VII–DIAGRAMS / OPERATING SEQUENCE
A–Unit Diagram

   

B–Operation Sequence

 1–

WARNING–HS25 units using single–pole
contactors:  Capacitor terminal “COM,”
orange condenser fan wire and red “R”
compressor wire are all connected to L2
at all times.  Remove all power at discon-
nect before servicing.

 2– Cooling demand energizes thermostat

terminal Y.  Voltage from terminal Y
passes through discharge temperature
sensor (compressor thermostat) and low
pressure switch to energize time delay
terminal 2.

 3– Time delay action is at the beginning of a

thermostat demand.  When energized,
time delay TD1–1 delays 8.5 seconds be-
fore energizing TD1–1 terminal 3.  When
TD1–1 terminal 3 is energized, the con-
tactor coil is energized.

 4– When compressor contactor is ener-

gized, N.O. contacts close to energize
compressor terminal “C” (black wire)
and black condenser fan motor wire.
Condenser fan and compressor immedi-
ately begin operating.

Summary of Contents for HS25-211

Page 1: ...must be matched according to Lennox recommendations for the compressor to be covered under warranty Refer to the Engineering Handbook for approved system matchups A misapplied system will cause errat...

Page 2: ...1 7 1 6 1 1 3 1 3 8 2 0 50 60 45 31 3 37 7 26 1 SPECIFICATIONS Model No HS25 261 HS25 311 HS25 411 Outdoor Coil Condenser Fan HCFC 22 charge furnished Face area sq ft Tube diameter in No of Rows Fins...

Page 3: ...uring a single orbit several pockets of gas are compressed simulta neously providing smooth continuous compression The scroll compressor is tolerant to the effects of liquid return If liquid enters th...

Page 4: ...the compressor contactor On initial ther mostat demand the compressor contactor is delayed for 8 5 seconds At the end of the delay the compressor is allowed to energize When thermostat demand is sa t...

Page 5: ...DISCHARGE TEMPERATURE SENSOR WIRES TO CONTROL BOX TO COMP TERM BOX IN 461 UNITS 3 1 2 TON AND SMALLER ONLY F High Pressure Switch A manual reset single pole single throw high pressure switch located...

Page 6: ...application of field fabricated lines Separate discharge and suction service ports are pro vided at the compressor for connection of gauge man ifold during charging procedure Model No LIQUID SUCTION L...

Page 7: ...rences are in construction Valves manufactured by Parker are forged assem blies Primore and Aeroquip valves are brazed to gether Valves are not rebuildable If a valve has failed it must be replaced Th...

Page 8: ...h gauge manifold and connect vacuum pump with vacuum gauge to center port of gauge manifold With both gauge manifold ser vice valves open start pump and evacuate evapo rator and refrigerant lines IMPO...

Page 9: ...table 6 as a general guide for performing main tenance checks Table 6 is not a procedure for charg ing the system Minor variations in these pressures may be expected due to differences in installation...

Page 10: ...erminal Y passes through discharge temperature sensor compressor thermostat and low pressure switch to energize time delay terminal 2 3 Time delay action is at the beginning of a thermostat demand Whe...

Reviews: