Page 28
SureLight Troubleshooting: Heating Sequence of Operation Contd.
NORMAL HEATING MODE
ABNORMAL HEATING MODE
FLAME RECTIFICATION CURRENT CHECK
CAN FLAME BE PROVEN WITHIN 4
SECONDS AFTER GAS VALVE OPENS?
(
0.15 microamps)
NO
FLAME PRESENT?
INDOOR BLOWER ON DELAY BEGINS. AFTER 45
SECOND DELAY, ACB HEAT SPEED TERMINAL IS
ENERGIZED. ACC. TERMINAL IS ENERGIZED.
PRIMARY AND SECONDARY LIMIT
SWITCHES CLOSED?
COMBUSTION AIR PRESSURE
SWITCH CLOSED?
LOW FLAME SIGNAL
(Does not affect operation of control)
LED #1 -- SLOW FLASH
LED #2 -- FAST FLASH
GAS VALVE DE-ENERGIZED.
COMBUSTION AIR BLOWER DE-ENERGIZED.
INDOOR BLOWER ON UNTIL SWITCH CLOSES.
LED #1 -- SLOW FLASH. LED #2 -- ON.
IS LIMIT SWITCH CLOSED?
GAS VALVE DE-ENERGIZED.
COMBUSTION AIR BLOWER ON.
INDOOR BLOWER OFF WITH DELAY
LED #1 -- OFF. LED #2 -- SLOW FLASH.
HAS CAB SWITCH CLOSED IN 2.5 MINUTES?
15SECOND COMBUSTION AIR BLOWER PREPURGE
INITIATED BY CLOSED PRESSURE SWITCH.
YES
IGNITOR WARMUP -- 20 SECONDS.
YES
4SECOND TRIAL FOR IGNITION.
GAS VALVE OPENS. IGNITOR ENERGIZED FOR
1 SECOND AFTER VALVE OPENS.
NO FLAME SENSED DURING THIS PERIOD.
YES
FLAME STABILIZATION PERIOD.
GAS VALVE OFF. COMBUSTION AIR BLOWER ON.
INDOOR BLOWER OFF.
HAS CONTROL FAILED TO SENSE FLAME FOR
FIVE CONSECUTIVE TRIES DURING A SINGLE
HEAT DEMAND?
NO
WATCHGUARD MODE. GAS VALVE OFF.
COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH DELAY
LEDs SIGNAL WATCHGUARD FAILURE CODE.
IS 60MINUTE RESET PERIOD COMPLETE?
YES
YES
NO
4 SECONDS
YES
HAS CONTROL RESET IGNITION
SEQUENCE FOUR ARIAL?
YES
NO
FLAME SIGNAL ABOVE 0.7 MICROAMPS?
NO
YES
YES
HAS PRIMARY LIMIT OPENED
FIVE ARIAL DURING ONE
UNSATISFIED HEATING DEMAND?
NO
YES
NO
YES
ROLLOUT SWITCH CLOSED?
GAS VALVE OFF. COMBUSTION AIR BLOWER OFF.
INDOOR BLOWER OFF WITH DELAY.
LED #1 -- ON. LED #2 -- SLOW FLASH.
SEQUENCE HOLDS UNTIL ROLLOUT SWITCH CLOSES.
NO
YES
YES
NO
THERMOSTAT DEMAND SATISFIED.
LED #1 & #2 SIMULTANEOUS SLOW FLASHES.
COMB. AIR BLOWER CONTINUES 5SECOND
POST PURGE AFTER T'STAT DEMAND IS SATISFIED.
HTG ACC. TERM. IS DE-ENERGIZED. INDOOR AIR
BLOWER COMPLETES SELECTED OFF" DELAY BE
FORE SHUTTING OFF. ACC. TERM. DE-ENERGIZED.
YES
YES
YES
NO
5MINUTE PRESSURE SWITCH
WATCHGUARD MODE.
YES