Page 3
ELECTRICAL DATA
Model No.
HP29-018
HP29-024
HP29-030
HP29-036
Line voltage data 60 hz
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
1ph
208/230v
3ph
460v
3ph
Rated load amps
7.9
10.1
14.7
16.0
11.0
5.6
Compressor
Power factor
.97
.96
.90
.91
.83
.83
Locked rotor amps
49.0
60.0
84.0
100
75.0
37.5
Outdoor Coil
Full load amps
1.1
1.1
1.1
1.1
1.1
0.55
Outdoor Coil
Fan Motor
Locked rotor amps
1.9
1.9
1.9
1.9
1.9
1.0
Rec. maximum fuse or circuit breaker size (amps)
15
20
30
35
20
10
*Minimum circuit ampacity
11.0
13.8
19.5
21.1
14.0
6.5
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
ELECTRICAL DATA
Model No.
HP29-042
HP29-048
HP29-060
Line voltage data 60 hz
208/230v
1ph
208/230v
3ph
460v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
208/230v
1ph
208/230v
3ph
460v
3ph
575v
3ph
Rated load amps
20.3
12.8
6.4
23.7
13.5
7.4
5.8
28.8
17.3
9.0
7.1
Compressor
Power factor
.84
.93
.93
.96
.88
.88
.88
.92
.86
.86
.86
Locked rotor amps
127
87.0
44.0
129.0
120.0
49.5
48.0
169.0
137.0
62.0
51.0
Outdoor Coil
Full load amps
1.9
1.1
0.55
1.9
1.9
0.90
0.90
1.9
1.9
0.90
0.90
Outdoor Coil
Fan Motor
Locked rotor amps
4.1
1.9
1.0
4.1
4.1
2.1
2.1
4.1
4.1
2.1
2.1
Rec. maximum fuse or circuit breaker size (amps)
40
25
15
50
30
15
10
60
40
20
15
*Minimum circuit ampacity
27.3
17.1
8.6
31.5
18.8
10.2
8.2
37.4
23.5
12.2
9.8
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus 10% and minus 5% of line voltage.
I − UNIT INFORMATION
HP29 units are available in 1 -1/2, 2, 2 -1/2, 3, 3 -1/2, 4 and 5
ton capacities.
All major components (indoor blower/coil) must be matched
according to Lennox recommendations for the compressor to
be covered under warranty. Refer to the Engineering
Handbook for approved system matchups. A misapplied
system will cause erratic operation and can result in early
compressor failure.
II − UNIT COMPONENTS
Unit components are illustrated in figure 2.
A − Control Box (Figures 3, 4 and 5)
Electrical openings are provided under the control box
cover. Field thermostat wiring is made to color-coded
pigtail connections as illustrated in figure 1.
FIGURE 1
THERMOSTAT WIRING IDENTIFICATION
BLACK
BEIG
E
ORANGE
YELLOW
RED
FROM OUTDOOR UNIT
TO
INDOOR UNIT/
THERMOST
AT
24V (POWER) INPUT
TO OUTDOOR UNIT
(COMPRESSOR)
(REVERSINGVALVE)
(ELECTRIC
HEAT)
(COMMON)
INPUT
INPUT
DEFROST OUTPUT
COMPRESSOR
CHECK/EXPANSION
VALVE
CONTROL
BOX
REVERSING
VALVE
DISCHARGE
MUFFLER
OUTDOOR
FAN/MOTOR
HP29 UNIT COMPONENTS
FIGURE 2
DEFROST
THERMOSTAT
BI-FLOW
FILTER DRIER
RECIPROCATING COMPRESSOR
SHOWN