Gas Heating Checkout − Central Control

Prerequisites:

S

Central mode switch on

S

Red LED on the central mode fan switch on

OUTPUT STATUS LEDs

W1 on

(W) RED on

DAMPER 2,3,4 OFF

hEATING on

fan on

central mode On

1. Set zone 1 thermostat for a heat demand; check:

D

Zone 1 thermostat W LED on (heating demand).

D

Output Heat W1 LED on (furnace on).

D

Heating LED on.

D

All damper LEDs off (damper open).

2. The furnace will begin its ignition sequence after Zone

1 has demanded heat. The zone control system will
start the furnace blower on low speed (0 PIAB air) 45
seconds after the combustion cycle has begun.

3. When warm air is sensed by the discharge air sensor,

the fan LED will light and the blower will slowly in-
crease to speed. The blower will operate at a speed
equivalent to the PIAB calculated for all zones calling,
taking into account the heating air reduction jumper
position. It may take the blower 60 to 90 seconds to
reach this speed.

4. Remove the heat demand from zone 1 (no heat input

or output and no blower demand). Upon removal of the
demand from zone 1, check:

D

Zone 1 thermostat W LED off (no heat demand).

D

Output Heat W1 LED off.

D

Fan LED off.

D

Heating LED off.

After 3−1/2 minute purge time, furnace blower turns off.

Heat Pump Heating Checkout − Single Zone

Prerequisites:

S

Zone 1 thermostat set to Heat

OUTPUT STATUS LEDs

DAMPER 2,3,4 on

DAMPER 1 Off

(W) RED ON

event Sequence:

1− Y1 ON

2− Y2 (IF EQUIPPED) ON

IF NO SIGNIFICANT
WARMING AFTER 4 MIN.

3− W1 ON IF NO

SIGNIFICANT WARMING
AFTER 4 MIN; THEN W2;
THEN W3

PRESSURE
SWITCH LED ON

hEATING on

fan on

ELECTRIC hEATING on (W/EVENT 3)

1. Set zone 1 thermostat for a heat demand; check:

D

Zone 1 thermostat W LED on (heating demand).

D

Damper LED 1 off (damper open).

D

Damper LEDs 2, 3, and 4 on (dampers closed).

D

Output Heat Y1 LED on (compressor on).

D

Heating LED on.

D

Fan LED on.

D

Pressure Switch LED on.

The compressor in the outdoor unit begins operating in
the heating mode. At approximately the same time,
the indoor blower starts, operating at a speed accord-
ing to the setting of the PIAB jumper for zone 1. It may
take the blower 60 to 90 seconds to reach this speed.

2.

If Single-Stage Heat Pump

 − 

Skip to step 3

. The dis-

charge air sensor continually samples air tempera-
ture. If, after 4 minutes, air temperature is not warming
significantly, the high speed compressor energizes.

D

Output Heat Y2 LED on (high speed compressor).

3. The discharge air sensor continually samples air tem-

perature. If, after (another) 4 minutes, air is not warm-
ing significantly, auxiliary heat sequence begins:

D

Electric Heating (E−Heating) LED on.

D

Output Heat W1 on, followed by (if available, and if
necessary) W2, and then W3.

4. Remove heat demand from zone 1.

D

All LEDs off, except:

D

Damper LEDs 2, 3, 4 on.

To check the amount of air being delivered to each
zone and to confirm that each individual zone damper
functions properly, repeat these steps for zones 2 − 4.

Summary of Contents for HARMONY II

Page 1: ...cs Codes 25 Troubleshooting Diagrams 27 PIAB Calculation Worksheet 30 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE Shipping Packing List Items shipped with the Harmony IIIt Zone Control System inclu...

Page 2: ...ke comfort settings for each zone A programmable thermostat should be used to provide a specialized heating and cooling sequence While the sys tem is in the zone mode a programmable thermostat con tro...

Page 3: ...nical or electro mechanical thermostats will not work with the Harmony IIIt zone control system Recommended thermostats include S SignatureStatt Thermostat 1 heat 1 cool 81M26 IMPORTANT When using thi...

Page 4: ...at Pump IMPORTANT LENNOX recommends ONLY Harmony II and Harmony IIIt Zone Control Systems for use with Variable Speed Blower Motor VSM technology 1 Lennox Blower Coil Unit with VSM Use ONLY blower coi...

Page 5: ...appliances and sunny windows near concealed pipes and chimneys or in unconditioned spaces such as closets or exterior walls Dampers Motorized dampers in the supply duct system regulate air to the zon...

Page 6: ...RTANT Be sure to cut jumper W914 if not cut the zone con trol board DS fuse will blow WARNING Electrical Shock Hazard Disconnect power from unit and wait at least five minutes to allow capacitors to d...

Page 7: ...s remove any factory installed jumper between terminal R and W1 W2 or W3 D In all cases cut and tape wire 7 see figure 8 on the VSM harness that runs from the BDC3 board to the motor 9 Figure 8 4 5 1...

Page 8: ...on Chart Model Equivalent Positions Harmony II 25 35 45 55 65 75 85 95 Harmony IIIt 0 10 30 40 50 70 80 90 When jumpers are set to 0 this corresponds to the mini mum air volume available according to...

Page 9: ...is re duced during heating mode Determining Actual Air Delivered By Blower The actual CFM delivered to each zone will be determined by the zone control system settings blower motor control board setti...

Page 10: ...AB 8 x CFM Max 2220 Min 720 x 1500 Min CFM 720 TOTAL 1920 CFM 4 Determine total air delivered during a continuous blower call Calculate these totals using the formu las and example Table 8 which uses...

Page 11: ...hp 1hp 2 2hp 1hp 2 3 3 DOESN T MATTER Dual fuel heating 1 stage AC heat pump SYSTEM E HEAT Configuration Stages HP GAS df gas df 2cool 1cool 1 2cool 1cool 1 2hp 1hp 2 2hp 1hp 2 3 3 Figure 14 NOTE Vari...

Page 12: ...g close to AC house wiring If this cannot be avoided limit close parallel of power and control wiring to a few feet Dampers and Damper Transformer Wiring Connect dampers to the zone control board as s...

Page 13: ...NOTE If not already done remove the wire to K20 blower relay terminal 7 on BDC3 board and tape it off Also be sure the factory installed jumper between terminal R and W1 W2 and W3 has been removed He...

Page 14: ...11 120 VAC 24 VAC C R IMPORTANT Connectivity is NOT COMPLETE until all electrical adjustments jumpers and wiring changes have been made See Electrical Adjustments for SureLight Board page 6 and for BD...

Page 15: ...UNDED METAL OBJECT BEFORE TOUCHING THE CIRCUIT BOARD LENNOX Harmony IIIt V3 0 2004 System Configuration E Heat jumper settings page 11 piab jumper settings page 8 air reduction jumper settings page 9...

Page 16: ...quipment DISCHARGE AIR SENSOR 88K38 included IMPORTANT Connect thermostat gauge wire to SureLight board C terminal HEAT PUMP VARIABLE SPEED FURNACE Figure 21 NOTE Do not wire Y wire s from the Harmony...

Page 17: ...ing the blower may continue after the end of a demand until the heater is cooled sufficiently Cooling Operation When the Harmony IIIt zone control system receives a thermostat cooling call the followi...

Page 18: ...p heat or in a dual mode system the heat demand is satisfied by the gas furnace Operation Troubleshooting Indicators Zone Control Board LEDs The zone control system operation is indicated by light emi...

Page 19: ...ng proper operation Perform the gas and heat pump heating checks on pages 20 through 24 Table 9 Time Delays Delay Time Function Blower Off Delay gas heat only 3 1 2 min Gas Furnace only Dumps air into...

Page 20: ...e damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Prerequisites S All zone thermostats set to Heat OUTPUT STATUS LEDs DAMPER 2 3 4 OFF W1 on W RED on hEAT...

Page 21: ...LEDs DAMPER 2 3 4 on DAMPER 1 Off W RED ON event Sequence 1 Y1 ON 2 Y2 IF EQUIPPED ON IF NO SIGNIFICANT WARMING AFTER 4 MIN 3 W1 ON IF NO SIGNIFICANT WARMING AFTER 4 MIN THEN W2 THEN W3 PRESSURE SWITC...

Page 22: ...ing 3 1 2 minute purge Other zones damper LEDs are on during the 3 1 2 minute purge dampers closed After 3 1 2 minute delay all dampers LEDs go off dampers open Heat Pump Heating Checkout Central Cont...

Page 23: ...individual zone damper functions properly repeat these steps for zones 2 4 Gas Heating Checkout Multiple Zone Dual Fuel Option and BPS Prerequisites S All zone thermostats set to Heat S Balance Point...

Page 24: ...ill produce a faulty reading At 77 F the resistance of the sensor will be 10K ohm at lower probe temperatures ex pect higher resistance at warmer probe temperatures ex pect lower resistance After read...

Page 25: ...or Some of the errors found in table will cause a fail safe or shutdown condition The system will shutdown after the er ror is present for about five seconds During a shutdown condition all dampers wi...

Page 26: ...ill cycle from high to off in cooling The compressor will cycle from high to off in heating The furnace will operate normally in gas heat Replace discharge probe If error persists replace zone control...

Page 27: ...spond to demand 0 volts AC open 24 volts AC closed Dampers should drive closed when 24 volts is jumpered to damper motor Is wiring correct in good condition Figure 23 Line Voltage to transformer 24VAC...

Page 28: ...n relays may need to be used 24VAC supplied to each thermostat terminal R from zone control system Check each thermostat for output signal when calling Heating output W1 Cooling output Y1 Do dampers r...

Page 29: ...charge air plenum as de scribed on Page 5 Is it wired cor rectly Does outdoor unit respond to demand Is it operating properly Test Defrost Does outdoor unit initiate and terminate defrost correctly W1...

Page 30: ...AB 0 2 x 100 20 Zone 1 CFM Required Minimum Maximum Minimum ZONE 1 PIAB x 100 b b ZONE 1 PIAB x 100 b ZONE 1 PIAB x 100 Zone 2 CFM Required Minimum Maximum Minimum ZONE 2 PIAB x 100 b b ZONE 2 PIAB x...

Reviews: