background image

14

4. 

Break the vacuum by allowing nitrogen into the port 

connections (liquid and gas line pipes) until a positive 

pressure is achieved 

5. 

Evacuate  the  system  to  a  minimum  reading  of  500 

Microns (0.5 Torr).

6.  For a moisture-free system, ensure the vacuum is held 

without movement for a minimum of 4 hours.

7.  If vacuum fails to hold, carry out steps 2 through 6 until 

vacuum holds.

Wiring Connections

WARNING

Electric Shock Hazard. Can cause injury or death. Unit 

must be grounded in accordance with national and local 

codes.
Line voltage is present at all components when unit is 

not in operation. Disconnect all remote electric power 

supplies before opening access panel. Unit may have 

multiple power sources.

CAUTION

All terminal connections must be made as illustrated 

in the following diagrams. Improperly connected wiring 

could damage unit or cause communication errors 

between indoor and outdoor units.

In the U.S.A., wiring must conform with current local codes 

and the current National Electric Code (NEC). In Canada, 

wiring must conform with current local codes and the 

current Canadian Electrical Code (CEC). 

Outdoor Unit 

•  Refer to unit nameplate for minimum circuit ampacity 

and maximum over-current protection size.

•  Make all electrical power wiring connections at the out-

door unit.

• 

Be sure to reattach all electrical box covers after con

-

nections are complete.

Indoor Unit

•  All indoor units are powered by the outdoor unit.
• 

Communication Wiring (Indoor Units 30K and Below): 

Use one stranded 4-conductor wire to provide power 

and communication.

•  Communication Wiring (Indoor Units 36K and Above): 

Use one stranded 3-conductor wire to provide power 

and one stranded 2-conductor wire to provide commu-

nication.

•  Use minimum of 15 GA stranded wiring.
•  When installing a condensate pump, wire in-line with 

the CN5 float switch.

IMPORTANT

This unit must be properly grounded and protected by a 

circuit breaker. The ground wire for the unit must not be 

connected to a gas or water pipe, a lightning conductor 

or a telephone ground wire. 
Do not connect power wires to the outdoor unit until 

all other wiring and piping connections have been 

completed.
Do not install the unit near a lighting appliance that 

includes a ballast. The ballast may affect remote control 

operation.

IMPORTANT

Install unit so that unit disconnect is accessible.

Use  specified  wiring  and  cable  to  make  electrical 

connections. Clamp cables securely and make sure that 

connections are tight to avoid strain on wiring. Insecure 

wiring connections may result in equipment failure and 

risk of fire. 

Wiring must be installed so that all cover plates can be 

securely closed.

IMPORTANT

All diagrams are typical. Refer to the wiring diagram on 

the unit for actual wiring.

208/230V Outdoor Unit

Terminal Block

From Power

Supply

1      2       3     L1   L2

Terminal Block

1      2       3     

208/230V Indoor Unit

Outdoor Unit 

Indoor Unit 

Figure 21. 

Single-Zone Wiring 12K

Summary of Contents for M0STAT60Q-1

Page 1: ...lean up All mini split operating conditions must be verified ac cording to these installation instructions MLA MPB and MFMA Series SINGLE ZONE MINI SPLIT SYSTEMS 208 230V Floor Mount Console 508048 01...

Page 2: ...ccessories Component Catalog Number M0STAT64Q 1 Programmable Wired Controller 15D30 Wired Controller Extension Cable 20 feet long Y8738 Indoor Outdoor Unit Match Ups Outdoor Unit Indoor Unit Voltage M...

Page 3: ...ence 1 1st Revision Voltage P 208 230V 1 phase 60hz Nominal Cooling Capacity 012 1 ton Unit Type L Low Ambient Heat Pump P Heat Pump CEILING FLOOR NON DUCTED INDOOR UNITS M FM A 012 S 4 2 P Unit Type...

Page 4: ...rated tape field provided Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided Tape Line set wrapped in foam insulation...

Page 5: ...2S4S P inches 34 1 4 20 1 4 21 7 8 13 1 8 13 3 8 mm 870 514 556 333 340 MLA012S4S P inches 34 1 4 20 1 4 21 3 4 12 1 4 13 3 8 mm 870 514 552 311 594 Indoor Units Hanging Brackets 2 FRONT VIEW SIDE VIE...

Page 6: ...e 6 inches 152 mm when mounted on brackets and with no obstructions on the other three sides Figure 3 Outdoor Unit Clearances Inches mm Indoor Unit FRONT VIEW SIDE VIEW 4 102 WALL SUPPLY AIR 40 1016 S...

Page 7: ...sed to strong electromagnetic forces Areas exposed to acids or alkaline detergents DO Place the unit so that it is not exposed to direct sun light Ensure the structural ceiling can support the weight...

Page 8: ...er several times per year to avoid corrosive buildup salt Some localities are adopting sound ordinances based on the unit s sound level registered from the adjacent property not from the property wher...

Page 9: ...et 12 in 305 mm 79 in 2007 mm Figure 9 Outdoor Unit Air Flow Obstructed by Snow Figure 10 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit Howe...

Page 10: ...l mounting brack et insert the provided drain connector into one of the 1 inch 25 mm drain holes and attached a field provided insulated drain hose to the connector Use field provid ed rubber plugs to...

Page 11: ...ength required for the application 4 Cut the selected pipes with a pipe cutter Make the cuts flat and smooth as illustrated in Figure 18 Cutting Pipe 9 0 Lean Crude Burr o Figure 18 Cutting Pipe 5 Ins...

Page 12: ...ON THE OUTSIDE OF THE FLARE MALE FLARE CONNECTION Figure 19 Making Connections Male to Female Connection 17 Once snug continue another half turn on each nut which should create a leak free joint A to...

Page 13: ...non condensables and moisture from the system Leak Test Use the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas servic...

Page 14: ...ons are complete Indoor Unit All indoor units are powered by the outdoor unit Communication Wiring Indoor Units 30K and Below Use one stranded 4 conductor wire to provide power and communication Commu...

Page 15: ...g Factory Setting For Setting Down louver For Setting Down louver SW101 SW101 ACTIVE ACTIVE 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON 1 1 2 2 ON ON SW103 SW103 For Setting Fan Motor Control then No Po...

Page 16: ...G CN 21 Y G CN 1A Y G Y G COMPRESSOR Y G CN 50 3 U V W BLUE RED BLACK EXV OUTDOOR MAIN PCB OUTDOOR TE MP S E NS OR COMPR E S S OR DIS CHAR GE TE MP S E NS OR OUTDOOR C OIL TEMP SENSOR RED BLACK WHTIE...

Page 17: ...amount of additional refrigerant Failure to do so may result in reduced performance Table 8 Additional Refrigerant Charge System Size KBtu Pipe Length feet meters Amount of Refrigerant to add 12 25 7...

Page 18: ...failure the system will immediately stop When power returns the Operation light on the indoor unit will flash To restart the unit press the ON OFF button on the remote control If the system has an aut...

Page 19: ...Figure 30 Open Front Panel 2 Remove the Air Filter Press the clamps on the right and left sides of the air filter down slightly then pull upward to remove the air filter Air Outlet Selection Switch Fi...

Page 20: ...actory installed CN4 Adapter Cable Optional Programmable Wired Controller 20 Foot Cable provided with Programmable Wired Controller Figure 33 Connecting Optional Programmable Wired Controller Connect...

Reviews: