background image

Page 8

 3– Replace stem cap. Tighten finger tight, then tight-

en an additional 1/6 turn.

V–CHARGING

The unit is factory–charged with the amount of
HCFC-22 refrigerant indicated on the unit rating plate.
This charge is based on a matching indoor coil and out-
door coil with a 25 foot (6096mm) line set. For varying
lengths of line set, refer to table 4 for refrigerant charge
adjustment. A blank space is provided on the unit rat-
ing plate to list actual field charge.

LIQUID LINE

1/4 in. (6 mm)

5/16 in. (8mm)

3/8 in. (10 mm)

TABLE 4

Ounce per 5 foot (ml per mm) adjust

from 20 foot (6096 mm) line set*

1 ounce per 5 feet (30 ml per 1524 mm)

*If line set is greater than 20 ft. (6.09m) add this amount. If line set

is less than 20 feet (6.09m) subtract this amount

SET DIAMETER

2 ounce per 5 feet (60 ml per 1524 mm)
3 ounce per 5 feet (90 ml per 1524 mm)

Units are designed for line sets up to 50ft. Consult Lennox
Refrigerant Piping Manual for line sets over 50ft.

IMPORTANT

If line length is greater than 20 feet (6096mm), add
this amount. If line length is less than 20 feet (6096
mm), subtract this amount.

A–Leak Testing

 1– Attach gauge manifold and connect a drum of dry

nitrogen to center port of gauge manifold.

  2– Add a small amount of refrigerant to the lines. Open

high pressure valve on gauge manifold. Pressurize
line set and indoor coil to 150 psig (1034 kPa).

WARNING

Danger  of Explosion.
Can cause injury, death and equipment
damage.
When using dry nitrogen, use a pres-
sure–reducing regulator, set at 150
psig (1034 kPa) or less to prevent ex-
cessive pressure.

 3– Check lines and connections for leaks.

NOTE –  If electronic leak detector is used, add a trace of
refrigerant to nitrogen for detection by leak detector.

 4– Release nitrogen pressure from the system, cor-

rect any leaks and recheck.

B–Evacuating the System

Evacuating the system of non–condensables is critical
for proper operation of the unit. Non–condensables are
defined as any gas that will not condense under temper-
atures and pressures present during operation of an air
conditioning system. Non–condensable such as water
vapor, combines with refrigerant to produce substances
that corrode copper piping and compressor parts.

 1– Attach gauge manifold and connect vacuum

pump (with vacuum gauge) to center port of
gauge manifold. With both gauge manifold ser-

vice valves open, start pump and evacuate evapo-
rator and refrigerant lines.

IMPORTANT

A temperature vacuum gauge, mercury vacuum
(U–tube), or thermocouple gauge should be used.
The usual Bourdon tube gauges are not accurate
enough in the vacuum range.

IMPORTANT

The compressor should never be used to evacuate
a refrigeration or air conditioning system.

CAUTION

Danger of Equipment Damage. Avoid deep vacu-
um operation. Do not use compressors to evacuate
a system. Extremely low vacuums can cause inter-
nal arcing and compressor failure. Damage caused
by deep vacuum operation will void warranty.

 2– Evacuate system to 

absolute

 pressure of  .92 inches

of mercury, 23 mm of mercury, or 23,000 microns.

 3– After system has been evacuated to an absolute

pressure of .92 inches mercury, 23 mm mercury, or
23,000 microns, close manifold valve to center port.

 4– Stop vacuum pump and disconnect from gauge

manifold. Attach a drum of dry nitrogen to center
port of gauge manifold, open drum valve slightly
to purge line, then break vacuum in system to 3
psig (20.7 kPa) pressure by opening manifold high
pressure valve to center port.

 5– Close nitrogen valve, disconnect drum from man-

ifold center port and release nitrogen from system.

 6– Reconnect vacuum pump to manifold center port

hose. Evacuate the system to an absolute pressure
less than .197 inches of mercury, 5 mm of mercury,
or 5000 microns, then turn off vacuum pump. If the
absolute pressure rises above .197 inches of mer-
cury, 5 mm of mercury, or 5000 microns within a
20–minute period after stopping vacuum pump,
repeat step 6. If not, evacuation is complete.
This evacuation procedure is adequate for a new
installation with clean and dry lines. If excessive
moisture is present, the evacuation process may
be required more than once.

 7– After evacuation has been completed, close gauge

manifold service valves. Disconnect vacuum
pump from manifold center port and connect re-
frigerant drum. Pressurize system slightly with re-
frigerant to break vacuum.

C–Charging

If the system is completely void of refrigerant, the rec-
ommended and most accurate method of charging is
to weigh the refrigerant into the unit according to the
total amount shown on the unit nameplate. Also refer
to the SPECIFICATIONS tables on page 2.

Summary of Contents for HS25-211

Page 1: ...must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the Engineering Handbook for approved system matchups A misapplied system will cause errat...

Page 2: ...1 7 1 6 1 1 3 1 3 8 2 0 50 60 45 31 3 37 7 26 1 SPECIFICATIONS Model No HS25 261 HS25 311 HS25 411 Outdoor Coil Condenser Fan HCFC 22 charge furnished Face area sq ft Tube diameter in No of Rows Fins...

Page 3: ...uring a single orbit several pockets of gas are compressed simulta neously providing smooth continuous compression The scroll compressor is tolerant to the effects of liquid return If liquid enters th...

Page 4: ...the compressor contactor On initial ther mostat demand the compressor contactor is delayed for 8 5 seconds At the end of the delay the compressor is allowed to energize When thermostat demand is sa t...

Page 5: ...DISCHARGE TEMPERATURE SENSOR WIRES TO CONTROL BOX TO COMP TERM BOX IN 461 UNITS 3 1 2 TON AND SMALLER ONLY F High Pressure Switch A manual reset single pole single throw high pressure switch located...

Page 6: ...application of field fabricated lines Separate discharge and suction service ports are pro vided at the compressor for connection of gauge man ifold during charging procedure Model No LIQUID SUCTION L...

Page 7: ...rences are in construction Valves manufactured by Parker are forged assem blies Primore and Aeroquip valves are brazed to gether Valves are not rebuildable If a valve has failed it must be replaced Th...

Page 8: ...h gauge manifold and connect vacuum pump with vacuum gauge to center port of gauge manifold With both gauge manifold ser vice valves open start pump and evacuate evapo rator and refrigerant lines IMPO...

Page 9: ...table 6 as a general guide for performing main tenance checks Table 6 is not a procedure for charg ing the system Minor variations in these pressures may be expected due to differences in installation...

Page 10: ...erminal Y passes through discharge temperature sensor compressor thermostat and low pressure switch to energize time delay terminal 2 3 Time delay action is at the beginning of a thermostat demand Whe...

Reviews: