Lennox HARMONY II Installation Instructions Manual Download Page 25

Page 25

HARMONY III

T

 SERIES

2. Establish a compressor heating demand and allow

system to begin operating (see heat pump heating
checkout section for details).

3. Allow system to operate several minutes so refrigerant

pressures can balance.

4. Momentarily block the return air opening and observe

the high pressure gauge. When hot gas line pressure
reaches approximately 375 psig for R−22 and 550 for
R−410A, an error code will be set in the zone control
system, DIAGS 1 and 4 will turn on, and outdoor unit
will stage down and turn off if the switch does not close
within 90 seconds. Afterwards, backup heat will be
used to satisfy the demand.

5. Remove the restriction. When hot gas pressure drops

below 275 psig (for R−22) or 425 psig (for R−410A), all
DIAGs should turn off.

Blower Speed Checkout

The indoor blower speed should vary as zone demand
changes. The fan speed LED varies in brightness as the
blower varies in speed. The brighter the LED, the more
CFM being delivered. Blower speed can also be viewed by
attaching an electronic voltmeter between DS and any C
terminal on the zone control board. While not a precise
measurement, the voltmeter fluctuation indicates that the
blower speed is changing.

1. Connect electronic voltmeter between DS and any C

terminal on the zone control board. Leave all field wir-
ing in place.

2. Select DC volts scale.
3. Start zone heating or cooling checkout procedure.
4. Observe voltages:

D

22 volts DC = high speed (varies depending on in-
put voltage at primary transformer).

D

11 volts DC (approx.) = medium speed 50% into
adjustment band of blower.

D

0 volts DC = low speed or off.

All speeds in between are a percentage of 22VDC.

Troubleshooting

Zone Control Board Diagnostics (Diagnostic
LEDs)

When the zone control system finds a problem (error con-
dition), it will turn on one or more of the diagnostic LEDs on
the board.

Decoding the Light Patterns

The LEDs can be lit in several different patterns, each pat-
tern corresponding to a different error condition. Table 10
shows each possible display pattern, a description of the
error, and ways to correct the error.

Some of the errors found in table will cause a fail−safe or
shutdown condition. The system will shutdown after the er-
ror is present for about five seconds. During a shutdown
condition, all dampers will open, there is no demand to the
condensing unit or furnace. Normal operation will resume
five seconds after the error has been corrected.

The blower may run during a fail−safe condition after a
heating demand. This is due to the operation of the blower
control board inside the furnace.

If a shutdown condition occurs while there is a call for cool-
ing, a five−minute timer is initiated before cooling can be
called for again. The timer begins at the time of the shut-
down condition and does not affect the response to, nor is
affected by a heating demand.

Troubleshooting diagrams (figures 23, 24, 25) identify
common areas to check when troubleshooting. The dia-
grams provide checkpoints related to connectivity and op-
eration of system equipment. Use these diagrams, along
with installation information contained throughout this
manual, to identify and correct problems.

Table 10

Diagnostics Codes

Code

#

(0−off;1−on)

Diag LED

1234

Fault
Indicated

Remedy

Fail-safe

(System

Shut Down)

0

0000

Normal
operation

No remedial action required.

1

1000

Insufficient
cooling

Occurs when unable to maintain desired temperature in cooling. Dis-
plays code and no further action is taken.

No

2

0100

Defrost time 
> 20 minutes

The defrost board should never allow a defrost for greater than 20 min-
utes. If this error occurs, check the outdoor unit to see if it is stuck in
defrost mode. The zone control system will use the backup heat during
this error and not the heat pump.

No

3

1100

Unsteady
thermostat
input

This error occurs when a thermostat changes state repeatedly and rap-
idly, indicating that the thermostat is making intermittent contact and
needs attention. The offending thermostat will be ignored for 4 minutes
after the zone control system detects the problem. After 4 minutes if the
signal from the thermostat is steady again, it will be recognized by the
zone control system. Disconnect thermostats until error goes away. This
will identify the source of bad input. If error remains after all inputs have
been disconnected, replace zone control board.

No

table continued on next page

Summary of Contents for HARMONY II

Page 1: ...cs Codes 25 Troubleshooting Diagrams 27 PIAB Calculation Worksheet 30 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Shipping Packing List Items shipped with the Harmony IIIt Zone Control System inclu...

Page 2: ...ke comfort settings for each zone A programmable thermostat should be used to provide a specialized heating and cooling sequence While the sys tem is in the zone mode a programmable thermostat con tro...

Page 3: ...nical or electro mechanical thermostats will not work with the Harmony IIIt zone control system Recommended thermostats include S SignatureStatt Thermostat 1 heat 1 cool 81M26 IMPORTANT When using thi...

Page 4: ...at Pump IMPORTANT LENNOX recommends ONLY Harmony II and Harmony IIIt Zone Control Systems for use with Variable Speed Blower Motor VSM technology 1 Lennox Blower Coil Unit with VSM Use ONLY blower coi...

Page 5: ...appliances and sunny windows near concealed pipes and chimneys or in unconditioned spaces such as closets or exterior walls Dampers Motorized dampers in the supply duct system regulate air to the zon...

Page 6: ...RTANT Be sure to cut jumper W914 if not cut the zone con trol board DS fuse will blow WARNING Electrical Shock Hazard Disconnect power from unit and wait at least five minutes to allow capacitors to d...

Page 7: ...s remove any factory installed jumper between terminal R and W1 W2 or W3 D In all cases cut and tape wire 7 see figure 8 on the VSM harness that runs from the BDC3 board to the motor 9 Figure 8 4 5 1...

Page 8: ...on Chart Model Equivalent Positions Harmony II 25 35 45 55 65 75 85 95 Harmony IIIt 0 10 30 40 50 70 80 90 When jumpers are set to 0 this corresponds to the mini mum air volume available according to...

Page 9: ...is re duced during heating mode Determining Actual Air Delivered By Blower The actual CFM delivered to each zone will be determined by the zone control system settings blower motor control board setti...

Page 10: ...AB 8 x CFM Max 2220 Min 720 x 1500 Min CFM 720 TOTAL 1920 CFM 4 Determine total air delivered during a continuous blower call Calculate these totals using the formu las and example Table 8 which uses...

Page 11: ...hp 1hp 2 2hp 1hp 2 3 3 DOESN T MATTER Dual fuel heating 1 stage AC heat pump SYSTEM E HEAT Configuration Stages HP GAS df gas df 2cool 1cool 1 2cool 1cool 1 2hp 1hp 2 2hp 1hp 2 3 3 Figure 14 NOTE Vari...

Page 12: ...g close to AC house wiring If this cannot be avoided limit close parallel of power and control wiring to a few feet Dampers and Damper Transformer Wiring Connect dampers to the zone control board as s...

Page 13: ...NOTE If not already done remove the wire to K20 blower relay terminal 7 on BDC3 board and tape it off Also be sure the factory installed jumper between terminal R and W1 W2 and W3 has been removed He...

Page 14: ...11 120 VAC 24 VAC C R IMPORTANT Connectivity is NOT COMPLETE until all electrical adjustments jumpers and wiring changes have been made See Electrical Adjustments for SureLight Board page 6 and for BD...

Page 15: ...UNDED METAL OBJECT BEFORE TOUCHING THE CIRCUIT BOARD LENNOX Harmony IIIt V3 0 2004 System Configuration E Heat jumper settings page 11 piab jumper settings page 8 air reduction jumper settings page 9...

Page 16: ...quipment DISCHARGE AIR SENSOR 88K38 included IMPORTANT Connect thermostat gauge wire to SureLight board C terminal HEAT PUMP VARIABLE SPEED FURNACE Figure 21 NOTE Do not wire Y wire s from the Harmony...

Page 17: ...ing the blower may continue after the end of a demand until the heater is cooled sufficiently Cooling Operation When the Harmony IIIt zone control system receives a thermostat cooling call the followi...

Page 18: ...p heat or in a dual mode system the heat demand is satisfied by the gas furnace Operation Troubleshooting Indicators Zone Control Board LEDs The zone control system operation is indicated by light emi...

Page 19: ...ng proper operation Perform the gas and heat pump heating checks on pages 20 through 24 Table 9 Time Delays Delay Time Function Blower Off Delay gas heat only 3 1 2 min Gas Furnace only Dumps air into...

Page 20: ...e damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Prerequisites S All zone thermostats set to Heat OUTPUT STATUS LEDs DAMPER 2 3 4 OFF W1 on W RED on hEAT...

Page 21: ...LEDs DAMPER 2 3 4 on DAMPER 1 Off W RED ON event Sequence 1 Y1 ON 2 Y2 IF EQUIPPED ON IF NO SIGNIFICANT WARMING AFTER 4 MIN 3 W1 ON IF NO SIGNIFICANT WARMING AFTER 4 MIN THEN W2 THEN W3 PRESSURE SWITC...

Page 22: ...ing 3 1 2 minute purge Other zones damper LEDs are on during the 3 1 2 minute purge dampers closed After 3 1 2 minute delay all dampers LEDs go off dampers open Heat Pump Heating Checkout Central Cont...

Page 23: ...individual zone damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Dual Fuel Option and BPS Prerequisites S All zone thermostats set to Heat S Balance Point...

Page 24: ...ill produce a faulty reading At 77 F the resistance of the sensor will be 10K ohm at lower probe temperatures ex pect higher resistance at warmer probe temperatures ex pect lower resistance After read...

Page 25: ...or Some of the errors found in table will cause a fail safe or shutdown condition The system will shutdown after the er ror is present for about five seconds During a shutdown condition all dampers wi...

Page 26: ...ill cycle from high to off in cooling The compressor will cycle from high to off in heating The furnace will operate normally in gas heat Replace discharge probe If error persists replace zone control...

Page 27: ...spond to demand 0 volts AC open 24 volts AC closed Dampers should drive closed when 24 volts is jumpered to damper motor Is wiring correct in good condition Figure 23 Line Voltage to transformer 24VAC...

Page 28: ...n relays may need to be used 24VAC supplied to each thermostat terminal R from zone control system Check each thermostat for output signal when calling Heating output W1 Cooling output Y1 Do dampers r...

Page 29: ...charge air plenum as de scribed on Page 5 Is it wired cor rectly Does outdoor unit respond to demand Is it operating properly Test Defrost Does outdoor unit initiate and terminate defrost correctly W1...

Page 30: ...AB 0 2 x 100 20 Zone 1 CFM Required Minimum Maximum Minimum ZONE 1 PIAB x 100 b b ZONE 1 PIAB x 100 b ZONE 1 PIAB x 100 Zone 2 CFM Required Minimum Maximum Minimum ZONE 2 PIAB x 100 b b ZONE 2 PIAB x...

Reviews: