background image

Page 11

Required Equipment

You will need the following equipment in order to flush the
existing line set and indoor coil: two clean R22 recovery
bottles, an oilless recovery machine with a pump down fea-
ture, and two sets of gauges (one for use with R22 and one
for use with the R410A).

Flushing Procedure

 1 − Remove existing R22 refrigerant using the appropri-

ate procedure below.

If the existing outdoor unit is not equipped with
shut−off valves, or if the unit is not operational
AND you plan to use the existing R22 refrigerant to
flush the system −−

 

Disconnect all power to the exist-

ing outdoor unit. Connect the existing unit, a 

clean

 re-

covery cylinder and the recovery machine according
to the instructions provided with the recovery ma-
chine. Remove all R22 refrigerant from the existing
system. Refer to gauges after shutdown to confirm
that the entire system is completely void of refrigerant.
Disconnect the liquid and vapor lines from the existing
outdoor unit.

If the existing outdoor unit is equipped with manu-
al shut−off valves AND you plan to use NEW R22
refrigerant to flush the system 

−− 

Start the existing

R22 system in the cooling mode and close the liquid
line valve. Pump all of the existing R22 refrigerant
back into the outdoor unit. (It may be necessary to by-
pass the low pressure switches to ensure complete re-

frigerant evacuation.) When the low side system pres-
sures reach 0 psig, close the vapor line valve.
Disconnect all power to the existing outdoor unit. Re-
fer to gauges after shutdown to confirm that the valves
are not allowing refrigerant to flow back into the low
side of the system. Disconnect the liquid and vapor
lines from the existing outdoor unit.

 2 − Remove the existing outdoor unit. Set the new R410A

unit and follow the brazing connection procedure
which begins on the previous page to make line set
connections. 

DO NOT install provided R410A

check/expansion valve at this time. 

Make low voltage and line voltage connections to the
new outdoor unit. 

DO NOT turn on power to the unit

or open the outdoor unit service valves at this
time.

 3 − Remove the existing refrigerant flow control orifice or

thermal expansion/check valve before continuing with
flushing procedures. The existing devices are not ap-
proved for use with R410A refrigerant and may pre-
vent proper flushing. Use a field−provided fitting to re-
connect the lines.

IMPORTANT

The line set and indoor coil must be flushed with at
least the same amount of clean refrigerant that pre-
viously charged the system. Check the charge in
the flushing cylinder before proceeding.

Flushing Connections

Figure 12

LOW

PRESSURE

HIGH

PRESSURE

VAPOR LINE

SERVICE VALVE

Indoor Coil

HPXA15 Unit

GAUGE MANIFOLD

Recovery Machine

Inverted R22 Cylinder

(Contains clean R22 to

be used for flushing)

LIQUID LINE

SERVICE VALVE

INLET

DISCHARGE

TANK RETURN

CLOSED

OPENED

Existing

EXISTING VAPOR LINE

EXISTING LIQUID LINE

RECOVERY

CYLINDER

NOTE − The inverted R22 cylinder must con-
tain at least the same amount of refrigerant
as was recovered from the existing system.

Summary of Contents for HPXA15 SERIES

Page 1: ...a qualified installer or service agency INSTALLATION INSTRUCTIONS HPXA15 SERIES UNITS HEAT PUMP UNITS 504 713M 02 04 Supersedes 12 02 Table of Contents HPXA15 Outdoor Unit 1 Shipping Packing List 1 G...

Page 2: ...in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 16 3 4 2 7 8 5 1 2 HPXA15 024 mm 708 657 759 311 570 367 562 425 730 140 HPXA15 030 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8 17 1 4 3...

Page 3: ...s 1 Place a sound absorbing material such as Isomode under the unit if it will be installed in a location or posi tion that will transmit sound or vibration to the living area or adjacent buildings 2...

Page 4: ...y support the unit Consult local codes for rooftop applications If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be constructed See figure 3 Size barrier at least...

Page 5: ...eld wiring diagram NOTE A complete unit wiring diagram is located in side the unit control box cover 3 Install room thermostat ordered separately on an in side wall approximately in the center of the...

Page 6: ...Corp 9351 L9 for proper size type and application of field fabricated lines Valve sizes are also listed in table 1 Refrigerant Connections HPXA15 Matched with New Indoor Coil and Line Set If an existi...

Page 7: ...ure 9 shows how to install line sets on horizontal runs Figure 10 shows how to make a transi tion from horizontal to vertical Finally figure 11 shows how to place the outdoor unit and line set Refrige...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...e Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 10 Outsid...

Page 10: ...Engineering Handbook for approved TXV match ups and application information Check expansion valves equipped with Chatleff fittings are available from Lennox Refer to the Engineering Handbook for appli...

Page 11: ...ine valve Disconnect all power to the existing outdoor unit Re fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system Disconn...

Page 12: ...se at up to 800 psi of pressure with a 4000 psi burst rating Service Valves Access the liquid line and vapor line service valves figures 13 and 14 and gauge ports are used for leak testing eva cuating...

Page 13: ...al injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system use a regu...

Page 14: ...set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid...

Page 15: ...e 4 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line te...

Page 16: ...lations Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the syste...

Page 17: ...door Coil E t i Ai HPXA15 024 HPXA15 030 HPXA15 036 HPXA15 042 HPXA15 048 HPXA15 060 Entering Air Temp F C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 65 18 3 252 131...

Page 18: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Page 19: ...t control defrost relay time delay diagnostic LEDs and a terminal strip for field wiring connections See figure 17 The control provides automatic switching from normal heating operation to defrost mod...

Page 20: ...The service light thermostat provides a signal which activates the room ther mostat service light during periods of inefficient operation Diagnostic LEDs The defrost board uses two LEDs for diagnosti...

Page 21: ...re lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Reviews: