background image

Page 14

Flushing Line Set and Indoor Coil

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove 

sembly.

C

Using two wrenches, disconnect liquid line from liquid 

ing. T

cess.

D

Remove and discard fixed orifice, valve stem assembly if present and

Teflon

®

 washer as illustrated above.

E

Use a field-provided fitting to temporarily reconnect the liquid line to the

indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE

REMOVAL PROCEDURE (UNCASED

COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL

PROCEDURE (UNCASED COIL SHOWN)

TWO PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER

LINE

CHECK

EXPANSION

VALVE

TEFLON®

RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

A

On fully cased coils, remove the coil access and plumbing panels.

B

Remove any shipping clamps holding the liquid line and distributor

assembly.

C

Disconnect  the  equalizer  line  from  the  check  expansion  valve

equalizer line fitting on the vapor line.

D

Remove the vapor line sensing bulb.

E

Disconnect the liquid line from the check expansion valve at the liquid

line assembly.

F

Disconnect the  check expansion valve from the liquid line orifice

housing. Take care not to twist or damage distributor tubes during this

process.

G

Remove and discard check expansion valve and the two Teflon

®

 rings.

H

Use a field-provided fitting to temporary reconnect the liquid line to the

indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

INVERTED CYLINDER

CONTAINS CLEAN

HCFC22* TO BE USED

FOR FLUSHING.

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK

RETURN

CLOSED

OPENED

RECOVERY CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

VAPO
R

LIQUID

1

A

Inverted HCFC-22 cylinder with clean refrigerant* to the vapor service

valve.

B

HCFC-22 gauge set (low side) to the liquid line valve.

C

HCFC-22 gauge set center port to inlet on the recovery machine with an

empty recovery tank to the gauge set.

D

Connect recovery tank to recovery machines per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR

FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

A

Set  the  recovery  machine  for  liquid  recovery  and  start  the

recovery machine.  Open  the  gauge  set  valves  to  allow  the

recovery machine to pull a vacuum on the existing system line

set and indoor unit coil.

B

Invert the cylinder of clean HCFC-22* and open its valve to allow

liquid refrigerant to flow into the system through the vapor line

valve. Allow the refrigerant to pass from the cylinder and through

the line set and the indoor unit coil before it enters the recovery

machine.

C

After all of the liquid refrigerant has been recovered, switch the

recovery machine to vapor recovery so that all of the HCFC-22

vapor is  recovered.  Allow  the  recovery  machine  to  pull  the

system down to 0.

D

Close the valve on the inverted HCFC-22 drum and the gauge

set valves. Pump the remaining refrigerant out of the recovery

machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the

same amount of clean refrigerant* that previously charged the

system. Check the charge in the flushing cylinder before

proceeding.

1A

2

3

1B

*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system

has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.

FIGURE 8. Removing Metering Device and Flushing

Summary of Contents for ML18XC2 Series

Page 1: ...cal Unit Parts Arrangement 5 Operating Gauge Set and Service Valves 5 Unit Placement 7 Removing and Installing Louvered Panels 8 New or Replacement Line Set 9 Brazing Connections 11 Flushing Line Set...

Page 2: ...the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification Nominal Cooling Capacity 024 2 ton...

Page 3: ...NNECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3...

Page 4: ...t ampacity MCA 14 6 20 2 26 2 32 2 Compressor Rated load amps 10 9 15 4 19 9 23 7 Locked rotor amps 61 92 127 151 Power factor 0 97 0 94 0 93 0 92 Outdoor Fan Motor Full load amps 1 1 1 4 2 6 Locked R...

Page 5: ...ugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2 NM Machine screws 10 28 ft lb 3 NM Compressor bol...

Page 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Page 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Page 9: ...ge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended topping off POE oils are M...

Page 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Page 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Page 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 15: ...reads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Page 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Page 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Page 19: ...Y1 Y2 C K1 S4 R C R W2 W1 Y2 C BLACK BLUE YELLOW Y Y1 G G W INDOOR UNIT TB1 THERMOSTAT A2 EL196E ML180E ML193E EL180E EL195E ML196E R W2 W1 G C BLACK BLUE YELLOW Y1 Y2 INDOOR UNIT A92 TB1 DS O W914 W9...

Page 20: ...to shut off compressor operation The auto reset switch closes when the compressor cas ing temperature falls to 151 187 F 66 C 86 C and the compressor is re energized This single pole single throw SPS...

Page 21: ...sure no obstructions restrict airflow to the outdoor unit Grass clippings leaves or shrubs crowding the unit can cause the unit to work harder and use more energy Keep shrubbery trimmed away from the...

Page 22: ...all factory and field installed wiring for loose connections 3 After evacuation is complete open the liquid line and suction line service valves to release the refrigerant charge contained in outdoor...

Page 23: ...pply Air Temperature Ambient Temperature Return Air Temperature System Refrigerant Charge Refer to manufacturer s information on unit or installation instructions for required subcooling and approach...

Reviews: