background image

Page 6

G–Low Pressure Switch

An auto-reset single-pole single-throw low pressure
switch located in the suction line of the compressor
shuts off the compressor when suction pressure drops
below the factory setting. The switch is normally
closed and is permanently adjusted to trip (open) at 25
+ 5 psi. The switch automatically resets when suction
line pressure rises above 55 + 5 psi. See figure 4 for re-
set switch location.

H–Dual Capacitor

The compressor and fan on all models use permanent
split capacitor motors.  A single “dual” capacitor is used
for both the fan motor and the compressor (see unit wir-
ing diagram).  The fan side of the capacitor and the com-
pressor side of the capacitor have different mfd ratings.
The capacitor is located inside the unit control box (see
figure 4).  Table 2 shows the ratings of the dual capacitor.

TABLE 2

Units

MFD

VAC

HS25 DUAL CAPACITOR RATING

HS25–261

HS25–311

HS25–411, -461

5

30

5

35

5

370

35

Terminal

FAN

HERM

FAN

HERM

FAN

HERM

440

HS25–211

5

25

FAN

HERM

HS25–511

HS25–651

10
40
10
55

FAN

HERM

FAN

HERM

I–Condenser Fan Motor

All units use single–phase PSC fan motors which re-
quire a run capacitor. The “FAN” side of the dual capac-
itor is used for this purpose. The specifications table on
page 1 of this manual shows the specifications of out-
door fans used in HS25s. In all units, the outdoor fan is
controlled by the compressor contactor.

IV–REFRIGERANT SYSTEM
A–Plumbing

Field refrigerant piping consists of liquid and suction
lines from the outdoor unit (sweat connections). Use
Lennox L10 series line sets as shown in table 3 or field
fabricated refrigerant lines.  Refer to the piping section
of the Lennox Service Unit Information Manual
(SUI–803–L9) for proper size, type and application of
field–fabricated lines.
Separate discharge and suction service ports are pro-
vided at the compressor for connection of gauge man-
ifold during charging procedure.

Model No.

LIQUID

SUCTION

L10

LINE

LINE

LINE SETS

HS25–261

3/8 in.

5/8 in.

L10–26

20 ft. – 50 ft.

HS25–311

HS25–411

3/8 in.

3/4 in.

L10–41

20 ft. – 50 ft.

HS25–461

HS25-511

3/8 in.

7/8 in.

TABLE 3

HS25–211

3/8 in.

1-1/8 in.

HS25–651

Field Fabricate

L10–65

20 ft. – 50 ft.

B–Service Valves

The liquid line and suction line service valves and
gauge ports are accessible by removing the compres-
sor access cover. Full service liquid and suction line
valves are used. See figures 7 and 8. The service ports
are used for leak testing, evacuating, charging and
checking charge.

KNIFE EDGE SEAL

STEM CAP

SERVICE

PORT CAP

TO LINE

SET

TO

CONDENSER

COIL

LIQUID LINE SERVICE VALVE

IMPORTANT

A schrader valve is not
provided on the liquid line
service port. Valve must
be backseated to turn off
pressure to service port.

FIGURE 7

VALVE STEM

USE SERVICE

WRENCH

(PART #18P66,

54B64 or 12P95)

SERVICE PORT OPEN

TO LINE SET WHEN

FRONT SEATED AND

CLOSED (OFF)

WHEN BACK

SEATED

NO SCHRADER

1 – Liquid Line Service Valve

A full-service liquid line valve made by one of several
manufacturers may be used. All liquid line service
valves function the same way, differences are in
construction. Valves manufactured by Parker are
forged assemblies. Valves manufactured by Primore
are brazed together. Valves are not rebuildable. If a
valve has failed it must be replaced. The liquid line ser-
vice valve is illustrated in figure 7.
The valve is equipped with a service port. There is no
schrader valve installed in the liquid line service port. A
service port cap is supplied to seal off the port.
The liquid line service valve is a front and back seating
valve. When the valve is backseated the service port is
not pressurized. The service port cap can be removed
and gauge connections can be made.

Summary of Contents for HS25-211

Page 1: ...must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the Engineering Handbook for approved system matchups A misapplied system will cause errat...

Page 2: ...1 7 1 6 1 1 3 1 3 8 2 0 50 60 45 31 3 37 7 26 1 SPECIFICATIONS Model No HS25 261 HS25 311 HS25 411 Outdoor Coil Condenser Fan HCFC 22 charge furnished Face area sq ft Tube diameter in No of Rows Fins...

Page 3: ...uring a single orbit several pockets of gas are compressed simulta neously providing smooth continuous compression The scroll compressor is tolerant to the effects of liquid return If liquid enters th...

Page 4: ...the compressor contactor On initial ther mostat demand the compressor contactor is delayed for 8 5 seconds At the end of the delay the compressor is allowed to energize When thermostat demand is sa t...

Page 5: ...DISCHARGE TEMPERATURE SENSOR WIRES TO CONTROL BOX TO COMP TERM BOX IN 461 UNITS 3 1 2 TON AND SMALLER ONLY F High Pressure Switch A manual reset single pole single throw high pressure switch located...

Page 6: ...application of field fabricated lines Separate discharge and suction service ports are pro vided at the compressor for connection of gauge man ifold during charging procedure Model No LIQUID SUCTION L...

Page 7: ...rences are in construction Valves manufactured by Parker are forged assem blies Primore and Aeroquip valves are brazed to gether Valves are not rebuildable If a valve has failed it must be replaced Th...

Page 8: ...h gauge manifold and connect vacuum pump with vacuum gauge to center port of gauge manifold With both gauge manifold ser vice valves open start pump and evacuate evapo rator and refrigerant lines IMPO...

Page 9: ...table 6 as a general guide for performing main tenance checks Table 6 is not a procedure for charg ing the system Minor variations in these pressures may be expected due to differences in installation...

Page 10: ...erminal Y passes through discharge temperature sensor compressor thermostat and low pressure switch to energize time delay terminal 2 3 Time delay action is at the beginning of a thermostat demand Whe...

Reviews: