1.  Operating mode selector 

(standby  , heating or cooling mode with manual selection of fan speed) 

2  LEDs for indicating heating mode, cooling mode and fan operation 
3  Setting facility for minimum setpoint limitation 

(in increments of 1 K) 

4  Setting facility for maximum setpoint limitation  

(in increments of 1 K) 

5  Room temperature setpoint knob 

Set of DIP switches 

DIP switch no.  Meaning 

Position ON 

Position OFF 

1 Fan 

control 

Fan control is temperature-
dependent in all operating 
modes 

Fan control in normal operation (and in 
energy saving mode with the RCC10.1) is 
temperature independent

1)

 

Operating mode change-
over via external switch 

Changeover between normal 
operation and energy saving 
mode 

Changeover between normal operation 
and standby 

1)

 

3

2)

 

 

Operating action of switch 
for external operating 
mode changeover 

Changeover activated when 
contact of switch is closed 
(N.O.)

1)

 

Changeover activated when contact of 
switch is open 
(N.C.) 

4

2)

 

 

Standby 

Frost protection function not 
enabled 

Frost protection function enabled 

1)

 

5

2)

 Switching 

differential  1 K in heating mode 

1)

 

0.5 K in cooling mode 

1)

 

4 K in heating mode 
2 K in cooling mode 

1) Factory 

setting 

2) Only

 with the RCC10 

The RCC10.1 comes with the following fixed settings: 

• 

Switching differential in heating mode: 

2 K 

• 

Switching differential in cooling mode: 

1 K 

• 

Standby: 

OFF, no frost protection 

• 

Operating action of switch for external 
operating mode changeover: 

N.O. 

Accessories 

 

Description Type 

reference 

Adapter plate 120 x 120 mm for 4“ x 4“

 

conduit

 

boxes ARG70 

Adapter plate   96 x 120 mm for 2“ x 4“

 

conduit

 

boxes  

ARG70.1 

Adapter plate for surface wiring 112x130 mm 

ARG70.2 

Setting and operating 
elements 

Legend

 

5

Summary of Contents for LXRCC10

Page 1: ...Providing indoor climate comfort Application guide LXRCC10 AGU 0509 E LXRCC10 Remote control...

Page 2: ......

Page 3: ...RCC10 1 normal and energy saving mode or OFF Operating mode changeover input for remote control Function for avoiding damage resulting from moisture RCC10 1 Selectable control parameters RCC10 Operat...

Page 4: ...ing an external operating mode changeover switch provided plant conditions do not call for energy saving or frost protection mode only with the RCC10 or turning the controller s power supply off The h...

Page 5: ...ility Arbitrary setpoint readjustments can thus be prevented Operating modes The following operating modes are available Heating or cooling mode with automatic changeover and with manually selected fa...

Page 6: ...oom temperature falls below 8 C and if DIP switch no 3 is set to OFF frost protec tion mode will become active The operating action of the switch N C or N O can be selected Type summary Type reference...

Page 7: ...l operation and standby 1 3 2 Operating action of switch for external operating mode changeover Changeover activated when contact of switch is closed N O 1 Changeover activated when contact of switch...

Page 8: ...r makes a reset during which the fan LED flashes indicating that the reset has been correctly made This takes about 3 seconds Then the controller will be ready to operate Prior to fitting the changeov...

Page 9: ...t Climatic conditions Temperature Humidity Mechanical conditions to IEC 721 3 2 class 2K3 25 70 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 721 3 1 class 1K3 25 70 C 95...

Page 10: ...n speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Only with the RCC10 Connection diagrams L L B1 M B2 D1 GN...

Page 11: ......

Page 12: ...o quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pr...

Reviews: