background image

Page 7

To Close Liquid or Suction Line Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Use a service wrench with a hex−head extension to

turn the stem clockwise to seat the valve. Tighten firm
ly.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

Five Ton Suction Line (Ball−Type) Service Valve

A balltype fullservice valve is used on five−ton HS40065
units only. These suction line service valves function the
same way, the differences are in the valve’s construction.
Valves are not rebuildable. If a valve has failed, it must be
replaced. A ball valve valve is illustrated in figure 6.

The ball valve is equipped with a service port. A Schrader
valve is factory installed. A service port cap is supplied to
protect the Schrader valve from contamination and assure
a leak free seal.

SUCTION LINE (BALL TYPE) SERVICE VALVE

(VALVE OPEN)

SCHRADER VALVE

SERVICE PORT

SERVICE

PORT

CAP

STEM CAP

STEM

USE ADJUSTABLE WRENCH

ROTATE STEM CLOCKWISE 90

_

 TO CLOSE

ROTATE STEM COUNTERCLOCKWISE 90

_

 TO OPEN

BALL

(SHOWN OPEN)

TO OUTDOOR COIL

TO INDOOR COIL

FIGURE 6

Leak Testing

After the line set has been connected to the indoor and out
door units, the line set connections and indoor unit must be
checked for leaks.

WARNING

Never use oxygen to pressurize refrigeration or air
conditioning systems. Oxygen will explode on
contact with oil and could cause personal injury.
When using high pressure gas such as nitrogen for
this purpose, be sure to use a regulator that can
control the pressure down to 1 or 2 psig (6.9 to 13.8
kPa).

Using an Electronic Leak Detector

IMPORTANT

Leak detector must be capable of sensing HFC re
frigerant.

 1 − Connect the high pressure hose of the manifold gauge

set to the suction valve service port. 

(Normally, the high

pressure hose is connected to the liquid line port, how
ever, connecting it to the suction port helps to protect
the manifold gauge set from damage caused by high
pressure.)

 2 − With both manifold valves closed, connect the cylinder

of R407C refrigerant. Open the valve on the R407C
cylinder (vapor only).

 3 − Open the high pressure side of the manifold to allow

R407C into the line set and indoor unit. Weigh in a trace
amount of R407C.

 [A trace amount is a maximum of 2

ounces (57 g) refrigerant or 3 pounds (31 kPa) pres
sure]. 

Close the valve on the R407C cylinder and the

valve on the high pressure side of the manifold gauge
set. Disconnect R407C cylinder.

 4 − Connect a cylinder of nitrogen with a pressure regulat

ing valve to the center port of the manifold gauge set.

 5 − Adjust nitrogen pressure to 150 psig (1034 kPa). Open

the valve on the high side of the manifold gauge set in
order to pressurize the line set and the indoor coil.

 6 − After a short period of time, open a refrigerant port to

make sure that an adequate amount of refrigerant has
been added for detection (refrigerant requirements
will vary with line lengths). Check all joints for leaks.
Purge nitrogen and R407C mixture. Correct any leaks
and recheck.

Evacuation & Dehydration

Evacuating the system of non−condensables is critical for
proper operation of the unit. Non−condensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Non−condensables and water vapor combine with
refrigerant to produce substances that corrode copper pip
ing and compressor parts.
  1 −Connect the manifold gauge set to the service valve

ports as follows: low pressure gauge to suction line
service valve; high pressure gauge to liquid line ser
vice valve.

IMPORTANT − Compliant scroll compressors (as with
any refrigerant compressor) should never be used to
evacuate a refrigeration or air conditioning system.
NOTE − A temperature vacuum gauge, mercury vacu
um or thermocouple gauge should be used. The usual
Bourdon tube gauges are inaccurate in the vacuum
range.

Summary of Contents for HS40 Series

Page 1: ...iance INSTALLATION INSTRUCTIONS HS40 SERIES UNITS CONDENSING UNITS 504 186M 11 2002 Supersedes 4 2000 Table of Contents HS40 Condensing Unit 1 Shipping Packing List 1 Unit Dimensions 2 General Informa...

Page 2: ...70 LIQUID LINE CONNECTION OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT...

Page 3: ...weight of the unit is properly distributed over roof joists and rafters Either redwood or steel supports are recommended Electrical The wiring must conform with current local codes and the current Can...

Page 4: ...mpressor Brazing Connection Procedure 1 The end of the refrigerant line must be cut square and its internal shape must remain round The line must be free of nicks or dents and must be deburred I D and...

Page 5: ...e outdoor unit service valves at this time 3 Remove the existing refrigerant flow control orifice or thermal expansion valve before continuing with flush ing procedures The existing devices are not ap...

Page 6: ...y leak seal To Access Schrader Port 1 Remove the service port cap with an adjustable wrench 2 Connect gauge to the service port 3 When testing is completed replace the service port cap Tighten finger...

Page 7: ...how ever connecting it to the suction port helps to protect the manifold gauge set from damage caused by high pressure 2 With both manifold valves closed connect the cylinder of R407C refrigerant Ope...

Page 8: ...been met disconnect the manifold gauge hose from the vacuum pump Then weigh in a LIQUID charge of R407C through the liquid and suction service valves Refer to the unit nameplate for the correct liquid...

Page 9: ...21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 14...

Page 10: ...ess The manually re set high pressure switch protects the system from high pressure conditions which result from a fan failure or a blocked or dirty coil The low pressure switch SPST NO protects the s...

Page 11: ...Serial No Date State State Service technician Amps Supply Condenser Fan Compressor Indoor Filter Clean Indoor Blower CFM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Evaporator...

Page 12: ...Page 12 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: