background image

4

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

If the vent system extends more than 5 feet 

(1.5m) above the roof flashing, stabilizers may 

be necessary. Additional screws may be used 

at section joints for added stability. Guide wires 

may be attached to the joint for additional sup-

port on multiple joint configurations.

G.

 

Continue installation of horizontal/inclined 

sections -

 Continue with the installation of the 

straight vent sections in horizontal/inclined run 

as described in 

Step C.

 Install support straps 

every 5 ft. (1.52 m) along horizontal/inclined 

vent runs using conventional plumber’s tape. 

See Page 17, Figure 26. It is very important 

that the horizontal/inclined run be maintained 

in a straight (no dips) and recommended to be 

in a slightly elevated plane, in a direction away 

from the fireplace of 1/4 " rise per foot (20 mm 

per meter) which is ideal

, though rise per foot 

run ratios that are smaller are acceptable all the 

way down to at or near level

.

  Use a carpenter’s 

level to measure from a constant surface and 

adjust the support straps as necessary. 

E.

 

Support the vertical vent run sections -

Note - 

Proper venting support is very important. 

The weight of the vent must not be supported 

by the fireplace in any degree.

Support  the  vertical  portion  of  the  venting 

system every 8 feet (2.4m) above the fireplace 

vent outlet. 

One method of support is by utilizing field pro-

vided support straps (conventional plumber's 

tape).  Secure the plumber's tape to the framing 

members with nails or screws.

 

Loop the tape 

around the vent, securing the ends of the tape 

to the framing. If desired, sheet metal screws #6 

x 1/2" length may be used to secure the support 

straps to the vent pipe.  Refer to 

Figure 18

F. Change vent direction to horizontal/inclined 

run -

 At transition from or to a horizontal/in-

clined run, install the SV4.5E45 and SV4.5E90 

elbows in the same manner as the straight vent 

sections. The elbows feature a twist section to 

allow them to be routed about the center axis 

of their initial collar section to align with the 

required direction of the next vent run element. 

Twist elbow sections in a clockwise direction 

only so as to avoid the possiblity of unlocking 

any of the previously connected vent sections.

 

See 

Figure 19

.

J. Install the storm collar -

 Install the storm 

collar,  supplied  with  the  flashing,  over  the 

vent/flashing joint. See 

Figure 21. 

Loosen the 

storm collar screw. Slide collar down until it 

meets the top of the flashing. Tighten the ad-

justing screw. Apply non-combustible caulking 

or mastic around the circumference of the joint 

to provide a water tight seal.

K. Install the vertical termination - 

The final 

step involves installation of the SV4.5CGV-1 

Vertical Termination.  Extend the vent sections 

to  the  height  as  shown  in  the  "Vertical  vent 

termination section" in 

Figure 4 

on 

Page 5

.  

The SV4.5CGV-1 Vertical Termination 

(Figure 

22)

 can be installed  in the exact same fashion 

as any other 

Secure Vent

 section. Align the 

termination  over  the  end  of  the  previously 

installed section, adjusting the radial alignment 

until the four locking dimples of the termination 

are aligned with the inlets of the four incline 

channels of the last vent section.  Push the ter-

mination down until it fully engages, then twist 

the termination clockwise running the dimples 

down and along the incline channels until they 

are seated at the end of the channels.

I.

 

Install the roof flashing - 

Extend the vent 

sections through the roof structure. Install the 

roof flashing over the vent section and posi-

tion such that the vent column rises vertically 

(use carpenters level) (

Figure 21 

). Nail along 

perimeter to secure flashing or adjust roofing 

to overlap the flashing edges at top and sides 

only and trim where necessary. Seal the top 

and both sides of the flashing with waterproof 

caulking.

Figure 19

7-5/8”

(194 mm)

4-13/16 

(122 mm)

Swivel Joint

(360° swivel)

SV4.5E45

45° Elbow)

Swivel Joint

(360° swivel)

SV4.5E90

90° Elbow)

(206 mm)

8-/8"

Framing Dimensions for Roof

Inches (millimeters)

Pitch

C

D

0/2

0-/2 in.

(267 mm)

0-/2 in.

(267 mm)

6/2

0-/2 in.

(267 mm)

2 in.

(305 mm)

2/2

0-/2 in.

(267 mm)

7 3/4 in.

(45 mm)

C

D

Figure 20 

- Roof Framing

VERTICAL VENT FIGURES/TABLES 

Note:

  

Secure  Vent 

 (rigid vent pipe)  is shown 

in the Figures; 

Secure Flex

 (flexible vent pipe) 

may also be used.

Figure 21

Figure 22

WARNING:  UNDER  NO  CIRCUM-

STANCES, MAY SEPARATE SECTIONS 

OF  CONCENTRIC  FLEXIBLE  VENT 

PIPE BE JOINED TOGETHER.

Storm

Collar

Flashing

It is important to maintain the required clear-

ances to combustibles: 1" (25 mm) at all sides 

for all vertical runs; and 3" (76 mm) at the top, 

1" (25 mm) at sides, and 1" (25 mm) at the 

bottom for all horizontal/inclined runs.

H.

 

Frame roof opening -

 Identify location for 

vent at the roof. Cut and/or frame opening per 

Roof Framing Chart (

Figure 20 )

.

Summary of Contents for Merit MLDVT-45NE

Page 1: ...FE DIRECT VENT MLDVT 30 35 40 45 SERIES Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not light any ap...

Page 2: ...owing vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and Z FLEX Model GA Venting Systems listed...

Page 3: ...pane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Do not use these appliances if any part has...

Page 4: ...re Tap Manifold Burner Stage Terminal Ground TP PILOT OUT VENT LO TH TP TH TP HI IN IN Regulator Mounting Screw Cold Climate Insulation For cold climate installations seal all cracks around the applia...

Page 5: ...bustible and combustible exterior sidewall This distance may be decreased to 2 5 mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Be aware that this is a heat produc...

Page 6: ...e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 f o t h g i e h a n i h t i w m c 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 f o t h g...

Page 7: ...sides as detailed inTable6 withthefollowingexception When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit...

Page 8: ...box floor securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 46 on Page 30 TYPICAL INSTAL...

Page 9: ...P VENT WITH ONE 90 ELBOW Framing should be constructed of 2x4 or larger lumber Inches mm D 30 D is the required framing depth dimension when the finish material drywall thickness is 2 in 3mm A 2 Frami...

Page 10: ...rlocalcode requirements i e arebelowgradepenetrations of the gas line allowed etc IMPORTANT Ifpropaneisused beawarethat if tank size is too small i e under 100 lbs if this is the only gas appliance in...

Page 11: ...ructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes theseinstructions thecurrentNational Fuel Gas Code ANSI Z223 1 in the USA or th...

Page 12: ...5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Page 13: ...are available in net lengths of 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm Refer to the Vent Section Length Charts on Page 12 for an aidinselectinglengthcombinations El...

Page 14: ...supplied with the flashing over the vent flashing joint See Figure 21 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the ad justingscrew Applynon combus...

Page 15: ...ERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 uWhenusingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF A Vent Restrictor as shown in Figure 14 Page 11...

Page 16: ...2 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 60 ft 18 3 m Max Figure 25 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure...

Page 17: ...ously connected vent sections See Figure 17 on Page 13 I Continue installation of horizontal inclined sections Continue with the installation of the straightventsectionsinhorizontal inclinedrun as des...

Page 18: ...nations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not plac...

Page 19: ...S THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 Use Table 10 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES Figur...

Page 20: ...6 096 m Max Figure 31 Top Vent TWO 90 DEGREE ELBOWS See Table 10 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES...

Page 21: ...Figure 29 V H H V vWall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF vWall Firestop...

Page 22: ...mperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure th...

Page 23: ...he electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 12 on Page 9 3 Removethe coverplate sknockoutandthen feedthepowersupplywirethroughtheknocko...

Page 24: ...artment Accessthevalvecompartmentbyremovingthe lower control compartment panel see Figure 38 by lifting and pulling the panel forward The panel is mounted on supporting tabs at the extreme right and l...

Page 25: ...e gas lines are tested and leak free be sure to rinse off the leak testing solution D Observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly acro...

Page 26: ...ted Dis tribute these pieces over the surface of the burner as shown in Figures 44 and 45 Do not use more than is necessary Ensure that the main burner slots remain uncovered by the ember material Pos...

Page 27: ...35 H7666 WARNING Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Left Rear Log Bracket Right Rear Log Bracket Rockwool Do Not Place...

Page 28: ...ot Place Rockwool Over Burner Slots Log Rack Volcanic Stone Right Rear Log Bracket 1 Position on the left rear log bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log...

Page 29: ...29 NOTES...

Page 30: ...with the bottom of the door held away from the fireplace Figure 46 Hook the top flange of the door frame over the top of the firebox frame 6 Let the bottom of the door frame swing gentlyintowardsthefi...

Page 31: ...ont glass panel are in place and sealed during adjustment 1 Locate adjustment rod and adjust air shutter to the standard set ting as shown in Figure 49 adjustment rod is located in the lower control c...

Page 32: ...7 7 B F 5 4 V S e l b a t s u j d A 2 1 2 1 o t 2 1 7 g n i h s a l F 1 8 L 7 7 6 C S 5 4 V S 6 s r a l l o C m r o t S x o b s r a l l o c 6 4 2 2 H F H 5 4 V S k c a p 0 1 r e c a p S p o t s e r i...

Page 33: ...o f n i m r e T l a c i t r e V x e l F h t i w 2 1 6 o t t a l f d i g i r f o n o i t c e s r e t p a d A r a l l o c t r o p p u s f o o r t n e v d n a g n i h s a l f f o o r y l b m e s s a r a...

Page 34: ...on kit when performing any gas conversion Gas Conversion Kits Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructionsandallappli...

Page 35: ...o pressure regula tor mounting screws Remove the pressure regulatoranddiaphragm Discardallremoved components Ensure the provided diaphragm is installed properly onto the replacement pressure regulator...

Page 36: ...pe joint compounds on flare fittings PILOT OUT VENT LO TH TP TH TP HI IN IN Pilot Stage Terminal Pressure Tap Inlet Pilot Gas Outlet Supply Gas Inlet Pressure Tap Manifold Burner Stage Terminal Ground...

Reviews: