3
Shipping and Packing List
Item
Quantity
M30 Thermostat with backplate attached
1
Wall plate
1
Mounting screws (M3.5x25mm self-tapping screws)
2
Wall anchors
2
Warranty sheet
1
Installation & setup guide
1
User guide
1
System Wiring Diagrams Fold-Out Sheet
1
Thermostat
Unit Dimensions (H x W x D)
Dimensions: 3-5/16 x 4-5/16 x 7/8 in. (84 x 110 x
22mm)
Wall Plate Dimensions (H x W)
Dimensions: 4-1/2” x 5-3/4” (114 x 146mm)
Compressor Short-Cycle Protection (Compressor
Protect)
This thermostat is equipped with automatic
compressor protection to prevent potential damage
due to short cycling or extended power outages.
The non-adjustable short-cycle protection provides
a 5-minute delay between heating or cooling cycles
to prevent the compressor from being damaged.
NOTE:
There is an option in advanced settings that
will allow this safety feature to be disabled.
By default it is set to ON. Short Cycle
protection is disabled during testing of the
outdoor unit. It is automatically reset once
the test is completed.
WARNING
Improper installation, adjustment, alteration, ser-
vice or maintenance can cause property damage,
personal injury or loss of life.
Installation and service must be performed
by a li censed professional HVAC installer (or
equivalent) or a service agency.
WARNING
Always turn off power at the main power source by
switching the circuit breaker to the OFF position
before installing or removing this thermostat.
All wiring must conform to local and national
building and electrical codes and ordinances.