background image

Page 16

Model

 Condensing Temp

°

F Warmer Than Liquid Line

HP29−261

HP29−311

HP29−461

HP29−211

HP29−511

HP29−651

SUBCOOLING METHOD

AMBIENT TEMPERATURE BELOW 60 

_

F (16 

_

C)

8°F (4.4°C)
6°F (3.3°C)

10°F (5.6°C)

12°F (6.7°C)
13°F (7.2°C)

5°F (2.8°C)

HP29−411

8°F (4.4°C)

TABLE 13

 

TABLE 14

HP29−018

HP29−036
HP29−042

HP29−030

HP29−024

HP29−048
HP29−060

4

_

F (2.2

_

C)

11

_

F (6.1)

7

_

F (3.9

_

C)

Model

 Condensing Temp

°

F Warmer Than Liquid Line

SUBCOOLING METHOD

AMBIENT TEMPERATURE BELOW 60 

_

F (16 

_

C)

8°F (4.4°C)

12°F (6.7°C)

10°F (5.6°C)

10°F (5.6°C)

71

PSIG

HP29 NORMAL OPERATING PRESSURES*

OUTDOORCOIL

ENTERINGAIR

TEMPERATURE

HP29−261

HP29−311

HP29−411

65

°

 F (TXV)

75

°

F (TXV)

85

°

F (TXV)

95

°

F (TXV)

LIQ.

+ 10

+ 10

PSIG

PSIG

LIQ.

+ 10

+ 10

PSIG

PSIG

LIQ.

+ 10

+ 10

PSIG

PSIG

105

°

F (TXV)

LIQ.

+ 10

+ 10

PSIG

PSIG

HP29−211

HP29−461

HP29−511

HP29−651

LIQ.

+ 10

+ 10

PSIG

PSIG

LIQ.

+ 10

PSIG

+ 10

VAP.

+ 10

PSIG

LIQ.

+ 10

PSIG

148
171
200
230
263

71
74
76
78
81

156
182
210
241
275

70
72
74
75
78

165
195
220
254
292

73
75
77
79
81

171
197
228
261
299

68
70
72
74
77

173
203

267
307

69
71
73
75
77

163
191
225
259
295

74
75
76
78
79

166
195
227
261
302

73
74
76
78

233

VAP.

VAP.

VAP.

VAP.

VAP.

VAP.

*These are typical pressures only. Indoor evaporator match up, indoor air quality and evaporator load will cause the pressures to vary.

TABLE 15

TABLE 16

HP29 NORMAL OPERATING PRESSURES

OUTDOOR

COIL AIR

HP29-018

HP29-024

HP29-030

HP29−036

HP29-042

HP29-048

HP29-060

MODE

COIL AIR

ENTERING

 TEMP.

_

F (

_

C)

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

LIQ.

+10

PSIG

SUC.

+5

PSIG

75 (24)

171

74

182

72

184

71

184

74

180

71

180

70

183

72

Cooling

TXV

85 (29)

200

76

210

74

214

72

215

75

205

74

210

70

214

73

g

TXV

Only

95 (35)

230

78

241

75

246

74

249

76

245

75

240

71

248

75

Only

105 (41)

263

81

275

78

282

45

285

76

280

76

280

72

285

77

20 (−7)

166

33

170

28

186

28

170

27

180

30

175

25

186

25

Heating

30 (−1)

177

42

184

36

198

36

180

38

190

40

185

35

200

32

Heating

40 (4)

  188

51

 194

42

210

43

230

50

195

47

195

43

212

42

50 (10)

200

61

212

56

218

53

240

55

205

54

206

52

224

50

* These are typical pressures only. Indoor evaporator match up, indoor air quality and evaporator load will cause the pressures to vary.

IMPORTANT

Use tables 15 and 16  as a general guide for
performing maintenance checks. Table  is not a
procedure for charging the system. Minor variations
in pressures may be expected due to differences in
installations. Significant deviations may mean the
system is not properly charged or that a problem
exists with some component in the system. Used
prudently, tables 15 and 16  could serve as a useful
service guide.

E − Oil Charge

Refer to tables 6 and 7 on page 7.

V − MAINTENANCE

At the beginning of each heating or cooling season, the
system should be cleaned as follows:

A − Outdoor Unit

 1 − Clean and inspect outdoor coil. (Coil may be

flushed with a water hose).

 2 − Visually inspect all connecting lines, joints and

coils for evidence of oil leaks.

IMPORTANT

If insufficient heating or cooling occurs, the unit
should be gauged and refrigerant charge
checked.

B − Indoor Coil

 1 − Clean coil if necessary.

 2 − Check connecting lines and coil for evidence of oil

leaks.

 3 − Check condensate line and clean if necessary.

C − Indoor Unit

 1 − Clean or change filters.

 2 − Bearings  are  pre-lubricated  and  need  no  further

oiling.

 3 − Check all wiring for loose connections.

 4 − Check for correct voltage at unit.

 5 − Check amp−draw on blower motor.

Unit nameplate_________Actual_________.

Summary of Contents for HP29 Series

Page 1: ...blades 18 457 3 18 457 3 18 457 4 Outdoor Motor hp W 1 6 124 1 6 124 1 6 124 Outdoor Coil F Cfm L s 2400 1135 2400 1135 2500 1180 Coil Fan Rpm 1105 1105 1100 Watts 180 180 200 Refrigerant charge furni...

Page 2: ...oz 5 34kg Liquid line in mm o d connection sweat 3 8 9 5 3 8 9 5 3 8 9 5 3 8 9 5 Vapor line in mm o d connection sweat 7 8 22 2 7 8 22 2 7 8 22 2 1 1 8 28 6 Shipping weight lbs kg 1 package 182 83 19...

Page 3: ...1 9 1 0 4 1 4 1 2 1 2 1 4 1 4 1 2 1 2 1 Rec maximum fuse or circuit breaker size amps 40 25 15 50 30 15 10 60 40 20 15 Minimum circuit ampacity 27 3 17 1 8 6 31 5 18 8 10 2 8 2 37 4 23 5 12 2 9 8 Refe...

Page 4: ...l or reciprocating and fan in single phase units use permanent split capacitor motors The capacitor is located inside the unit control box see figure 4 and 5 A single dual capacitor C12 is used for bo...

Page 5: ...t terminal Y1 24V Single phase HP29 units are not equipped with a 24V transformer All 24 VAC controls are powered by the indoor unit Refer to unit wiring diagram J voltage units only are equipped with...

Page 6: ...ced to 6 5 seconds The TEST mode may be started at any time If the jumper is in the TEST position at power up or for longer than five minutes the control will ignore the TEST selection and will defaul...

Page 7: ...90 T3 minutes See figure 7 The defrost timing jumper is factory installed to provide a 60 minute defrost interval If the timing selector jumper is not in place the control defaults to a 90 minute defr...

Page 8: ...the unit The time delay may be bypassed by placing the temperature select jumper across the TEST pins for 0 5 seconds Pressure Switch Circuit The defrost control board used in optional units includes...

Page 9: ...nd its inherent properties Two identical scrolls are mated together forming concentric spiral shapes One scroll remains stationary while the other is allowed to orbit The orbiting scroll does not rota...

Page 10: ...N MOTOR AND COMPRESSOR ACCESS Remove 7 screws REMOVE 7 SCREWS SECURING FAN GUARD REMOVE FAN GUARD FAN ASSEMBLY FAN GUARD WIRING DRIP LOOP Remove 4 nuts ALIGN FAN HUB FLUSH WITH MOTOR SHAFT D Reversing...

Page 11: ...Tighten finger tight then tighten an additional 1 6 turn FIGURE 12 LIQUID LINE SERVICE VALVE VALVE OPEN SCHRADER VALVE SERVICE PORT SERVICE PORT CAP INSERT HEX WRENCH HERE INLET TO INDOOR COIL OUTLET...

Page 12: ...is used on HP29 5 ton units These vapor line service valves function the same way differences are in construction Valves are not rebuildable If a valve has failed it must be replaced A ball valve is...

Page 13: ...16 7 9 5 8 15 9 HP29 024 L10 15 21 50 50 15 L15 31 20 20 6 HP29 311 L15 31 30 30 9 5 16 7 9 3 4 19 HP29 311 HP29 030 L15 31 40 40 12 5 16 7 9 3 4 19 L15 31 50 50 15 L10 15 41 20 20 6 HP29 410 L10 15...

Page 14: ...th vacuum gauge to center port of gauge manifold With both manifold service valves open start pump and evacuate indoor coil and refrigerant lines IMPORTANT A temperature vacuum gauge mercury vacuum U...

Page 15: ...Ambient Temperature HP29 261 HP29 311 HP29 461 APPROACH METHOD AMBIENT TEMPERATURE OF 60 _F 16 _C OR ABOVE 13 F 7 2 C 16 F 8 9 C 13 F 7 2 C HP29 211 10 F 5 6 C HP29 511 16 F 8 9 C HP29 651 18 F 10 C 1...

Page 16: ...183 72 Cooling TXV 85 29 200 76 210 74 214 72 215 75 205 74 210 70 214 73 g TXV Only 95 35 230 78 241 75 246 74 249 76 245 75 240 71 248 75 Only 105 41 263 81 275 78 282 45 285 76 280 76 280 72 285 7...

Page 17: ...uns Figure 19 shows how to make a transition from horizontal to vertical Finally figure 20 shows how to place the outdoor unit and line set REFRIGERANT LINE SETS HOW TO INSTALL VERTICAL RUNS new const...

Page 18: ...hang line set from joist or rafter use either metal strapping material or anchored heavy nylon wire ties Floor Joist or Roof Rafter Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid L...

Page 19: ...Page 19 VII WIRING DIAGRAMS AND SEQUENCE OF OPERATION HP29 SINGLE PHASE WITH RECIPROCATING COMPRESSOR HP29 1 2 UNITS 1 2 3 5 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19...

Page 20: ...Page 20 HP29 SINGLE PHASE WITH RECIPROCATING COMPRESSOR 1 2 3 5 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19...

Page 21: ...Page 21 HP29 SINGLE PHASE WITH RECIPROCATING COMPRESSOR 1 2 3 5 6 4 7 8 9 10 11 12 15 14 16 17 18 20 1 19 19...

Page 22: ...Page 22 HP29 SINGLE PHASE WITH SCROLL COMPRESSOR HP29 1 2 UNITS 1 2 3 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19 4...

Page 23: ...Page 23 HP29 SINGLE PHASE WITH SCROLL COMPRESSOR 1 2 3 6 4 7 8 9 10 11 12 15 14 16 17 18 19 20 1 19 19 4...

Page 24: ...Page 24 HP29 SINGLE PHASE WITH SCROLL COMPRESSOR 1 2 3 6 4 7 8 9 10 11 12 15 14 16 17 18 20 1 19 19 4...

Page 25: ...mpressor contactor K1 is de energized 8 K1 1 opens and compressor B1 and outdoor fan motor B4 are de energized and stop immediately 9 Terminal O is de energized when internal thermostat is out of cool...

Page 26: ...14 16 17 18 19 1 4 18 18 18 NOTE Scroll three phase compressors must be phased correctly Compressor noise may be significantly higher indicating phasing is incorrect Compressor operating backwards wil...

Page 27: ...Page 27 HP29 THREE PHASE WITH RECIPROCATING OR SCROLL COMPRESSOR 1 2 3 5 6 7 8 9 10 11 13 15 14 16 17 18 19 1 18...

Page 28: ...ed and stop immediately 8 Terminal O is de energized when internal thermostat wiring is out of cooling mode de energizing reversing valve L1 FIRST STAGE HEAT 9 Heating demand initiates at Y1 10 24VAC...

Reviews: