The water temperature acquired by the changeover sensor (QAH11.1 + ARG86.3) is 
used by the controller to switch from heating to cooling mode, or vice versa. When the 
water temperature lies above 28 °C, the controller switches to heating mode, below  
16 °C it switches to cooling mode. If, immediately after switching on, the water tempera-
ture lies between the 2 changeover points, the controller will start in heating mode. The 
water temperature is measured at minute-intervals and the operational status updated. 

Heating mode 

Cooling mode 

Automatic changeover 

1

0

SDH

Y11

W

30

21

D0

1

T [°C]

 

1

0

SDC

Y11

W

T [°C]

3021

D02

 

CM

HM

M

T

W

 [°C]

302

1

D

03

16

28

 

CM Cooling 

mode 

T

W

 Water 

temperature 

HM 

Heating mode 

Room temperature setpoint 

Operating mode 

Y11 

Manipulated variable “Valve“ 

SDC 

Switching differential “Cooling“ 

Room temperature 

SDH 

Switching differential “Heating“ 

 
The task of the changeover sensor is to initiate the change from heating to cooling 
mode even if the two-port valves are shut down for a longer period of time. To ensure 
this function, the valves are opened for one minute at 2-hour intervals during off hours. 
(Note: this function is not effective when using thermal actuators) 
 
The room temperature setpoint can be limited in increments of 1 K by making use of 
the minimum and maximum limitation facility. Arbitrary setpoint readjustments can thus 
be prevented. 

Operating modes 

The following operating modes are available: 

Heating or cooling mode with automatic changeover and with manually selected fan 
speed III, II or I. In normal operation, the controller maintains the adjusted setpoint. 

The frost protection function is activated only when DIP switch no.4 is set to OFF.  
Frost protection mode can be activated either 

• 

by manually switching to standby  . 

• 

by activating the external operating mode changeover switch, provided DIP switch  

no.2 is set to OFF 

If the room temperature falls below 8 °C, the controller will automatically switch to frost 
protection mode. In that case, the heating valve opens and the fan operates at the se-
lected speed. If the operating mode selector is in position standby  , the fan will oper-
ate at speed I. The room temperature is maintained at a setpoint of 8 °C and the set-
point adjusted by the user will be ignored. 
If frost protection mode is locked (DIP switch no.4 in position ON), standby is locked 
also, which means that the controller will not switch to standby but to OFF: 

In energy saving mode, the setpoint of heating is 16 °C and the setpoint of cooling 28 
°C, independent of the position of the setpoint knob. This operating mode will be acti-
vated when input D1 for operating mode changeover is active and DIP switch no.2 is 
set to ON. 

Automatic 
changeover 

Purging function 

Energy saver 

Normal operation 

Frost protection mode 

(only with the RCC10)

 

Energy saving  
mode 

3

Summary of Contents for LXRCC10

Page 1: ...Providing indoor climate comfort Application guide LXRCC10 AGU 0509 E LXRCC10 Remote control...

Page 2: ......

Page 3: ...RCC10 1 normal and energy saving mode or OFF Operating mode changeover input for remote control Function for avoiding damage resulting from moisture RCC10 1 Selectable control parameters RCC10 Operat...

Page 4: ...ing an external operating mode changeover switch provided plant conditions do not call for energy saving or frost protection mode only with the RCC10 or turning the controller s power supply off The h...

Page 5: ...ility Arbitrary setpoint readjustments can thus be prevented Operating modes The following operating modes are available Heating or cooling mode with automatic changeover and with manually selected fa...

Page 6: ...oom temperature falls below 8 C and if DIP switch no 3 is set to OFF frost protec tion mode will become active The operating action of the switch N C or N O can be selected Type summary Type reference...

Page 7: ...l operation and standby 1 3 2 Operating action of switch for external operating mode changeover Changeover activated when contact of switch is closed N O 1 Changeover activated when contact of switch...

Page 8: ...r makes a reset during which the fan LED flashes indicating that the reset has been correctly made This takes about 3 seconds Then the controller will be ready to operate Prior to fitting the changeov...

Page 9: ...t Climatic conditions Temperature Humidity Mechanical conditions to IEC 721 3 2 class 2K3 25 70 C 95 r h class 2M2 Storage Climatic conditions Temperature Humidity to IEC 721 3 1 class 1K3 25 70 C 95...

Page 10: ...n speed III AC 230 V Y11 Control output Valve AC 230 V N O contact for N C valves Y12 Control output Valve AC 230 V N C contact for N O valves Only with the RCC10 Connection diagrams L L B1 M B2 D1 GN...

Page 11: ......

Page 12: ...o quality the Specifications Ratings and Dimensions are subject to change without notice and without incurring liability Improper installation adjustment alteration service or maintenance can cause pr...

Reviews: