background image

Page 8

  2 −The nitrogen holding charge in the unit must be re

leased. Open both manifold valves to release the nitro
gen from the unit. See page 5 for service valve opera
tion.

  3 −Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

  4 −Open both manifold valves and start vacuum pump.

  5 −Evacuate the line set, condensing unit, and indoor unit

to an 

absolute pressure

 of 23 mm (23,000 microns) of

mercury. During the early stages of evacuation, it is de
sirable to close the manifold gauge valve at least once
to determine if there is a rapid rise in 

absolute pres

sure

. A rapid rise in pressure indicates a relatively

large leak. If this occurs, the leak testing procedure
must be repeated.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres
sure in a vacuum is equal to atmospheric pressure mi
nus vacuum pressure.

  6 −When the absolute pressure reaches 23 mm (23,000

microns) of mercury, close the manifold gauge valves,
turn off the vacuum pump and disconnect the manifold
gauge center port hose from vacuum pump. Attach the
manifold center port hose to a nitrogen cylinder with
pressure regulator set to 150 psig (1034 kPa) and
purge the hose. Open the manifold gauge valves to
break the vacuum in the system. Close the manifold
gauge valves.

WARNING

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use com
pressors to evacuate a system.
Extremely low vacuums can cause internal arcing
and compressor failure.
Damage caused by deep vacuum operation will
void warranty.

  7 −Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the system.

  8 −Reconnect the manifold gauge  to the  vacuum pump,

turn the pump on and continue to evacuate the system
until the absolute pressure does not rise above .5 mm
(500 microns) of mercury within a 20−minute period after
shutting off the vacuum pump and closing the manifold
gauge valves.

 9  −When the absolute pressure requirement from step 9

has been met, disconnect the manifold gauge hose
from the vacuum pump. Then, weigh in a LIQUID
charge of R407C through the liquid and suction service
valves.

Refer to the unit nameplate for the correct liquid charge.
If you can not measure in the total amount, refer to the
start−up section and set the final system charge accord
ing to the charging instructions. 

The R407C refrigerant

cylinder should be chocolate brown.

Start−Up

 1 − Rotate the fan to check for frozen bearings or binding.

 2 − Inspect all factory and field−installed wiring for loose

connections.

 3 − Check voltage supply at the disconnect switch. The

voltage must be within range listed on unit nameplate.
If not, do not start equipment until the power company
has been consulted and the voltage condition cor
rected.

 4 − Set thermostat for a cooling demand, turn on power to

blower and close condensing unit disconnect switch to
start.

 5 − Recheck unit voltage with unit running. Power must be

within range shown on unit nameplate. Check amper
age draw of unit. Refer to unit nameplate for correct
running amps.

Charging

Charge the unit with the amount of liquid R407C refrigerant
that is indicated on the unit namplate. This charge is based
on a matching indoor coil and outdoor coil with 4.6 m line
set. For varying lengths of line set, refer to table 2 for refrig
erant charge adjustment.

TABLE 2

Liquid Line Set Diameter

Grams per 1.5 m adjust

from 4.6 m line set*

5/16 in. (8 mm)

57 g per 1.5 m

3/8 in. (10 mm)

85 g per 1.5 m

*If line length is greater than 4.6 m, add this amount. If line
length is less than 4.6 m, subtract this amount.

IMPORTANT

Mineral oils are not compatible with R407C. If oil
must be added, it must be a polyol ester oil.

The compressor is charged with sufficient polyol ester
oil for line set lengths up to 15 m. If line set lengths lon
ger than 15 m will be required, add 1 ounce (28 gm) of oil
for every additional 3 m of line set. Do not add any more
than 207 ml of oil. Copeland has approved Mobil EAL

t

Arctic 22CC and ICI EMKARATE

t

 RL32CF for use with

these compressors when oil must be added in the field.

The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
the indoor temperature must range from 21°C to 26°C. Be
sure to monitor system pressures while charging.

Summary of Contents for HS40 Series

Page 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Page 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Page 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Page 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Page 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Page 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Page 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Page 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Page 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Page 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Page 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Page 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: