Isolation Grommets

Locate the provided isolation grommets. Use a knife to slit
the webbing on each grommet. Slide larger grommet onto
vapor line and smaller grommet onto liquid line. Insert
grommets into mullion to isolate refrigerant lines from
sheet metal edges.

WARNING

Polyol ester (POE) oils used with R410A refrigerant
absorb moisture very quickly. It is very important
that the refrigerant system be kept closed as much
as possible. DO NOT remove line set caps or ser-
vice valve stub caps until you are ready to make
connections.

Brazing Connection Procedure

 1 − The end of the refrigerant line must be cut square and

its internal shape must remain round. The line must be
free of nicks or dents and must be deburred (I.D. and
O.D.)

 2 − Before making line set connections, use dry nitrogen to

purge the refrigerant piping. This will help to prevent
oxidation and the introduction of moisture into the sys-
tem.

 3 − Use silver alloy brazing rods (5 or 6 percent minimum

silver alloy for copper−to−copper brazing or 45 percent
silver alloy for copper−to−brass or copper−to−steel braz-
ing). Wrap a wet cloth around the valve body and the
copper tube stub. Remove light maroon washers from
service valves and shield light maroon stickers in order
to protect them during brazing. Braze the line set to the
service valve.

 4 − Quench the joint with water or a wet cloth to prevent

heat damage to the valve core and opening port.

IMPORTANT − The tube end must stay bottomed in the
fitting during final assembly to ensure proper seating,
sealing and rigidity.

Refrigerant Metering Device

HPXA15 units are used in check expansion valve systems
only. See the Lennox Engineering Handbook for approved
TXV match-ups and application information.

Check expansion valves equipped with Chatleff fittings
are available from Lennox. Refer to the Engineering
Handbook for applicable expansion valves for use with
specific match-ups.

If you install a check expansion valve with an indoor coil
that includes a fixed orifice, remove the orifice before
installing the check expansion valve.

See figure 1  for installation of the check expansion valve.

Metering Device Installation

expansion 

valve

o−ring

o−ring

strainer

liquid line 

stub

distributor

Figure 1 

IMPORTANT

Failure to remove RFC orifice when installing an ex-
pansion valve on the indoor coil will result in improp-
er operation and damage to the system.

Flushing Existing Line Set & Indoor Coil

 

WARNING

Danger of fire. Bleeding the refrigerant
charge from only the high side may
result in the low side shell and suc-
tion tubing being pressurized. App-
plication of a brazing torch while pres-
surized may result in ignition of the
refrigerant and oil mixture − check the
high and low pressures before unbra-
zing.

IMPORTANT

If this unit is being matched with an approved line
set or indoor coil that was previously charged with
R22 refrigerant, or if it is being matched with a coil
that was manufactured before January of 1999, the
coil and line set must be flushed prior to installation.
Take care to empty all existing traps. Polyol ester
(POE) oils are used in Lennox units charged with
R410A refrigerant. Residual mineral oil can act as an
insulator, preventing proper heat transfer. It can
also clog the thermal expansion valve, reducing
system performance and capacity.
Failure to properly flush the system per the instruc-
tions below will void the warranty.

CAUTION

This procedure should not be performed on sys-
tems which contain contaminants (Example: com-
pressor burn out).

Summary of Contents for HPXA15 SERIES

Page 1: ...a qualified installer or service agency INSTALLATION INSTRUCTIONS HPXA15 SERIES UNITS HEAT PUMP UNITS 504 713M 02 04 Supersedes 12 02 Table of Contents HPXA15 Outdoor Unit 1 Shipping Packing List 1 G...

Page 2: ...in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 16 3 4 2 7 8 5 1 2 HPXA15 024 mm 708 657 759 311 570 367 562 425 730 140 HPXA15 030 in 30 7 8 32 1 8 34 1 16 12 3 4 26 5 8 18 5 8 28 1 8 17 1 4 3...

Page 3: ...s 1 Place a sound absorbing material such as Isomode under the unit if it will be installed in a location or posi tion that will transmit sound or vibration to the living area or adjacent buildings 2...

Page 4: ...y support the unit Consult local codes for rooftop applications If unit coil cannot be mounted away from prevailing winter winds a wind barrier should be constructed See figure 3 Size barrier at least...

Page 5: ...eld wiring diagram NOTE A complete unit wiring diagram is located in side the unit control box cover 3 Install room thermostat ordered separately on an in side wall approximately in the center of the...

Page 6: ...Corp 9351 L9 for proper size type and application of field fabricated lines Valve sizes are also listed in table 1 Refrigerant Connections HPXA15 Matched with New Indoor Coil and Line Set If an existi...

Page 7: ...ure 9 shows how to install line sets on horizontal runs Figure 10 shows how to make a transi tion from horizontal to vertical Finally figure 11 shows how to place the outdoor unit and line set Refrige...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...e Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 10 Outsid...

Page 10: ...Engineering Handbook for approved TXV match ups and application information Check expansion valves equipped with Chatleff fittings are available from Lennox Refer to the Engineering Handbook for appli...

Page 11: ...ine valve Disconnect all power to the existing outdoor unit Re fer to gauges after shutdown to confirm that the valves are not allowing refrigerant to flow back into the low side of the system Disconn...

Page 12: ...se at up to 800 psi of pressure with a 4000 psi burst rating Service Valves Access the liquid line and vapor line service valves figures 13 and 14 and gauge ports are used for leak testing eva cuating...

Page 13: ...al injury WARNING Danger of explosion Can cause equipment damage injury or death When using a high pressure gas such as dry nitrogen to pressurize a refrigeration or air conditioning system use a regu...

Page 14: ...set to 150 psig 1034 kPa and purge the hose Open the manifold gauge valves to break the vacuum in the line set and indoor unit Close the manifold gauge valves WARNING Danger of Equipment Damage Avoid...

Page 15: ...e 4 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line te...

Page 16: ...lations Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the syste...

Page 17: ...door Coil E t i Ai HPXA15 024 HPXA15 030 HPXA15 036 HPXA15 042 HPXA15 048 HPXA15 060 Entering Air Temp F C Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor 65 18 3 252 131...

Page 18: ...506 5 43 125 0 74 214 0 105 340 5 136 512 9 44 127 3 75 217 4 106 345 3 137 519 3 45 129 7 76 220 9 107 350 1 138 525 8 46 132 2 77 224 4 108 355 0 139 532 4 47 134 6 78 228 0 109 360 0 140 539 0 48...

Page 19: ...t control defrost relay time delay diagnostic LEDs and a terminal strip for field wiring connections See figure 17 The control provides automatic switching from normal heating operation to defrost mod...

Page 20: ...The service light thermostat provides a signal which activates the room ther mostat service light during periods of inefficient operation Diagnostic LEDs The defrost board uses two LEDs for diagnosti...

Page 21: ...re lubrication is needed 3 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Reviews: