background image

Page 8

STRAINER

FILTER DRIER

WITH INTERNAL

CHECK VALVE

DISCHARGE

 MUFFLER

COMPRESSOR

VAPOR LINE

VALVE

REVERSING

VALVE

INDOOR

UNIT

LIQUID

LINE

VALVE

THERMOMETER

WELL

EXPANSION

VALVE

SUCTION

HIGH

PRESSURE

HP25 COOLING CYCLE

(Showing Gauge Manifold Connections)

FIGURE 7

NOTE-Use gauge ports on vapor line valve and liquid valve for evacuating refrigerant lines

and indoor coil. Use suction gauge port to measure suction pressure during charging.

EXPANSION

VALVE

CHECK

VALVE

CHARGE  COMPENSATOR

 5- If outdoor temperature is 60

F (15

C) or above,

place thermometer in well and read liquid line
temperature. Difference between ambient and liq
uid line temperatures should match values given
in table 4. Refrigerant must be added to lower ap
proach temperature. Remove refrigerant from sys
tem to increase approach temperature.

TABLE 4

Model

Liquid Temp. Minus

Ambient Temp. 

F (

C)

HP25-211

HP25-311

HP25-410

HP25-460

8  (4)

8 (4)

9 (5)

9 (5)

Approach Method-Expansion Valve Systems

HP25-261

8 (4)

HP25-510

HP25-650

5 (3)

5 (3)

 6- If ambient temperature is less than 60

F (15

C), air

flow might need to be restricted to achieve pressur
es in the 200-250 psig (1379-1724 kPa) range (See
figure 8). These higher pressures are necessary for
checking charge. Block equal sections of air intake
panels, moving obstructions sideways as shown
until liquid pressure is in the 200-250 psig
(1379-1724 kPa) range.

BLOCKING OUTDOOR COIL

FIGURE 8

OUTDOOR COIL SHOULD BE BLOCKED

ONE SIDE AT A TIME WITH CARDBOARD

OR PLASTIC SHEET UNTIL PROPER TEST

ING PRESSURES ARE REACHED.

CARDBOARD OR PLASTIC SHEET

 7- Read liquid line temperature. Read liquid line pres

sure from gauge and convert to condensing tem
perature using standard R-22 temperature/pres
sure conversion chart. The difference between the
liquid line temperature and the conversion temper
ature is the subcooling temperature (subcooling =
conversion temperature minus liquid tempera
ture). Subcooling should approximate values given
in table 5. Add refrigerant to increase subcooling
and remove refrigerant to reduce subcooling.

TABLE 5

Subcooling Method-Expansion Valve Systems

Model

Subcooling  

F (

C)

HP25-261/311/410

HP25-460

3 + 2 (2 + 1)

8 + 2 (4 + 1)

HP25-211

8 + 2 (4 + 1)

HP25-510
HP25-650

10 + 2 (6 + 1)
12 + 2 (7 + 1)

Summary of Contents for HP-511-513

Page 1: ...evied for non compliance INSTALLATION INSTRUCTIONS HP25 SERIES UNITS HEAT PUMP UNITS 503 302M 6 95 Supersedes 503 247M TABLE OF CONTENTS HP25 HEAT PUMP UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFOR...

Page 2: ...D E F G H J K L HP25 211 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 1 7 8 16 3 4 5 1 2 2 7 8 HP25 211 HP25 261 mm 708 657 759 311 570 367 562 48 425 140 73 HP25 311 in 30 7 8 32 1 8 34 1 16...

Page 3: ...OTE 48 1219mm clearance required on top of unit One side dimension may be 12 305mm 36 914mm 36 914mm 36 914mm 36 914mm Heat pump units operate under a wide range of weath er conditions therefore sever...

Page 4: ...is instruction see figure 6 and in indoor unit instructions Refer to figure 5 for thermostat designa tions Refer to unit rating plate for minimum circuit am pacity and maximum fuse size WARNING Unit m...

Page 5: ...1 1 8 in 28 6 mm FIELD FABRICATED L15 LINE SETS L15 41 20 ft 50 ft 6 1 m 15 2 m L15 65 30 ft 50 ft 9 1 m 15 2 m FIELD FABRICATED L15 26 20 ft 50 ft 6 1 m 15 2 m NOTE To obtain maximum efficiency remov...

Page 6: ...o produce substances that corrode copper piping and compressor parts 1 Connect manifold gauge set to the service valve ports as follows low pressure gauge to vapor line service valve high pressure gau...

Page 7: ...and suc tions pressures do not perform normally follow the steps below to correctly phase in the unit 1 Disconnect power to the unit 2 Reverse any two field power leads to the unit 3 Reapply power to...

Page 8: ...6 If ambient temperature is less than 60 F 15 C air flow might need to be restricted to achieve pressur es in the 200 250 psig 1379 1724 kPa range See figure 8 These higher pressures are necessary for...

Page 9: ...ngle pole single throw which is located on the liquid line The switch shuts off the compressor when discharge pressure rises above the factory set ting The switch is normally closed and is permanently...

Page 10: ...PS2 termi nals on the defrost board If using an additional pres sure switch remove jumper before connecting additional switch to control board If no additional switch is needed DO NOT REMOVE JUMPER U...

Page 11: ...power supplies At the beginning of each heating or cooling season the system should be cleaned as follows Heat Pump Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Outdo...

Page 12: ...o City City Serial No Date State State Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Ev...

Reviews: