background image

Page 12

 4 − Remove  the  pressure  tap valve cores from the

HPXA15 unit’s service valves. Connect an R22 cylin-
der with clean refrigerant to the vapor service valve.
Connect the R22 gauge set to the liquid line valve and
connect a recovery machine with an empty recovery
tank to the gauge set.

 5 − Set the recovery machine for liquid recovery and start

the recovery machine. Open the gauge set valves to
allow the recovery machine to pull a vacuum on the ex-
isting system line set and indoor coil.

 6 − Invert the cylinder of clean R22 and open its valve to

allow liquid refrigerant to flow into the system through
the vapor line valve. Allow the refrigerant to pass from
the cylinder and through the line set and the indoor coil
before it enters the recovery machine.

 7 − After all of the liquid refrigerant has been recovered,

switch the recovery machine to vapor recovery so that
all of the R22 vapor is recovered.

NOTE − A single system flush should remove all of the
mineral oil from the existing refrigerant lines and in-
door coil. A second flushing may be done (using clean
refrigerant) if insufficient amounts of mineral oil were
removed during the first flush.

 Each time the system

is flushed, you must allow the recovery machine
to pull a vacuum on the system at the end of the
procedure.

 8 − Close the valve on the inverted R22 drum and the

gauge set valves. Pump the remaining refrigerant out
of the recovery machine and turn the machine off.

 9 − Use nitrogen to break the vacuum on the refrigerant

lines and indoor coil before removing the recovery ma-
chine, gauges and R22 refrigerant drum. Reinstall
pressure tap valve cores into HPXA15 service valves.

10 −Install the provided check/expansion valve (approved

for use with R410A refrigerant) in the liquid line at the
indoor coil.

Manifold Gauge Set

Manifold gauge sets used with systems charged with
R410A refrigerant must be capable of handling the higher
system operating pressures. The gauges should be rated
for use with pressures of 0 − 800 on the high side and a low
side of 30" vacuum to 250 psi with dampened speed to 500
psi. Gauge hoses must be rated for use at up to 800 psi of
pressure with a 4000 psi burst rating.

Service Valves

Access the liquid line and vapor line service valves (figures
13 and 14) and gauge ports are used for leak testing, eva-
cuating, charging and checking charge. See table 1 for
torque requirements.

Each valve is equipped with a service port which has a fac-
tory−installed Schrader valve. A service port cap protects
the Schrader valve from contamination and serves as the
primary leak seal.

Table 1

Torque Requirements

Part

Recommended Torque

Service valve cap

8 ft.− lb.

11 NM

Sheet metal screws

16 in.− lb.

2 NM

Machine screws #10

28 in.− lb.

3 NM

Compressor bolts

90 in.− lb.

10 NM

Gauge port seal cap

8 ft.− lb.

11 NM

IMPORTANT

Service valves are closed to the outdoor unit and
open to line set connections. Do not open the valves
until refrigerant lines have been leak tested and
evacuated. All precautions should be exercised to
keep the system free from dirt, moisture and air.

To Access Schrader Port:

 1 − Remove service port cap with an adjustable wrench.
 2 − Connect gauge to the service port.
 3 − When testing is complete, replace service port cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Service Valve:

 1 − Remove stem cap with an adjustable wrench.
 2 − Using service wrench and hex head extension, back

the stem out counterclockwise as far as it will go.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace stem cap and tighten it firmly. Tighten finger

tight, then tighten an additional 1/6 turn.

To Close Service Valve:

 1 − Remove stem cap with an adjustable wrench.

 2 − Using service wrench and hex head extension, turn

stem clockwise to seat valve. Tighten it firmly.

NOTE − Use a 3/16" hex head extension for liquid line
sizes or a 5/16" extension for vapor line sizes.

 3 − Replace stem cap. Tighten finger tight, then tighten an

additional 1/6 turn.

Vapor Line (Ball Type) Valve

Vapor line service valves function the same way as the oth-
er valves, the difference is in the construction. These
valves are not rebuildable. If a valve has failed, you must
replace it. A ball valve valve is illustrated in figure 14.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−
free seal.

Summary of Contents for HPXA15 SERIES

Page 1: ...a qualified installer or service agency INSTALLATION INSTRUCTIONS HPXA15 SERIES UNITS HEAT PUMP UNITS 504 713M 02 04 Supersedes 12 02 Table of Contents HPXA15 Outdoor Unit 1 Shipping Packing List 1 G...

Page 2: ...in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 16 3 4 2 7 8 5 1 2 HPXA15 024 mm 708 657 759 311 570 367 562 425 730 140 HPXA15 030 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8 17 1 4 3...

Page 3: ...s 1 Place a sound absorbing material such as Isomode under the unit if it will be installed in a location or posi tion that will transmit sound or vibration to the living area or adjacent buildings 2...

Page 4: ...y support the unit Consult local codes for rooftop applications If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be constructed See figure 3 Size barrier at least...

Page 5: ...eld wiring diagram NOTE A complete unit wiring diagram is located in side the unit control box cover 3 Install room thermostat ordered separately on an in side wall approximately in the center of the...

Page 6: ...Corp 9351 L9 for proper size type and application of field fabricated lines Valve sizes are also listed in table 1 Refrigerant Connections HPXA15 Matched with New Indoor Coil and Line Set If an existi...

Page 7: ...ure 9 shows how to install line sets on horizontal runs Figure 10 shows how to make a transi tion from horizontal to vertical Finally figure 11 shows how to place the outdoor unit and line set Refrige...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...e Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 10 Outsid...

Page 10: ...Engineering Handbook for approved TXV match ups and application information Check expansion valves equipped with Chatleff fittings are available from Lennox Refer to the Engineering Handbook for appli...

Page 11: ...ine valve Disconnect all power to the existing outdoor unit Re fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system Disconn...

Page 12: ...se at up to 800 psi of pressure with a 4000 psi burst rating Service Valves Access the liquid line and vapor line service valves figures 13 and 14 and gauge ports are used for leak testing eva cuating...

Page 13: ...al injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system use a regu...

Page 14: ...set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid...

Page 15: ...e 4 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line te...

Page 16: ...lations Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the syste...

Page 17: ...door Coil E t i Ai HPXA15 024 HPXA15 030 HPXA15 036 HPXA15 042 HPXA15 048 HPXA15 060 Entering Air Temp F C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 65 18 3 252 131...

Page 18: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Page 19: ...t control defrost relay time delay diagnostic LEDs and a terminal strip for field wiring connections See figure 17 The control provides automatic switching from normal heating operation to defrost mod...

Page 20: ...The service light thermostat provides a signal which activates the room ther mostat service light during periods of inefficient operation Diagnostic LEDs The defrost board uses two LEDs for diagnosti...

Page 21: ...re lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Reviews: