background image

6

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Maintain a minimum " (25 mm) clearance to 

combustibles on the vertical sections. Clear-

ances for the horizontal runs are; 3" (76 mm) 

on top, " (25 mm) on sides, and " (25 mm) 

at the bottom.

B.

 

Frame exterior wall opening -

 

Locate  the  center  of  the  vent  outlet  on 

the  exterior  wall  according  to  the  dimen-

sions  shown  in 

Figure  12  on  Page  9.

  Cut 

and/or  frame  an  opening,  10-1/2"  x  12  1/8"  

(267 mm x 308mm) inside dimensions, about 

this center. 

C.

 

Frame ceiling opening -

 If the vertical route 

is to penetrate a ceiling, use plumb line to locate 

the center above the appliance. Cut and/or frame 

an opening, 10-1/2" x 10-1/2" (267 mm x 267 

mm) inside dimensions, about this center (refer 

to 

Figure 16 on Page 3

).

u

 Ceiling 

Firestop / Spacer 

(SV4.5VF)

v

Wall Firestop/

Spacer (SV4.5HF)

u

 

When using Secure Flex, use Firestop / Spacer SF4.5VF

v

 

When using Secure Flex, use Firestop / Spacer SF4.5HF

V

H

H

V

Example: 

 If 20 feet total (H+H

1

horizontal vent run is needed, then  

4 feet minimum of (V) vertical vent 

will be required.

This table shows a 1(V) to 5(H) 

ratio.    For  every  1  foot  of  (V) 

vertical,  you  are  allowed  5  feet 

of  (H+H

1

)  horizontal  run  up  to 

a maximum total horizontal run 

of 20 feet.

An elbow is acceptable as 1 foot 

of  vertical  rise  except  where 

an  elbow  is  the  only  vertical 

component  in  the  system.  See 

Figure 29

.

Table B

H + 

H

 Maximum

 

V Minimum

feet

(meter)

feet

(meter)

5

(.524)

Elbow Only

5

(.524)

(0.305)

0

(3.048)

2

(0.60)

5

(4.572)

3

(0.94)

20

(6.096)

4

(.29)

H + H

 = 20 feet (6.096 m) Max.

V + V

 + H + H

 = 60 ft. (8.3 m) Max.

Figure 25 - Top Vent - THREE ELBOWS

VERTICAL VENT FIGURES/TABLES 

(CONTINUED)

HORIZONTAL (OUTSIDE WALL) 

TERMINATION SYSTEM

Figure 26 on Page 7, and Figures 27 to 32 on 

Pages 8 to 2 

and their associated  Horizontal 

Vent  Table  illustrate  the  various  horizontal 

venting  configurations  that  are  possible  for 

use with these appliances.  

Secure Vent

 pipe 

applications are shown in these Figures; 

Secure 

Flex

 pipe may also be used. A Horizontal Vent 

Table summarizes each system’s minimum and 

maximum vertical and horizontal length values 

that can be used to design and install the vent 

components in a variety of applications. 

Both of these horizontal vent systems terminate 

through an outside wall. Building Codes limit or 

prohibit terminating in specific areas. Refer to 

Figure 6

 

on Page 6 

for location guidelines.

Secure Vent

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connection, (

refer 

to 

Figure 17

 

on Page 3

).  All of the appli-

ances covered in this document are fitted with 

collars having locking inclined channels. The 

dimpled end of the vent components fit over 

the appliance collar to create the positive twist 

lock connection.

A.

 

Plan the vent run -

 

Analyze  the  vent  routing  and  determine  the 

types  and  quantities  of  sections  required       

4-1/2" (114 mm), 10-1/2" (267 mm), 22-1/2" 

(572 mm), 34-1/2" (876 mm) and 46-1/2" (1181 

mm) net section lengths are available.  Plan the 

vent lengths so that a joint does not occur at the 

intersection of ceiling or roof joists. Make allow-

ances for elbows as indicated in 

Figure 19

.

Summary of Contents for Merit MLDVT-45NE

Page 1: ...FE DIRECT VENT MLDVT 30 35 40 45 SERIES Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not light any ap...

Page 2: ...owing vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and Z FLEX Model GA Venting Systems listed...

Page 3: ...pane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Do not use these appliances if any part has...

Page 4: ...re Tap Manifold Burner Stage Terminal Ground TP PILOT OUT VENT LO TH TP TH TP HI IN IN Regulator Mounting Screw Cold Climate Insulation For cold climate installations seal all cracks around the applia...

Page 5: ...bustible and combustible exterior sidewall This distance may be decreased to 2 5 mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Be aware that this is a heat produc...

Page 6: ...e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 f o t h g i e h a n i h t i w m c 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 f o t h g...

Page 7: ...sides as detailed inTable6 withthefollowingexception When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit...

Page 8: ...box floor securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 46 on Page 30 TYPICAL INSTAL...

Page 9: ...P VENT WITH ONE 90 ELBOW Framing should be constructed of 2x4 or larger lumber Inches mm D 30 D is the required framing depth dimension when the finish material drywall thickness is 2 in 3mm A 2 Frami...

Page 10: ...rlocalcode requirements i e arebelowgradepenetrations of the gas line allowed etc IMPORTANT Ifpropaneisused beawarethat if tank size is too small i e under 100 lbs if this is the only gas appliance in...

Page 11: ...ructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes theseinstructions thecurrentNational Fuel Gas Code ANSI Z223 1 in the USA or th...

Page 12: ...5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Page 13: ...are available in net lengths of 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm Refer to the Vent Section Length Charts on Page 12 for an aidinselectinglengthcombinations El...

Page 14: ...supplied with the flashing over the vent flashing joint See Figure 21 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the ad justingscrew Applynon combus...

Page 15: ...ERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 uWhenusingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF A Vent Restrictor as shown in Figure 14 Page 11...

Page 16: ...2 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 60 ft 18 3 m Max Figure 25 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure...

Page 17: ...ously connected vent sections See Figure 17 on Page 13 I Continue installation of horizontal inclined sections Continue with the installation of the straightventsectionsinhorizontal inclinedrun as des...

Page 18: ...nations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not plac...

Page 19: ...S THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 Use Table 10 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES Figur...

Page 20: ...6 096 m Max Figure 31 Top Vent TWO 90 DEGREE ELBOWS See Table 10 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES...

Page 21: ...Figure 29 V H H V vWall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF vWall Firestop...

Page 22: ...mperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure th...

Page 23: ...he electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 12 on Page 9 3 Removethe coverplate sknockoutandthen feedthepowersupplywirethroughtheknocko...

Page 24: ...artment Accessthevalvecompartmentbyremovingthe lower control compartment panel see Figure 38 by lifting and pulling the panel forward The panel is mounted on supporting tabs at the extreme right and l...

Page 25: ...e gas lines are tested and leak free be sure to rinse off the leak testing solution D Observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly acro...

Page 26: ...ted Dis tribute these pieces over the surface of the burner as shown in Figures 44 and 45 Do not use more than is necessary Ensure that the main burner slots remain uncovered by the ember material Pos...

Page 27: ...35 H7666 WARNING Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Left Rear Log Bracket Right Rear Log Bracket Rockwool Do Not Place...

Page 28: ...ot Place Rockwool Over Burner Slots Log Rack Volcanic Stone Right Rear Log Bracket 1 Position on the left rear log bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log...

Page 29: ...29 NOTES...

Page 30: ...with the bottom of the door held away from the fireplace Figure 46 Hook the top flange of the door frame over the top of the firebox frame 6 Let the bottom of the door frame swing gentlyintowardsthefi...

Page 31: ...ont glass panel are in place and sealed during adjustment 1 Locate adjustment rod and adjust air shutter to the standard set ting as shown in Figure 49 adjustment rod is located in the lower control c...

Page 32: ...7 7 B F 5 4 V S e l b a t s u j d A 2 1 2 1 o t 2 1 7 g n i h s a l F 1 8 L 7 7 6 C S 5 4 V S 6 s r a l l o C m r o t S x o b s r a l l o c 6 4 2 2 H F H 5 4 V S k c a p 0 1 r e c a p S p o t s e r i...

Page 33: ...o f n i m r e T l a c i t r e V x e l F h t i w 2 1 6 o t t a l f d i g i r f o n o i t c e s r e t p a d A r a l l o c t r o p p u s f o o r t n e v d n a g n i h s a l f f o o r y l b m e s s a r a...

Page 34: ...on kit when performing any gas conversion Gas Conversion Kits Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructionsandallappli...

Page 35: ...o pressure regula tor mounting screws Remove the pressure regulatoranddiaphragm Discardallremoved components Ensure the provided diaphragm is installed properly onto the replacement pressure regulator...

Page 36: ...pe joint compounds on flare fittings PILOT OUT VENT LO TH TP TH TP HI IN IN Pilot Stage Terminal Pressure Tap Inlet Pilot Gas Outlet Supply Gas Inlet Pressure Tap Manifold Burner Stage Terminal Ground...

Reviews: