background image

Page 6

LEAK TESTING

After the line set has been connected to the indoor and

outdoor units, the line set connections and indoor unit

must be checked for leaks.

WARNING

Never use oxygen to pressurize refrigeration or air

conditioning system. Oxygen will explode on con

tact with oil and could cause personal injury. When

using high pressure gas such as nitrogen or CO

2

 for

this purpose, be sure to use a regulator that can

control the pressure down to 1 or 2 psig (6.9 to 13.8

kPa).

Using an Electronic Leak Detector or Halide

 1- Connect a cylinder of nitrogen with a pressure reg

ulating valve to the center port of the manifold

gauge set.

 2- Connect the high pressure hose of the manifold

gauge set to the service port of the vapor valve.

(Normally, the high pressure hose is connected to

the liquid line port, however, connecting it to the

vapor port better protects the manifold gauge set

from high pressure damage.)

 3- With both manifold valves closed, open the valve

on the R22 bottle (vapor only).

 4- Open the high pressure side of the manifold to al

low R22 into the line set and indoor unit. Weigh in a

trace amount of R22.

 [A trace amount is a maxi

mum of  2 ounces (57g) refrigerant or 3 pounds (31

kPa) pressure]. 

Close the valve on the R22 bottle

and the valve on the high pressure side of the man

ifold gauge set. Disconnect R22 bottle.

 5- Adjust nitrogen pressure to 150 psig (1034 kPa). Open

the valve on the high side of the manifold gauge set

which will pressurize line set and indoor unit.

 6- After a short period of time, open a refrigerant port

to make sure the refrigerant added is adequate to

be detected. (Amounts of refrigerant will vary with

line lengths.) Check all joints for leaks. Purge nitro

gen and R22 mixture. Correct any leaks and re

check.

EVACUATING

Evacuating the system of non-condensables is critical

for proper operation of the unit. Non-condensables are

defined as any gas that will not condense under temper

atures and pressures present during operation of an air

conditioning system. Non-condensables and water va

por combine with refrigerant to produce substances

that corrode copper piping and compressor parts.

 1- Connect manifold gauge set to the service valve ports

as follows: low pressure gauge to vapor  line service
valve; high pressure gauge to liquid line service valve.

 2- Connect the vacuum pump (with vacuum gauge)

to the center port of the manifold gauge set.

 3- Open both manifold valves and start vacuum

pump.

 4- Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23mm of mercury or approximately 1

inch of mercury. During the early stages of evacua

tion, it is desirable to close the manifold gauge

valve at least once to determine if there is a rapid

rise in 

absolute pressure

. A rapid rise in pressure

indicates a relatively large leak. If this occurs, the

leak testing procedure must be repeated.

NOTE - The term 

absolute pressure

 means the to

tal actual pressure within a given volume or sys
tem, above the absolute zero of pressure. Absolute
pressure in a vacuum is equal to atmospheric pres
sure minus vacuum pressure.

 5- When the absolute pressure reaches 23mm of mer

cury, close the manifold gauge valves, turn off the

vacuum pump and disconnect the manifold gauge

center port hose from vacuum pump. Attach the

manifold center port hose to a nitrogen cylinder

with pressure regulator set to 150 psig (1034 kPa)

and purge the hose. Open the manifold gauge

valves to break the vacuum in the line set and in

door unit. Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.

Avoid deep vacuum operation. Do not use com

pressors to evacuate a system.

Extremely low vacuums can cause internal arcing

and compressor failure.

Damage caused by deep vacuum operation will

void warranty.

 6- Shut off the nitrogen cylinder and remove the man

ifold gauge hose from the cylinder. Open the man

ifold gauge valves to release the nitrogen from the

line set and indoor unit.

 7- Reconnect the manifold gauge to the vacuum

pump, turn the pump on and continue to evacuate

the line set and indoor unit until the absolute pres

sure does not rise above .5mm of mercury within a

20 minute period after shutting off the vacuum

pump and closing the manifold gauge valves.

 8- Depending on the equipment used to determine

the vacuum level, absolute pressure of .5mm of

mercury is equal to 500 microns.

Summary of Contents for HP-511-513

Page 1: ...evied for non compliance INSTALLATION INSTRUCTIONS HP25 SERIES UNITS HEAT PUMP UNITS 503 302M 6 95 Supersedes 503 247M TABLE OF CONTENTS HP25 HEAT PUMP UNIT 1 SHIPPING AND PACKING LIST 1 GENERAL INFOR...

Page 2: ...D E F G H J K L HP25 211 in 27 7 8 25 7 8 29 7 8 12 1 4 22 7 16 14 7 16 22 1 8 1 7 8 16 3 4 5 1 2 2 7 8 HP25 211 HP25 261 mm 708 657 759 311 570 367 562 48 425 140 73 HP25 311 in 30 7 8 32 1 8 34 1 16...

Page 3: ...OTE 48 1219mm clearance required on top of unit One side dimension may be 12 305mm 36 914mm 36 914mm 36 914mm 36 914mm Heat pump units operate under a wide range of weath er conditions therefore sever...

Page 4: ...is instruction see figure 6 and in indoor unit instructions Refer to figure 5 for thermostat designa tions Refer to unit rating plate for minimum circuit am pacity and maximum fuse size WARNING Unit m...

Page 5: ...1 1 8 in 28 6 mm FIELD FABRICATED L15 LINE SETS L15 41 20 ft 50 ft 6 1 m 15 2 m L15 65 30 ft 50 ft 9 1 m 15 2 m FIELD FABRICATED L15 26 20 ft 50 ft 6 1 m 15 2 m NOTE To obtain maximum efficiency remov...

Page 6: ...o produce substances that corrode copper piping and compressor parts 1 Connect manifold gauge set to the service valve ports as follows low pressure gauge to vapor line service valve high pressure gau...

Page 7: ...and suc tions pressures do not perform normally follow the steps below to correctly phase in the unit 1 Disconnect power to the unit 2 Reverse any two field power leads to the unit 3 Reapply power to...

Page 8: ...6 If ambient temperature is less than 60 F 15 C air flow might need to be restricted to achieve pressur es in the 200 250 psig 1379 1724 kPa range See figure 8 These higher pressures are necessary for...

Page 9: ...ngle pole single throw which is located on the liquid line The switch shuts off the compressor when discharge pressure rises above the factory set ting The switch is normally closed and is permanently...

Page 10: ...PS2 termi nals on the defrost board If using an additional pres sure switch remove jumper before connecting additional switch to control board If no additional switch is needed DO NOT REMOVE JUMPER U...

Page 11: ...power supplies At the beginning of each heating or cooling season the system should be cleaned as follows Heat Pump Unit 1 Clean and inspect outdoor coil Coil may be flushed with a water hose 2 Outdo...

Page 12: ...o City City Serial No Date State State Service Technician Amps Supply Outdoor Fan Compressor Indoor Filter Clean Indoor Blower RPM Electrical Connections Tight Supply Voltage Unit Off S P Drop Over Ev...

Reviews: