4
1
1
1
Tons of add-on cooling
2.5 - 4
3-5
3 - 5
3-5
Air Volume Range - cfm
760 - 1740
1050 - 2105
1055 - 2220
1310 - 2400
Electrical Data
Voltage
120 volts - 60 hertz - 1 phase
Blower motor full load amps
8.4
10.9
10.9
10.9
Maximum overcurrent protection
15
15
15
15
Shipping Data
lbs. - 1 package
152
152
164
174
NOTE - Filters and provisions for mounting are not furnished and must be field provided.
1
Annual Fuel Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations. Isolated combustion system rating for non-weatherized furnaces.
Summary of Contents for ML196UH030XE36B
Page 57: ...Page 57...