background image

Page 8

G− Crankcase heater Thermostat (S40)

Thermostat S40 controls the crankcase heater in all units.

S40 is located on the liquid line.  When liquid line tempera-

ture drops below 50° F the thermostat S40 closes energizing

HR1. The thermostat will open, de−energizing HR1 once liq-

uid line temperature reaches  70° F .

H−Filter Drier

A filter drier designed for all HPXA16 model units is factory

installed in the liquid line. The filter drier is designed to re-

move moisture and foreign matter, which can lead to com-

pressor failure.

Moisture and  / or Acid Check

 

Because POE oils absorb moisture, the dryness of the

system must be verified any time the refrigerant sys-

tem is exposed to open air. 

A

  c

ompressor oil sample

must be taken to determine if excessive moisture has been

introduced to the oil. Table 3 lists kits available from Lennox

to check POE oils.

If oil sample taken from a system that has been exposed to

open air does not test in the dry color range, the filter drier

MUST be replaced.

IMPORTANT

Replacement filter drier MUST be approved for
R−410A refrigerant and POE application.

Foreign Matter Check

It is recommended that a liquid line filter drier be replaced

when the pressure drop across the filter drier is greater

than 4 psig.

I−Accumulator (HPXA16−060 only)

ALL 5 ton HPXA16 units are equipped with an accumulator.

The purpose of the accumulator is to trap and evaporate all

liquid refrigerant returning to the compressor.

J−Charge Compensator

HPXA16−048 series units are equipped with a charge com-
pensator located in the vapor line between the reversing
valve and outdoor coil manifold.  The compensator is used
to collect and store excess refrigerant in the heating mode.
Figure 11 shows operation of the charge compensator.

In heating mode, the vapor line passing through the charge
compensator tank is cooler than the liquid line. Excess re-
frigerant (condensed liquid) from the indoor coil is trapped
by the compensator. The vapor line is cooler than the liquid
line so liquid migrates from the liquid line to the compensa-
tor tank where it is stored. In cooling mode, the vapor line
passing through the charge compensator tank is hotter
than the liquid line. Stored liquid is boiled and forced back
into the liquid line for circulation.

FIGURE 11

CHARGE COMPENSATOR OPERATION

During cooling mode, the va-
por line is hotter than the liq-
uid line. Stored liquid is
heated (boiled) and forced
back into circulation.

During heating mode, the va-
por line is cooler than the liq-
uid line. Excess refrigerant is
forced into the charge com-
pensator where it condenses
and collects.

Vapor Line

(To Outdoor Coil)

Vapor Line

(From Compressor Discharge Port)

Vapor Line

(From Outdoor Coil)

Vapor Line

(To Compressor Suction Port)

Stored Liquid

To Liquid Line

To be Circulated

Through Indoor Coil

Excess Refrigerant

To be Condensed and Stored

as Liquid

Compensator Tank

Compensator Tank

COOLING MODE

HEATING MODE

K−Crankcase Heater (HR1)

Compressors in all units are equipped with a 70 watt belly-
band type crankcase heater. HR1 prevents liquid from ac-
cumulating in the compressor. HR1 is controlled by the
crankcaseheater thermostat.

L−Defrost System

The demand defrost controller measures differential tem-
peratures to detect when the system is performing poorly
because of ice build−up on the outdoor coil. The controller
self−calibrates" when the defrost system starts and after
each system defrost cycle. The defrost control board com-
ponents are shown in figure 12.

TABLE 3

KIT

CONTENTS

TUBE SHELF LIFE

10N46 − Refrigerant Analysis

Checkmate−RT700

10N45 − Acid Test Tubes

Checkmate−RT750A (three pack)

2 − 3 years @ room temperature. 3+
years refrigerated

10N44 − Moisture Test Tubes

Checkmate − RT751 Tubes (three
pack)

6 − 12 months @ room temperature. 2
years refrigerated

74N40 − Easy Oil Test Tubes

Checkmate − RT752C Tubes (three
pack)

2 − 3 years @ room temperature. 3+
years refrigerated

74N39 − Acid Test Kit

Sporlan One Shot − TA−1

Summary of Contents for HPXA16 series

Page 1: ...ice equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and service must be pe...

