HP40 Heat Pump Unit

HP40 heat pumps use R407C which is an ozone friendly
HFC refrigerant. This unit must be installed with a match-
ing indoor coil and line set as outlined in the Lennox Engi-
neering Handbook. HP40 heat pumps are designed for
use in expansion valve systems only. They are not de-
signed to be used in RFC systems. An expansion valve
and filter drier approved for use with R407C have been
shipped with the unit. These components must be
installed prior to unit operation.

IMPORTANT

This unit must be matched with an indoor coil as
specified in Lennox’ Engineering Handbook.
Coils previously charged with R22 must be
flushed.

WARNING

This equipment must only be installed and serviced
by properly qualified personnel. Equipment con-
tains dangerous voltages and moving parts. Al-
ways switch off power supply before opening any
access panel. Electrical control panel doors and fan
access door must be locked to prevent unautho-
rized access at beginning of instruction.

WARNING

Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

INSTALLATION
INSTRUCTIONS

HP40 Heat Pump Units

HEAT PUMP UNITS
1−1/2 through 5 ton
504,538M
06/04
Supersedes 11/02

Table of Contents

HP40 Heat Pump Unit

1

. . . . . . . . . . . . . . . . . . . . . . . . . . 

Shipping & Packing List

1

. . . . . . . . . . . . . . . . . . . . . . . . . 

General Information

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Unit Dimensions

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Setting the Unit

3

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Electrical

4

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Plumbing

5

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Refrigerant Metering Device

5

. . . . . . . . . . . . . . . . . . . . . 

Manifold Gauge Set

7

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Liquid & Vapor Line Service Valves

7

. . . . . . . . . . . . . . . 

Leak Testing

8

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

System Evacuation

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Start−Up

9

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Charging Considerations

10

. . . . . . . . . . . . . . . . . . . . . . . 

System Operation

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Defrost System

12

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Maintenance

13

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

RETAIN THESE INSTRUCTIONS

FOR FUTURE REFERENCE

Shipping & Packing List

 1 − Assembled HP40 heat pump unit

 1 − Bag assembly:
 

1 − Sight glass

 

1 − Coupling reducer, 5/16 x 3/8 inch (024)

Check unit for shipping damage. If any damage is found,
contact the last carrier immediately.

General Information

These instructions are intended as a general guide and
do not supersede national or local codes in any way. Con-
sult authorities having jurisdiction before installation.

The HP40 unit is CE marked" in accordance with the re-
quirements of the latest European Directives for Electrical
and Machinery Safety and Electromagnetic Compatibility.
In addition, HP40 units have type Approval Certification
with the Gas Appliance Directive.

IMPORTANT

International Legislation bans the intentional vent-
ing of refrigerant (CFCs and HCFCs). Approved
methods of recovery, recycling or reclaiming must
be followed. Fines and/or incarceration may be lev-
ied for noncompliance.

Litho U.S.A.

Summary of Contents for HP40

Page 1: ...th INSTALLATION INSTRUCTIONS HP40 Heat Pump Units HEAT PUMP UNITS 1 1 2 through 5 ton 504 538M 06 04 Supersedes 11 02 Table of Contents HP40 Heat Pump Unit 1 Shipping Packing List 1 General Informatio...

Page 2: ...ICAL INLETS 111 162 162 TOP VIEW BASE SECTION 51 19 111 111 111 111 111 COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL STAND OFF KIT Field installed 4 required LIQUID LINE CONNECTION...

Page 3: ...a support frame is constructed it must not block drain holes in the base of the unit 4 When you install the unit in areas where low ambient temperatures exist locate the unit so winter prevail ing win...

Page 4: ...sunlight drafts or vibration Do not install the thermostat on an outside wall The most desirable position for the thermostat is near the cen ter of the conditioned area and approximately 1 5 m from t...

Page 5: ...it is being matched with an approved line set or indoor coil which was previously charged with R22 refrigerant or if it is being matched with a coil which was manufactured before January of 1999 the c...

Page 6: ...The line set and indoor coil must be flushed with at least the same amount of clean refrigerant that previously charged the system Check the charge in the flushing cylinder before proceeding 5 Set th...

Page 7: ...e sets used with systems charged with R407C refrigerant must be able to accommodate higher system operating pressures The gauges should be rated for pressures of 0 800 psi on the high side and a low s...

Page 8: ...ced A ball valve is il lustrated in figure 8 The ball valve is equipped with a service port anda fac tory installed Schrader valve A service port cap is supplied to protect the Schrader valve from con...

Page 9: ...0 microns of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from the vacuum pump Attach the manifold center port hose to a nitro ge...

Page 10: ...C airflow over the outdoor coil will need to be reduced to drive up the liquid line pressure to a range of 1379 to 1724 kPa To do this block off the outdoor coil with cardboard or a plas tic sheet BLO...

Page 11: ...2 21 138 951 121 834 38 229 1578 202 1392 21 141 972 123 848 39 232 1599 205 1413 22 143 985 126 868 40 236 1627 208 1431 22 146 1006 128 882 40 239 1647 211 1454 23 148 1020 130 896 41 242 1668 214 1...

Page 12: ...o allow the crankcase heater sufficient time to prevent compressor from slugging Defrost System The HP40 defrost system includes two components a de frost thermostat and a defrost control Defrost Ther...

Page 13: ...using a pressure switch the factory installed jumper wire must be connected Diagnostic LEDs The defrost board uses two LEDs for diagnostics The LEDs flash a specific sequence according to the conditi...

Page 14: ...Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off Outdoor Coil Entering Air Temperature Discharge Pressur...

Page 15: ...Page 15...

Page 16: ...Page 16 Lennox Industries P O Box 174 Westgate Interchange Northampton NN5 5AG Telephone 01604 591159 Facsimile 01604 587536...

Reviews: