background image

Page 4

III–UNIT  COMPONENTS
A–Transformer

The contactor coil, time delay and temperature sen-
sor are all energized by 24VAC supplied by the indoor
unit. All other controls in the outdoor unit are pow-
ered by line voltage. Refer to unit wiring diagram.
The HS25 is not equipped with an internal line volt-
age to 24V transformer.

B–Contactor

The compressor is energized by a contactor located in
the control box. HS25-211 through -511 units use SPST
contactors. HS25-651 units use a DPST contactor. The
contactor is energized by indoor thermostat terminal Y
when thermostat demand is present.

WARNING

HS25 UNITS USING SINGLE-POLE CONTACTORS:
ONE LEG OF COMPRESSOR, CAPACITOR AND
CONDENSER FAN ARE CONNECTED TO LINE
VOLTAGE AT ALL TIMES. POTENTIAL EXISTS FOR
ELECTRICAL SHOCK RESULTING IN INJURY OR
DEATH.  REMOVE ALL POWER AT DISCONNECT
BEFORE SERVICING.

C–TD1–1 Time Delay

Each HS25 is equipped with a Lennox built TD1–1 time
delay located in the control box (figure 4). The time
delay is electrically connected between thermostat ter-
minal Y and the compressor contactor. On initial ther-
mostat demand, the compressor contactor is delayed
for 8.5 seconds.  At the end of the delay, the compressor
is allowed to energize. When thermostat demand is sa-
tisfied, the time delay opens the circuit to the compres-
sor contactor coil and the compressor is de–energized.
The time delay performs no other functions. Without
the delay it would be possible to short cycle the com-
pressor.  A scroll compressor, when short cycled, can
run backward if head pressure is still high.  It does not
harm a scroll compressor to run backward, but it could
cause a nuisance tripout of safety limits (internal over-
load).  For this reason, if a TD1–1 delay should fail, it
must be replaced.  Do not bypass the control.

DANGER

DO NOT ATTEMPT TO REPAIR THIS CONTROL.
UNSAFE OPERATION WILL RESULT.  IF THE CON-
TROL IS FOUND TO BE INOPERATIVE, SIMPLY RE-
PLACE THE ENTIRE CONTROL.

FIGURE 4

HS25 UNIT COMPONENTS

CONTACTOR

LIQUID LINE

SERVICE VALVE

SUCTION LINE

SERVICE VALVE

COMPRESSOR

COMPRESSOR

TERMINAL BOX

THERMOMETER

WELL

DUAL CAPACITOR

TD1–1

TIME DELAY

AND GAUGE PORT

AND GAUGE PORT

LOW

PRESSURE

SWITCH

COMPRESSOR
TEMPERATURE

SENSOR

CONDENSER FAN

(NOT SHOWN)

TOP OF CABINET

ACCUMULATOR

HS25-511/651

ONLY

HIGH

PRESSURE

SWITCH

Summary of Contents for HS25-211

Page 1: ...must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the Engineering Handbook for approved system matchups A misapplied system will cause errat...

Page 2: ...1 7 1 6 1 1 3 1 3 8 2 0 50 60 45 31 3 37 7 26 1 SPECIFICATIONS Model No HS25 261 HS25 311 HS25 411 Outdoor Coil Condenser Fan HCFC 22 charge furnished Face area sq ft Tube diameter in No of Rows Fins...

Page 3: ...uring a single orbit several pockets of gas are compressed simulta neously providing smooth continuous compression The scroll compressor is tolerant to the effects of liquid return If liquid enters th...

Page 4: ...the compressor contactor On initial ther mostat demand the compressor contactor is delayed for 8 5 seconds At the end of the delay the compressor is allowed to energize When thermostat demand is sa t...

Page 5: ...DISCHARGE TEMPERATURE SENSOR WIRES TO CONTROL BOX TO COMP TERM BOX IN 461 UNITS 3 1 2 TON AND SMALLER ONLY F High Pressure Switch A manual reset single pole single throw high pressure switch located...

Page 6: ...application of field fabricated lines Separate discharge and suction service ports are pro vided at the compressor for connection of gauge man ifold during charging procedure Model No LIQUID SUCTION L...

Page 7: ...rences are in construction Valves manufactured by Parker are forged assem blies Primore and Aeroquip valves are brazed to gether Valves are not rebuildable If a valve has failed it must be replaced Th...

Page 8: ...h gauge manifold and connect vacuum pump with vacuum gauge to center port of gauge manifold With both gauge manifold ser vice valves open start pump and evacuate evapo rator and refrigerant lines IMPO...

Page 9: ...table 6 as a general guide for performing main tenance checks Table 6 is not a procedure for charg ing the system Minor variations in these pressures may be expected due to differences in installation...

Page 10: ...erminal Y passes through discharge temperature sensor compressor thermostat and low pressure switch to energize time delay terminal 2 3 Time delay action is at the beginning of a thermostat demand Whe...

Reviews: