background image

Page 5

CAUTION

This procedure should not be performed on sys
tems which contain contaminants (Example: com
pressor burn out).

Required Equipment

You will need the following equipment in order to flush the
existing line set and indoor coil: two clean R22 recovery
bottles, an oilless recovery machine with a pump down fea
ture, and two sets of gauges (one for use with R22 and one
for use with the R407C).

Flushing Procedure

 1 − Remove existing R22 refrigerant using the appropri

ate procedure below.

If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing R22 refrigerant to
flush the system −−

 

Disconnect all power to the exist

ing outdoor unit. Connect the existing unit, a 

clean

 re

covery cylinder and the recovery machine according
to the instructions provided with the recovery ma
chine. Remove all R22 refrigerant from the existing
system. Refer to gauges after shutdown to confirm
that the entire system is completely void of refrigerant.
Disconnect the liquid and suction lines from the exist
ing outdoor unit.

If the existing outdoor unit is equipped with manu
al shut−off valves AND you plan to use NEW R22
refrigerant to flush the system 

−− 

Start the existing

R22 system in the cooling mode and close the liquid
line valve. Pump all of the existing R22 refrigerant
back into the outdoor unit. (It may be necessary to by
pass the low pressure switches to ensure complete re
frigerant evacuation.) When the low side system pres
sures reach 0 psig, close the suction line valve. Dis
connect all power to the existing outdoor unit. Refer to
gauges after shutdown to confirm that the valves are
not allowing refrigerant to flow back into the low side of
the system. Disconnect the liquid and vapor lines from
the existing outdoor unit.

 2 − Remove the existing outdoor unit. Set the new R407C

unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. 

DO NOT install provided R407C ex

pansion valve at this time. 

Make low voltage and line voltage connections to the
new outdoor unit. 

DO NOT turn on power to the unit

or open the outdoor unit service valves at this
time.

 3 − Remove the existing refrigerant flow control orifice or

thermal expansion valve before continuing with flush
ing procedures. The existing devices are not approved
for use with R407C refrigerant and may prevent prop
er flushing. Use a field−provided fitting to reconnect the
lines.

IMPORTANT

The line set and indoor coil must be flushed with at
least the same amount of clean refrigerant that pre
viously charged the system. Check the charge in
the flushing cylinder before proceeding.

 4 − Remove the pressure tap valve cores from the HS40

unit’s service valves. Connect an R22 cylinder with
clean refrigerant to the suction service valve. Con
nect the R22 gauge set to the liquid line valve and
connect a recovery machine with an empty recovery
tank to the gauge set.

 5 − Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the ex
isting system line set and indoor coil.

 6 − Invert the cylinder of clean R22 and open its valve to

allow liquid refrigerant to flow into the system through
the suction line valve. Allow the refrigerant to pass
from the cylinder and through the line set and the in
door coil before it enters the recovery machine.

 7 − After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the R22 vapor is recovered. All the recovery ma
chine to pull a vacuum on the system.

NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush.

 Each time the system

is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.

 8 − Close the valve on the inverted R22 drum and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

 9 − Use nitrogen to break the vacuum on the refrigerant

lines and indoor coil before removing the recovery ma
chine, gauges and R22 refrigerant drum. Reinstall
pressure tap valve cores into HS40 service valves.

10 −Install the provided expansion valve (approved for use

with R407C refrigerant) in the liquid line at the indoor
coil.

Summary of Contents for HS40 Series

Page 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Page 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Page 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Page 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Page 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Page 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Page 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Page 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Page 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Page 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Page 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Page 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: