background image

Page 6

FLUSHING CONNECTIONS

LOW

PRESSURE

HIGH

PRESSURE

SUCTION LINE

SERVICE VALVE

INDOOR COIL

HS40 UNIT

GAUGE MANIFOLD

RECOVERY MACHINE

INVERTED R22

CYLINDER

(Contains clean

R22 to be used for

flushing)

LIQUID LINE

SERVICE VALVE

INLET

DISCHARGE

TANK RETURN

CLOSED

OPENED

EXISTING

EXISTING SUCTION LINE

EXISTING LIQUID LINE

RECOVERY

CYLINDER

NOTE − The inverted R22 cylin
der must contain at least the
same amount of refrigerant as
was recovered from the existing
system.

FIGURE 4

Liquid & Suction Line Service Valves

The liquid line and suction line service valves (figures 5 and
6) and gauge ports are accessible from outside the unit.
The service ports are used for leak testing, evacuating,
charging and checking charge.

The valves are equipped with a service port. A Schrader
valve is factory−installed. A service port cap is supplied to
protect the Schrader valve from contamination and to
serve as the primary leak seal.

To Access Schrader Port:

 1 − Remove the service port cap with an adjustable wrench.

 2 − Connect gauge to the service port.

 3 − When testing is completed, replace the service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Suction Line Service Valve:

 1 − Remove the stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex−head extension to

back the stem out counterclockwise until the valve
stem just touches the retaining ring.

DANGER

Do not attempt to backseat this valve. Attempts to
backseat this valve will cause snap ring to explode
from valve body under pressure of refrigerant. Per
sonal injury and unit damage will result.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

LIQUID AND SUCTION LINE SERVICE VALVES

(VALVE OPEN)

SCHRADER

VALVE

SERVICE

PORT

SERVICE

PORT

CAP

INSERT HEX

WRENCH HERE

FIELD SIDE

UNIT SIDE

STEM CAP

SCHRADER VALVE OPEN

TO LINE SET WHEN VALVE IS

CLOSED (FRONT SEATED)

SERVICE

PORT

SERVICE

PORT CAP

RETAINING RING

STEM CAP

INSERT HEX

WRENCH HERE

(VALVE CLOSED)

(VALVE FRONT SEATED)

FIELD SIDE

UNIT SIDE

FIGURE 5

Summary of Contents for HS40 Series

Page 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Page 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Page 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Page 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Page 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Page 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Page 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Page 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Page 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Page 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Page 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Page 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: