Functions 

The controller acquires the room temperature with its integrated sensor or external 
room temperature sensor (QAA32) or external return air temperature sensor (QAH11.1) 
– if used (optional with the RCC10) – and maintains the setpoint by delivering control 
commands to the 2-point-valve. 
The switching differential with the 

• 

RCC10 is adjustable; it can be 1 or 4 K in heating mode and 0.5 or 2 K in cooling 
mode 

• 

RCC10.1 is fixed; it is 2 K in heating mode and 1 K in cooling mode 

The fan is switched to the selected speed via control output Q1, Q2 or Q3. 

When the function “Temperature-dependent fan control“ is activated (can be selected 
with DIP switch no.1), the fan is switched on / off depending on the temperature, that is, 
together with the valve. 

It is switched off by 

• 

leaving the heating or cooling sequence, provided the function “Temperature-
dependent fan control “ is activated, or 

• 

manually changing to standby  , provided plant conditions do not call for frost 
protection mode (only with the RCC10), or 

• 

activating an external operating mode changeover switch, provided plant conditions 
do not call for energy saving or frost protection mode (only with the RCC10), or  

• 

 turning the controller’s power supply off. 

 

 

The heating or cooling valve receives the 

OPEN

 command via control output Y11 when 

1.  the measured room temperature lies by half the switching differential below the 

setpoint (heating mode) or above the setpoint (cooling mode), and 

2.  the valve has been fully closed for more than one minute. 
 
The heating or cooling valve receives the 

CLOSE

 command via control output Y11 

when 

1.  the measured room temperature lies by half the switching differential above the 

setpoint (heating mode) or below the setpoint (cooling mode), and 

2.  the valve has been fully open for more than one minute. 

Note:  control output Y12 delivers a control command which is inverted to the control 

command at output Y11 and can be used for normally open valves 

The RCC10 provides control either depending on the measured room temperature or 
depending on the fan coil unit’s return air temperature. Changeover is automatic if a 
QAH11.1 cable temperature sensor is connected. 

Fan operation 

Heating and  
cooling mode 

 
ON 

OFF 

Return air tempera-
ture 

2

Summary of Contents for LXRCC10

Page 1: ...Providing indoor climate comfort Application guide LXRCC10 AGU 0509 E LXRCC10 Remote control...

Page 2: ......

Page 3: ...RCC10 1 normal and energy saving mode or OFF Operating mode changeover input for remote control Function for avoiding damage resulting from moisture RCC10 1 Selectable control parameters RCC10 Operat...

Page 4: ...ing an external operating mode changeover switch provided plant conditions do not call for energy saving or frost protection mode only with the RCC10 or turning the controller s power supply off The h...

Page 5: ...ility Arbitrary setpoint readjustments can thus be prevented Operating modes The following operating modes are available Heating or cooling mode with automatic changeover and with manually selected fa...

Page 6: ...oom temperature falls below 8 C and if DIP switch no 3 is set to OFF frost protec tion mode will become active The operating action of the switch N C or N O can be selected Type summary Type reference...

Page 7: ...l operation and standby 1 3 2 Operating action of switch for external operating mode changeover Changeover activated when contact of switch is closed N O 1 Changeover activated when contact of switch...

Page 8: ...r makes a reset during which the fan LED flashes indicating that the reset has been correctly made This takes about 3 seconds Then the controller will be ready to operate Prior to fitting the changeov...

Page 9: ...t Climatic conditions Temperature Humidity Mechanical conditions to IEC 721 3 2 class 2K3 25 70 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 721 3 1 class 1K3 25 70 C 95...

Page 10: ...n speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Only with the RCC10 Connection diagrams L L B1 M B2 D1 GN...

Page 11: ......

Page 12: ...o quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pr...

Reviews: