background image

3

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Inlet Gas Supply Pressure 

(all models)

Fuel #

Minimum

Maximum

Natural Gas

4.5" WC

(.2 kPa)

0.5" WC

(2.6 kPa)

Propane

.0" WC

(2.74 kPa)

3.0" WC

(3.23 kPa)

Table 3

Gas Pressure - All Models

Tables 3 and 4  

show the appliances' gas 

pressure requirements:

Test gauge connections are provided on the 

front of the millivolt and electronic gas control 

valve (identified IN for the inlet and OUT for 

the manifold side).  The control valves have a 

3/8" (10mm) NPT thread inlet and outlet side 

of the valve.

Gas Valve Diagrams

See 

Figure 1

 for Millivolt models and 

Figure 2 

For Electronic Models.

These appliances must not be connected to a 

chimney or flue serving a separate solid fuel 

burning appliance.

Orifice Sizes -  Sea Level to High Altitude

(All Models)

These appliances are tested and approved for 

installation at elevations of 0-4500 feet (0-1372 

meters)  above  sea  level  using  the  standard 

burner  orifice  sizes  (marked  with  an  "*"  in 

Table  5 

).    For  elevations  above  4500  feet, 

contact your gas supplier or qualified service 

technician . 

Install the appliance according to the regulations 

of the local authorities having jurisdiction and, 

in the USA, the National Fuel Gas Code NFPA 

54 / ANSI Z223.1 - latest edition or, in Canada, 

the CAN/CSA-B149.1 - latest edition.

Manifold Gas Supply Pressure

(all models)

Fuel #

Low

High

Natural 

Gas

(Lo) 2.2" WC

(0.55 kPa)

(Hi) 3.5" WC

(0.87 kPa)

Propane (Lo) 6.3" WC

(.57 kPa)

(Hi) 0.0" WC

(2.49 kPa)

Table 4

Burner Orifice Sizes 

Elevation 0-4500 feet ( 0-372 meters)

Model

Series

Nat.Gas

drill size (inches)

Propane

drill size (inches)

  MLDVT-30

#50 (0.070")*

H4873•

#59 (0.04")*

H7838

  MLDVT-35

#49 (0.073")*

2L82•

0.045"*

75L0•

  MLDVT-40

#43 (0.089")*

99K75•

#55 (0.052")*

9L52•

  MLDVT-45

0.090"*

37L70•

#54 (0.055")*

99K79•

Table 5

These appliances must be isolated from the 

gas supply piping system (

by closing their 

individual manual shut-off valve

) during any 

pressure testing of the gas supply piping 

system at test pressures equal to or 

less 

than 

1/2 psig (3.5 kPa).

These  appliances  and  their  individual 

shut-off valves 

must be disconnected

 from 

the gas supply piping system during any 

pressure testing of that system at pressures 

greater than

 1/2 psig (3.5 kPa)

.

Propane tanks are at pressures that will cause 

damage to valve components.  Verify that the 

tanks have step down regulators to reduce the 

pressure to safe levels.

Do not use these appliances if any part has been 

under water. Immediately call a qualified, profes-

sional service technician to inspect the appliance 

and to replace any parts of the control system and 

any gas control which have been under water.

Ne pas se servir de cet appareil s'il a été plongé 

dans l'eau, complètement ou en partie.  Appeler 

un technicien qualifié pour inspecter l'appareil et 

remplacer toute partie du système de contrôle et 

toute commande qui ont été plongés dans l'leau. 

SIT Millivolt  Gas Valve

Figure 1

 Input (BTU) Manually-Modulated 

Gas Valves (all models)

NATURAL GAS

Models

Input Rate (BTU / HR)

     MLDVT-30N

  

3,500 high

0,500 low

     MLDVT-35N

 

6,000 high

2,500 low

     MLDVT-40N

22,000 high

7,000 low

     MLDVT-45N

23,000 high

7,500 low

Table 1

 Input (BTU) Manually-Modulated 

Gas Valves (all models)

PROPANE GAS

Models

Input Rate (BTU / HR)

     MLDVT-30P

2,500 high

9,000 low

     MLDVT-35P

   

5,000 high

,500 low

     MLDVT-40P

20,000 high

5,800 low

     MLDVT-45P

22,000 high

7,000 low

Table 2

Provide adequate clearances around air open-

ings and adequate accessibility clearance for 

service and proper operation. Never obstruct 

the front openings of the appliance.

