background image

Page 23

Sequence of Operation HPXA16−024/060

First Stage Cool (low capacity)

Transformer from indoor unit supplies 24VAC power to
the thermostat and outdoor unit controls.

1− Internal wiring energizes terminal O by cooling mode

selection, energizing the reversing valve. Cooling de-
mand initiates at Y1 in the thermostat.

2− 24VAC passes through high pressure switch S4 and

discharge thermostat switch S5 energizing compres-
sor contactor K1.

HPXA16−024

 − Compressor begins start up. Relay

K31 remains closed during start up and capacitor
C7 remains in the circuit. As compressor speeds up
K31 is energized, de−energizing capacitor C7.

3− K1−1 N.O. closes energizing compressor B1 and out-

door fan motor B4. Transformer T46 is also energized.

4− Solenoid L34 is NOT energized. The slider ring re-

mains open limiting compressor to low capacity.

Second Stage Cool (high capacity)

5− Second stage thermostat demand energizes  solenoid

relay K195. K195−1 closes sending voltage to rectifier
plug D4.  D4 converts the AC voltage to DC voltage and
energizes  L34 unloader solenoid. L34 then closes the
slider ring, allowing the compressor to operate at high
capacity.

Heating

A – Low Capacity

1−   Room thermostat in heating mode. Room thermostat

outputs Y1 signal to the defrost board in the heat pump
and to the indoor air handler.

2 − The defrost board checks for open low or high−pres-

sure switches and proper coil, ambient and discharge
sensor readings. If checks show no issues, the defrost
board sends 24 volts through Y1 OUT signal to the K1
compressor contactor coil.

3− K1−1 closes, energizing the compressor and outdoor

fan motor through the normally closed fan relay con-
tacts on the defrost board.

4− The compressor will run on low capacity along with the

single speed outdoor fan motor.

B – High Capacity (Ambient temperature above de-
frost board Y2 lock−in temperature)

1− Room thermostat in heating mode. Room thermostat

outputs Y1 and Y2 (if applicable to that room thermo-
stat) signal to the defrost board in the heat pump and to
the indoor unit.

 2− The defrost board checks for open low or high−pres-

sure switches and proper coil, ambient and discharge
sensor readings. If checks show no issues, the defrost
board sends 24 volts through Y1 OUT signal to the K1
compressor contactor coil.

3 − The defrost board sends 24 volts through Y2 OUT to

the L34 compressor solenoid plug. The 2− wire com-
pressor solenoid plug converts the 24volt AC outputs
to a 24volt DC signal input to the L34 internal high ca-
pacity solenoid valve in the compressor.

4 − K1−1 closes, energizing the compressor and outdoor

fan motor through the normally closed fan relay con-
tacts on the defrost board. The compressor runs high
capacity.

B – High Capacity (Ambient temperature below de-
frost board Y2 lock−in temperature)

1 − Room thermostat in heating mode. Room thermostat

outputs Y1 signal to the defrost board in the heat pump
and to the indoor unit.

 2 − The defrost board checks for open low or high−pres-

sure switches and proper coil, ambient and discharge
sensor readings. If checks show no issues, the defrost
board sends 24 volts through Y1 OUT signal to the K1
compressor contactor coil.

3 − The defrost board

 Y2 locks in 

sends 24 volts through

Y2 OUT to the L34 compressor solenoid plug. The plug
converts the 24volt AC outputs to a 24volt DC signal in-
put to the L34 internal high capacity solenoid valve in
the compressor.

4 − K1−1 closes, energizing the compressor and outdoor

fan motor through the normally closed fan relay con-
tacts on the defrost board. The compressor runs on
high capacity.

Defrost Mode

When a defrost cycle is initiated, the control ener-
gizes the reversing valve solenoid and turns off the
condenser fan. The control will also put 24VAC on
the W1" (auxiliary heat) line. The unit will stay in this
mode until either the coil sensor temperature is
above the selected termination temperature, the de-
frost time of 14 minutes has been completed, or the
room thermostat demand cycle has been satisfied.
(If the temperature select shunt is not installed, the
default termination temperature will be 90°F.) If the
room thermostat demand cycle terminates the
cycle, the defrost cycle will be held until the next
room thermostat demand cycle. If the coil sensor
temperature is still below the selected termination
temperature, the control will continue the defrost
cycle until the cycle is terminated in one of the meth-
ods mentioned above. If a defrost is terminated by
time and the coil temperature did not remain above
35°F (2°C) for 4 minutes the control will go to the
34−minute Time/Temperature mode.

