background image

8

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

J.

 

Assemble vent run to exterior wall -

 If not 

previously measured, locate the center of the 

vent at the exterior wall. Prepare an opening as 

described in 

Step B

.  Assemble the vent system 

to point where the terminus of the last section is 

located relative to the exterior surface to which 

the termination is to be attached as shown in

 

Figure 28 and Table 10 on Pages 8 and 9

If the terminus of the last section is not within 

this distance, use the 

telescopic vent section 

SV4.5LA, 

as  the  last  vent  section.  For  wall 

thicknesses greater than that shown in 

Figure 

28

, refer to 

Table 10 on Page 9

. This Table 

lists  the additional venting components needed 

(in addition to the termination and adapter) for 

a particular range of wall thicknesses.

K.

 

Attach  termination  adapter  -

  Attach  the 

adapter (adapter - SV4.5RCH - provided with the  

termination) to the vent section or telescoping 

vent section), elbow or appliance collar as shown 

in 

Figure 27

  

in the same manner as any SV4.5 

vent component (refer to 

Step E

).

L.

 

Install Firestop/Spacer at exterior wall -

 

When using the termination, install  SV4.5HF 

(Secure Vent), SF4.5HF (Secure Flex) Firestop/

Spacer over the opening at the exterior side 

of the framing, long side up, with the 3 inch 

spacer clearance at the top as shown in 

Figure 

27

, and nail into place.

(The Firestop/Spacer may also be installed over 

the opening at the interior side of framing).

M.  Install  the  Termination  (SV4.5HT-2  or  

SV4.5HTSS) 

For  the  last  step,  from  outside  the  exterior 

wall, slide the collars of the termination onto 

the adapter (the outer inside the outer and the 

inner  ouside  the  inner)  until  the  termination 

seats against the exterior wall surface to which 

it will be attached.  Orient the housing of the 

termination with the arrow pointed upwards.  

Secure the termination to the exterior wall.  

The 

horizontal termination must not be recessed 

into the exterior wall or siding by more than 

the -/4" (32 mm)

 as shown in 

Figure 28

.

Horizontal terminations have been designed to perform in a wide range of weather condi-

tions.  Our terminations meet or exceed industry standards.

When selecting the locations of your horizontal terminations, do not place the termina-

tion where water from eaves and adjoining rooflines may create a heavy flow of cascad-

ing water onto the termination cap.  If the cap must be placed where the possibility of 

cascading water exists, it is the responsibility of the builder to direct the water away 

from the termination cap by using gutters or other means.

Take care to carefully follow the installation instructions for the termination, including 

the use of silicone caulking where required.

Figure 28

Figure 27 -

 INSTALLING HORIZONTAL TERMINATION

IMPORTANT:  The vent termination is hot 

while  in  operation  and  for  a  period  of 

time following the use of the fireplace.  

To  prevent  contact  with  hot  surfaces, 

we  recommend  the  use  of  a  Termina-

tion Guard. See Page 32. This can be 

purchased at your local dealer.

Siding

Stucco

-/4"  Maximum  Recess  of

the  Square  Termination  into

Exterior  Finishing  Material

Exterior Surface of

Framing

6 in. to 9-/4 in.

(52 to 235 mm)**

Exterior Surface of Siding

Interior Surface of

Finished Wall

Maximum  wall thickness

0 in.(254 mm)**

SV4.5HT-2

Square Termination

Shown

Maximum  Extent  of

Vent  Run  Sections

Relative  to  Exterior

Surface  of  Framing

Last Vent Section. Use

T e l e s c o p i c   V e n t

Section (SV4.5LA), If

Necessary

Adapter

SV4.5RCH

SV4.5HT-2

Square Termination

Shown

Venting Connection and Exterior Wall Recessing

of the Horizontal Termination

*Use silicone caulking to

seal the top and sides of

the termination, up to the

underlayment, stucco, or

masonry wall surface.

**For thicknesses greater

    than 0”, see Table 0.

*Caulk

*Caulk

Firestop/Spacer (SV4.5HF) shown

on the exterior side of the wall. It

may also be installed on the

interior side.

Typical

Termination

Shown

7"

(78)

5-/8"

(30 mm)

2-/8"

(308 mm)

Note: Centerline of Vent Piping is

NOT the Same as the Centerline of

the Frame Opening.

6 to 48 inch Vent Section,

Telescopic vent section,

Elbow or Appliance Collar

See Figure 2 on page 9

for Min. Distance to Base

of Appliance.

Base of Appliance

3"

(76 mm)

"

(25.4 mm)

Adapter

SV4.5RCH

0-/2"

(267 mm)

Summary of Contents for Merit MLDVT-45NE

Page 1: ...FE DIRECT VENT MLDVT 30 35 40 45 SERIES Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not light any ap...

Page 2: ...owing vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and Z FLEX Model GA Venting Systems listed...

Page 3: ...pane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Do not use these appliances if any part has...

Page 4: ...re Tap Manifold Burner Stage Terminal Ground TP PILOT OUT VENT LO TH TP TH TP HI IN IN Regulator Mounting Screw Cold Climate Insulation For cold climate installations seal all cracks around the applia...

Page 5: ...bustible and combustible exterior sidewall This distance may be decreased to 2 5 mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Be aware that this is a heat produc...

Page 6: ...e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 f o t h g i e h a n i h t i w m c 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 f o t h g...

Page 7: ...sides as detailed inTable6 withthefollowingexception When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit...

Page 8: ...box floor securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 46 on Page 30 TYPICAL INSTAL...

Page 9: ...P VENT WITH ONE 90 ELBOW Framing should be constructed of 2x4 or larger lumber Inches mm D 30 D is the required framing depth dimension when the finish material drywall thickness is 2 in 3mm A 2 Frami...

Page 10: ...rlocalcode requirements i e arebelowgradepenetrations of the gas line allowed etc IMPORTANT Ifpropaneisused beawarethat if tank size is too small i e under 100 lbs if this is the only gas appliance in...

Page 11: ...ructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes theseinstructions thecurrentNational Fuel Gas Code ANSI Z223 1 in the USA or th...

Page 12: ...5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Page 13: ...are available in net lengths of 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm Refer to the Vent Section Length Charts on Page 12 for an aidinselectinglengthcombinations El...

Page 14: ...supplied with the flashing over the vent flashing joint See Figure 21 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the ad justingscrew Applynon combus...

Page 15: ...ERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 uWhenusingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF A Vent Restrictor as shown in Figure 14 Page 11...

Page 16: ...2 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 60 ft 18 3 m Max Figure 25 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure...

Page 17: ...ously connected vent sections See Figure 17 on Page 13 I Continue installation of horizontal inclined sections Continue with the installation of the straightventsectionsinhorizontal inclinedrun as des...

Page 18: ...nations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not plac...

Page 19: ...S THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 Use Table 10 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES Figur...

Page 20: ...6 096 m Max Figure 31 Top Vent TWO 90 DEGREE ELBOWS See Table 10 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES...

Page 21: ...Figure 29 V H H V vWall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF vWall Firestop...

Page 22: ...mperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure th...

Page 23: ...he electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 12 on Page 9 3 Removethe coverplate sknockoutandthen feedthepowersupplywirethroughtheknocko...

Page 24: ...artment Accessthevalvecompartmentbyremovingthe lower control compartment panel see Figure 38 by lifting and pulling the panel forward The panel is mounted on supporting tabs at the extreme right and l...

Page 25: ...e gas lines are tested and leak free be sure to rinse off the leak testing solution D Observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly acro...

Page 26: ...ted Dis tribute these pieces over the surface of the burner as shown in Figures 44 and 45 Do not use more than is necessary Ensure that the main burner slots remain uncovered by the ember material Pos...

Page 27: ...35 H7666 WARNING Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Left Rear Log Bracket Right Rear Log Bracket Rockwool Do Not Place...

Page 28: ...ot Place Rockwool Over Burner Slots Log Rack Volcanic Stone Right Rear Log Bracket 1 Position on the left rear log bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log...

Page 29: ...29 NOTES...

Page 30: ...with the bottom of the door held away from the fireplace Figure 46 Hook the top flange of the door frame over the top of the firebox frame 6 Let the bottom of the door frame swing gentlyintowardsthefi...

Page 31: ...ont glass panel are in place and sealed during adjustment 1 Locate adjustment rod and adjust air shutter to the standard set ting as shown in Figure 49 adjustment rod is located in the lower control c...

Page 32: ...7 7 B F 5 4 V S e l b a t s u j d A 2 1 2 1 o t 2 1 7 g n i h s a l F 1 8 L 7 7 6 C S 5 4 V S 6 s r a l l o C m r o t S x o b s r a l l o c 6 4 2 2 H F H 5 4 V S k c a p 0 1 r e c a p S p o t s e r i...

Page 33: ...o f n i m r e T l a c i t r e V x e l F h t i w 2 1 6 o t t a l f d i g i r f o n o i t c e s r e t p a d A r a l l o c t r o p p u s f o o r t n e v d n a g n i h s a l f f o o r y l b m e s s a r a...

Page 34: ...on kit when performing any gas conversion Gas Conversion Kits Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructionsandallappli...

Page 35: ...o pressure regula tor mounting screws Remove the pressure regulatoranddiaphragm Discardallremoved components Ensure the provided diaphragm is installed properly onto the replacement pressure regulator...

Page 36: ...pe joint compounds on flare fittings PILOT OUT VENT LO TH TP TH TP HI IN IN Pilot Stage Terminal Pressure Tap Inlet Pilot Gas Outlet Supply Gas Inlet Pressure Tap Manifold Burner Stage Terminal Ground...

Reviews: