Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 53 •
WA HIGH EFFCIENCY
WA
075 090 100 110 130 150
200
230
270 300 370
Minimum outlet water temperature
°C
5
Maximum inlet water temperature
°C
20
Minimum difference water inlet/outlet
°C
3
Maximum difference water inlet/outlet
°C
8
Minimum outside air temperature
°C
6
Minimum outside air temperature
with low ambient kit
°C
-10
Maximum outside air temperature :
• Normal operation with CLIMATIC™ 50
12°C/7°C water
+ one compressor unloaded
°C
53
51
51
54
53
53
51
51
52
53
49
• Start-up with CLIMATIC™ 50
+ Electronic expansion valve
and ONE compressor unloaded
°C
52
49
49
53
52
52
49
49
50
52
46
WA SUPER LOW NOISE
WA
075 090 100 110 130 150
200
230
270 300 370
Minimum outlet water temperature
°C
5
Maximum inlet water temperature
°C
20
Minimum difference water inlet/outlet
°C
3
Maximum difference water inlet/outlet
°C
8
Minimum outside air temperature
°C
6
Minimum outside air temperature
with low ambient kit
°C
-10
Maximum outside air temperature :
• Normal operation with CLIMATIC™ 50
12°C/7°C water
+ one compressor unloaded
°C
52
49
49
53
52
52
50
49,5
51,5
52,3
47,1
• Start-up with CLIMATIC™ 50
+ Thermostatic expansion valve
and ONE compressor unloaded
°C
50
46
46
51
50
49
47
46
48
49
43
• Start-up with CLIMATIC™ 50
+ Electronic expansion valve
and one compressor unloaded
°C
51
47
48
52
51
50
48
47
49
50
44