Summary of Contents for HPXA16 series

Page 1: ...ice equipment rated for R 410A WARNING Improper installation adjustment alteration service or maintenance can cause property damage person al injury or loss of life Installation and service must be pe...

Page 2: ...230V 1ph 208 230V 1ph 208 230V 1ph 3 Maximum overcurrent protection amps 20 35 45 60 2 Minimum circuit ampacity 13 7 22 1 28 2 33 8 Compressor Rated load amps 10 3 16 7 21 2 25 7 p Locked rotor amps...

Page 3: ...NG SCROLL DISCHARGE SUCTION CROSS SECTION OF SCROLLS TIPS SEALED BY DISCHARGE PRESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the out er crescent shaped gas pocket crea...

Page 4: ...operate on first stage until demand is satisfied or the indoor temperature reaches the thermostat set point calling for second stage Second stage high capacity is achieved by blocking the bypass port...

Page 5: ...tch Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating op eration on heat pump or below cooling operation the room temperature 5 F 3 Remove control access...

Page 6: ...ltage at the female connector end of the full wave rectifier plug The DC voltage reading should be 1 5 to 3 volts lower than the input voltage to the plug wire leads EX Input voltage is 24VAC output v...

Page 7: ...y will allow moisture to en ter the bearing resulting in motor failure See figure 9 FIGURE 8 A SEE TABLE 2 FAN GUARD Condenser fan and motor Wiring Drip loop TABLE 2 HPXA16 UNIT A DIM 1 8 024 036 1 1...

Page 8: ...ss re frigerant condensed liquid from the indoor coil is trapped by the compensator The vapor line is cooler than the liquid line so liquid migrates from the liquid line to the compensa tor tank where...

Page 9: ...s for a fifth time during the current Y1 Input the control will enter a lockout condi tion The 5 strike pressure switch lockout condition can be reset by cycling OFF the 24 volt power to the control b...

Page 10: ...d recognizes five temperature sensor range faults during a single Y1 compressor demand it re verts to a lockout mode and displays the appropriate code The board detects open sensor or out of tem perat...

Page 11: ...ast defrost cycle while the coil tempera ture remains below 35 F 2 C the demand defrost control will initiate a defrost cycle Actuation When the reversing valve is de energized the Y1 circuit is energ...

Page 12: ...r will check for ambient and coil faults open or shorted If a fault exists the unit will remain in Heat Mode and no further test mode operation will be executed until the test short is removed and re...

Page 13: ...nection to sys tem have secure connections to system to prevent refrigerant leaks or errors in pressure and temperature measurements SLOW Flash ON Discharge Line Tempera ture Fault This code detects s...

Page 14: ...The reversing valve is energized during cooling de mand and during defrost III REFRIGERANT SYSTEM Field refrigerant piping consists of liquid and vapor lines from the outdoor unit sweat connections U...

Page 15: ...for liquid line size 3 Replace stem cap and tighten it firmly Tighten finger tight then tighten an additional 1 6 turn To Close Service Valve 1 Remove stem cap with an adjustable wrench 2 Using servic...

Page 16: ...he vapor valve service port Normally the high pres sure hose is connected to the liquid line port however connecting it to the vapor port better protects the man ifold gauge set from high pressure dam...

Page 17: ...in the heating season one of the following proce dures must be followed to ensure proper system charge Weighing in the Charge TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant o...

Page 18: ...d indicate that the system is overcharged Pressures lower than those listed indicate that the system is undercharged Verify adjusted charge using the approach method Approach Method 4 Use the same dig...

Page 19: ...Vapor 65 18 3 222 143 244 136 232 134 249 126 75 23 9 256 145 282 139 266 136 289 134 85 29 4 302 145 325 142 309 139 330 140 95 35 0 349 147 377 144 359 142 378 143 105 40 6 403 149 428 146 410 144 4...

Page 20: ...5 506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Page 21: ...m POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the electrical power to unit OFF at dis connect switch e...

Page 22: ...Page 22 VII DIAGRAM OPERATING SEQUENCE...

Page 23: ...ost board sends 24 volts through Y1 OUT signal to the K1 compressor contactor coil 3 The defrost board sends 24 volts through Y2 OUT to the L34 compressor solenoid plug The 2 wire com pressor solenoid...

Reviews: