1. Operating mode selector
(standby , heating or cooling mode with manual selection of fan speed)
2 LEDs for indicating heating mode, cooling mode and fan operation
3 Setting facility for minimum setpoint limitation
(in increments of 1 K)
4 Setting facility for maximum setpoint limitation
(in increments of 1 K)
5 Room temperature setpoint knob
6
Set of DIP switches
DIP switch no. Meaning
Position ON
Position OFF
1 Fan
control
Fan control is temperature-
dependent in all operating
modes
Fan control in normal operation (and in
energy saving mode with the RCC10.1) is
temperature independent
1)
2
Operating mode change-
over via external switch
Changeover between normal
operation and energy saving
mode
Changeover between normal operation
and standby
1)
3
2)
Operating action of switch
for external operating
mode changeover
Changeover activated when
contact of switch is closed
(N.O.)
1)
Changeover activated when contact of
switch is open
(N.C.)
4
2)
Standby
Frost protection function not
enabled
Frost protection function enabled
1)
5
2)
Switching
differential 1 K in heating mode
1)
0.5 K in cooling mode
1)
4 K in heating mode
2 K in cooling mode
1) Factory
setting
2) Only
with the RCC10
The RCC10.1 comes with the following fixed settings:
•
Switching differential in heating mode:
2 K
•
Switching differential in cooling mode:
1 K
•
Standby:
OFF, no frost protection
•
Operating action of switch for external
operating mode changeover:
N.O.
Accessories
Description Type
reference
Adapter plate 120 x 120 mm for 4“ x 4“
conduit
boxes ARG70
Adapter plate 96 x 120 mm for 2“ x 4“
conduit
boxes
ARG70.1
Adapter plate for surface wiring 112x130 mm
ARG70.2
Setting and operating
elements
Legend
5