Page 2: ...230V 1ph 208 230V 1ph 208 230V 1ph 3 Maximum overcurrent protection amps 20 35 45 60 2 Minimum circuit ampacity 13 7 22 1 28 2 33 8 Compressor Rated load amps 10 3 16 7 21 2 25 7 p Locked rotor amps...

Page 3: ...NG SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the out er crescent shaped gas pocket crea...

Page 4: ...operate on first stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second stage Second stage high capacity is achieved by blocking the bypass port...

Page 5: ...tch Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating op eration on heat pump or below cooling operation the room temperature 5 F 3 Remove control access...

Page 6: ...ltage at the female connector end of the full wave rectifier plug The DC voltage reading should be 1 5 to 3 volts lower than the input voltage to the plug wire leads EX Input voltage is 24VAC output v...

Page 7: ...y will allow moisture to en ter the bearing resulting in motor failure See figure 9 FIGURE 8 A SEE TABLE 2 FAN GUARD Condenser fan and motor Wiring Drip loop TABLE 2 HPXA16 UNIT A DIM 1 8 024 036 1 1...

Page 8: ...ss re frigerant condensed liquid from the indoor coil is trapped by the compensator The vapor line is cooler than the liquid line so liquid migrates from the liquid line to the compensa tor tank where...

Page 9: ...s for a fifth time during the current Y1 Input the control will enter a lockout condi tion The 5 strike pressure switch lockout condition can be reset by cycling OFF the 24 volt power to the control b...

Page 10: ...d recognizes five temperature sensor range faults during a single Y1 compressor demand it re verts to a lockout mode and displays the appropriate code The board detects open sensor or out of tem perat...

Page 11: ...ast defrost cycle while the coil tempera ture remains below 35 F 2 C the demand defrost control will initiate a defrost cycle Actuation When the reversing valve is de energized the Y1 circuit is energ...

Page 12: ...r will check for ambient and coil faults open or shorted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re...

Page 13: ...nection to sys tem have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements SLOW Flash ON Discharge Line Tempera ture Fault This code detects s...

Page 14: ...The reversing valve is energized during cooling de mand and during defrost III REFRIGERANT SYSTEM Field refrigerant piping consists of liquid and vapor lines from the outdoor unit sweat connections U...

Page 15: ...for liquid line size 3 Replace stem cap and tighten it firmly Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1 Remove stem cap with an adjustable wrench 2 Using servic...

Page 16: ...he vapor valve service port Normally the high pres sure hose is connected to the liquid line port however connecting it to the vapor port better protects the man ifold gauge set from high pressure dam...

Page 17: ...in the heating season one of the following proce dures must be followed to ensure proper system charge Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant o...

Page 18: ...d indicate that the system is overcharged Pressures lower than those listed indicate that the system is undercharged Verify adjusted charge using the approach method Approach Method 4 Use the same dig...

Page 19: ...Vapor 65 18 3 222 143 244 136 232 134 249 126 75 23 9 256 145 282 139 266 136 289 134 85 29 4 302 145 325 142 309 139 330 140 95 35 0 349 147 377 144 359 142 378 143 105 40 6 403 149 428 146 410 144 4...

Page 20: ...5 506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Page 21: ...m POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the electrical power to unit OFF at dis connect switch e...

Page 22: ...Page 22 VII DIAGRAM OPERATING SEQUENCE...

Page 23: ...ost board sends 24 volts through Y1 OUT signal to the K1 compressor contactor coil 3 The defrost board sends 24 volts through Y2 OUT to the L34 compressor solenoid plug The 2 wire com pressor solenoid...

Reviews: