Installation - Operation - Maintenance manual (IOM)
•
AIR COOLED CHILLERS & SPLIT UNITS - 1106-E
• 54 •
ECOLOGIC WAH - COOLING MODE
WAH
150
200
230
Minimum outlet water temperature
°C
5
Maximum inlet water temperature
°C
20
Minimum difference water inlet/outlet
°C
3
Maximum difference water inlet/outlet
°C
8
Minimum outside air temperature
°C
6
Maximum outside air temperature :
• Normal operation with CLIMATIC™ 50
12°C/7°C water
+ one compressor unloaded
°C
51
50
49
• Start-up with CLIMATIC™ 50
+ Thermostatic expansion valve
and ONE compressor unloaded
°C
49
47
46
ECOLOGIC WAH - HEATING MODE
WAH
150
200
230
Minimum inlet water temperature
°C
10
Maximum outlet water temperature
°C
50
Minimum difference water inlet/outlet
°C
3
Maximum difference water inlet/outlet
°C
8
Minimum outside air temperature
with water outlet 35°C
°C
-10
Maximum outside air temperature
°C
30