These appliances are designed to operate on 

natural or propane gas only. The use of other 

fuels  or  combination  of  fuels  will  degrade 

the performance of this system and may be 

dangerous. 

These fireplaces are designed as supplemental 

heaters. Therefore, it is advisable to have an alter-

nate heat source when installed in a dwelling.

Millivolt Models - 

The millivolt appliances are 

manually controlled and feature a spark igniter 

(piezo) that allows the appliance's pilot gas to 

be lit without the use of matches or batteries.  

This system provides continued service in the 

event of a power outage.

Millivolt models come standard with a manu-

ally-modulated gas valve; flame appearance and 

heat output can be controlled at the gas valve. 

The BTU Input for these appliances is shown 

in 

Tables 1 and 2.

H I

LO

W

HT

PT

HT

PT

PILO

T

PI

LO

T

ON

it

OFF

IN

OUT

Manifold Pressure Tap

Inlet Pressure Tap

Pilot Adjustment

Screw

HI/LO Variable 

Flame Height 

Adjustment

Main Gas Control Knob

OFF/PILOT/ON

* Standard size installed at factory

•  Part /Cat. Number

Summary of Contents for Merit MLDVT-45NE

Page 1: ...FE DIRECT VENT MLDVT 30 35 40 45 SERIES Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not light any ap...

Page 2: ...owing vent com ponents only Secure Vent Direct Vent System Compo nents Secure Flex Flexible Vent Components manufactured by Security Chimneys Inter national and Z FLEX Model GA Venting Systems listed...

Page 3: ...pane tanks are at pressures that will cause damage to valve components Verify that the tanks have step down regulators to reduce the pressure to safe levels Do not use these appliances if any part has...

Page 4: ...re Tap Manifold Burner Stage Terminal Ground TP PILOT OUT VENT LO TH TP TH TP HI IN IN Regulator Mounting Screw Cold Climate Insulation For cold climate installations seal all cracks around the applia...

Page 5: ...bustible and combustible exterior sidewall This distance may be decreased to 2 5 mm for non combustible exterior sidewalls only if the SV4 5HT 2 termination is used Be aware that this is a heat produc...

Page 6: ...e c n a r a e l C H y l b m e s s a r o t a l u g e r r e t e m t e e f 5 f o t h g i e h a n i h t i w m c 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 f o t h g...

Page 7: ...sides as detailed inTable6 withthefollowingexception When the unit is installed with one side flush with a wall the wall on the other side of the unit must not extend beyond the front edge of the unit...

Page 8: ...box floor securing the glass door Remove the door by tilting it outward at the bottom and lifting it up Set the door aside protecting it from inadvertent damage See Figure 46 on Page 30 TYPICAL INSTAL...

Page 9: ...P VENT WITH ONE 90 ELBOW Framing should be constructed of 2x4 or larger lumber Inches mm D 30 D is the required framing depth dimension when the finish material drywall thickness is 2 in 3mm A 2 Frami...

Page 10: ...rlocalcode requirements i e arebelowgradepenetrations of the gas line allowed etc IMPORTANT Ifpropaneisused beawarethat if tank size is too small i e under 100 lbs if this is the only gas appliance in...

Page 11: ...ructions should be used as a guideline and do not supersede local codes in any way Install vent according to local codes theseinstructions thecurrentNational Fuel Gas Code ANSI Z223 1 in the USA or th...

Page 12: ...5 5 5 5 2 6 4 0 1 2 0 0 3 7 5 5 7 4 0 0 1 1 0 2 6 6 5 2 5 0 2 2 0 0 4 5 7 6 5 2 6 5 0 0 3 0 0 3 9 6 5 7 5 0 0 0 2 0 2 2 7 6 1 0 3 0 0 4 5 3 7 5 2 1 6 1 0 0 2 0 3 5 9 7 5 2 6 6 0 1 0 2 0 3 1 8 5 7 6 0...

Page 13: ...are available in net lengths of 4 1 2 114 mm 10 1 2 267 mm 22 1 2 572 mm 34 1 2 876 mm and 46 1 2 1181 mm Refer to the Vent Section Length Charts on Page 12 for an aidinselectinglengthcombinations El...

Page 14: ...supplied with the flashing over the vent flashing joint See Figure 21 Loosen the storm collar screw Slide collar down until it meets the top of the flashing Tighten the ad justingscrew Applynon combus...

Page 15: ...ERE AN ELBOW IS THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 uWhenusingSecureFlex useFirestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5VF A Vent Restrictor as shown in Figure 14 Page 11...

Page 16: ...2 3 0 914 20 6 096 4 1 219 H H1 20 feet 6 096 m Max V V1 H H1 60 ft 18 3 m Max Figure 25 Top Vent three elbows VERTICAL VENT FIGURES TABLES CONTINUED Horizontal Outside Wall Termination System Figure...

Page 17: ...ously connected vent sections See Figure 17 on Page 13 I Continue installation of horizontal inclined sections Continue with the installation of the straightventsectionsinhorizontal inclinedrun as des...

Page 18: ...nations have been designed to perform in a wide range of weather condi tions Our terminations meet or exceed industry standards When selecting the locations of your horizontal terminations do not plac...

Page 19: ...S THE ONLY VERTICAL COMPONENT IN THE SYSTEM See Figure 29 Use Table 10 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES Figur...

Page 20: ...6 096 m Max Figure 31 Top Vent TWO 90 DEGREE ELBOWS See Table 10 on Page 19 as an aid in venting component selection for a particular range of exterior wall thicknesses HORIZONTAL VENT FIGURES TABLES...

Page 21: ...Figure 29 V H H V vWall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uWhen using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF vWall Firestop...

Page 22: ...mperature sealant Catalog No 10K81 to the inner adapter collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slidetheinnerflexpipeovertheadaptercol lar Ensure th...

Page 23: ...he electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 12 on Page 9 3 Removethe coverplate sknockoutandthen feedthepowersupplywirethroughtheknocko...

Page 24: ...artment Accessthevalvecompartmentbyremovingthe lower control compartment panel see Figure 38 by lifting and pulling the panel forward The panel is mounted on supporting tabs at the extreme right and l...

Page 25: ...e gas lines are tested and leak free be sure to rinse off the leak testing solution D Observe the individual tongues of flame on the burner Make sure all ports are open and producing flame evenly acro...

Page 26: ...ted Dis tribute these pieces over the surface of the burner as shown in Figures 44 and 45 Do not use more than is necessary Ensure that the main burner slots remain uncovered by the ember material Pos...

Page 27: ...35 H7666 WARNING Logs get very hot and will remain hot up to one hour after gas supply is turned off Handle only when logs are cool Left Rear Log Bracket Right Rear Log Bracket Rockwool Do Not Place...

Page 28: ...ot Place Rockwool Over Burner Slots Log Rack Volcanic Stone Right Rear Log Bracket 1 Position on the left rear log bracket 4 2 3 Position the left front log 2 and the right front log 3 against the log...

Page 29: ...29 NOTES...

Page 30: ...with the bottom of the door held away from the fireplace Figure 46 Hook the top flange of the door frame over the top of the firebox frame 6 Let the bottom of the door frame swing gentlyintowardsthefi...

Page 31: ...ont glass panel are in place and sealed during adjustment 1 Locate adjustment rod and adjust air shutter to the standard set ting as shown in Figure 49 adjustment rod is located in the lower control c...

Page 32: ...7 7 B F 5 4 V S e l b a t s u j d A 2 1 2 1 o t 2 1 7 g n i h s a l F 1 8 L 7 7 6 C S 5 4 V S 6 s r a l l o C m r o t S x o b s r a l l o c 6 4 2 2 H F H 5 4 V S k c a p 0 1 r e c a p S p o t s e r i...

Page 33: ...o f n i m r e T l a c i t r e V x e l F h t i w 2 1 6 o t t a l f d i g i r f o n o i t c e s r e t p a d A r a l l o c t r o p p u s f o o r t n e v d n a g n i h s a l f f o o r y l b m e s s a r a...

Page 34: ...on kit when performing any gas conversion Gas Conversion Kits Warning This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructionsandallappli...

Page 35: ...o pressure regula tor mounting screws Remove the pressure regulatoranddiaphragm Discardallremoved components Ensure the provided diaphragm is installed properly onto the replacement pressure regulator...

Page 36: ...pe joint compounds on flare fittings PILOT OUT VENT LO TH TP TH TP HI IN IN Pilot Stage Terminal Pressure Tap Inlet Pilot Gas Outlet Supply Gas Inlet Pressure Tap Manifold Burner Stage Terminal Ground...

Reviews: