background image

Page 16

Homeowner Information

CAUTION

Before attempting to perform any service or mainte­
nance, turn the electrical power to unit OFF at dis­
connect switch.

In order to ensure peak performance, your system must be
properly maintained. Clogged filters and blocked airflow
prevent your unit from operating at its most efficient level.
The system should be inspected and serviced before each
cooling and heating season by a licensed professional
HVAC service technician (or equivalent).

Heat Pump Operation

Your new Lennox heat pump has several characteristics
that you should be aware of:

S

Heat pumps satisfy heating demand by delivering
large amounts of 

warm

 air into the living space. This

is quite different from gas‐ or oil‐fired furnaces or an
electric furnace which deliver lower volumes of consid­
erably 

hotter

 air to heat the space.

S

Do not be alarmed if you notice frost on the outdoor coil
in the winter months. Frost develops on the outdoor
coil during the heating cycle when temperatures are
below 45

°

F (7

°

C). The heat pump control activates a

defrost cycle lasting 5 to 15 minutes at preset intervals
to clear the outdoor coil of the frost.

S

During the defrost cycle, you may notice steam rising
from the outdoor unit. This is a normal occurrence.
The thermostat may engage auxiliary heat during the
defrost cycle to satisfy a heating demand; however,
the unit will return to normal operation at the conclu­
sion of the defrost cycle.

Homeowner Maintenance

The following maintenance may be performed by the
homeowner.

S

Contact a licensed professional HVAC technician to
schedule inspection and maintenance appointments for
your equipment before each heating and cooling sea­
son.

S

Check the indoor unit filter each month and replace the
filter, if necessary.
Have your Lennox dealer show you where your indoor
unit filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind a
return air grille in the wall or ceiling. Check the filter
monthly and clean or replace it as needed.
Disposable filters should be replaced with a filter of the
same type and size.

S

Check the indoor unit drain line for obstructions monthly
during the cooling season. 
The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show you
the location of the drain line and how to check for ob­

structions. (This would also apply to an auxiliary drain,
if installed.)

S

Check the area around the outdoor unit monthly and re­
move any obstructions that may restrict airflow to the
outdoor unit. This would include grass clippings, leaves,
or papers that may have settled around the unit.

S

Trim shrubbery away from the unit and periodically
check for debris which collects around the unit.

S

During the winter months, keep the snow level below the
louvered panels.

NOTE

 

-

 The filter and all access panels must be in place

any time the unit is in operation. If you are unsure about the
filter required for your system, call your Lennox dealer for
assistance.

IMPORTANT !

Sprinklers and soaker hoses should not be installed
where they could cause prolonged exposure to the
outdoor unit by treated water. Prolonged exposure
of the unit to treated water (i.e., sprinkler systems,
soakers, waste water, etc.) will corrode the surface
of steel and aluminum parts, diminish performance
and affect longevity of the unit.

Thermostat Operation

See the iComfort

®

 thermostat homeowner manual for in­

structions on how to operate your thermostat.

Preservice Check

If your system fails to operate, check the following before
calling for service:

S

Verify room thermostat settings are correct.

S

Verify that all electrical disconnect switches are ON.

S

Check for any blown fuses or tripped circuit breakers.

S

Verify unit access panels are in place.

S

Verify air filter is clean.

S

If service is needed, locate and write down the unit
model number and have it handy before calling.

Extended Power Outage

The heat pump is equipped with a compressor crankcase
heater which protects the compressor during cold weather
operation.
If power to your unit has been interrupted for several hours
or more, set the room thermostat selector to the EMER­
GENCY HEAT setting to obtain temporary heat without the
risk of serious damage to the heat pump.

In EMERGENCY HEAT mode, all heating demand is satis­
fied by auxiliary heat; heat pump operation is locked out.
After a six‐hour compressor crankcase warm‐up period,
the thermostat can be switched to the HEAT setting and
normal heat pump operation may resume.

Professional Maintenance

Your heat pump system should be inspected and main­
tained yearly (before the start of the heating and cooling
seasons) by a licensed professional HVAC technician. You
can expect the technician to check the following items.

These checks may only be conducted by a licensed
professional HVAC technician.

Summary of Contents for Elite XP20-024-230

Page 1: ...formation consult the Installa tion and Service Procedures manual available as Corp 1408 L10 on DaveNet or through the Technical Support department at 800 453 6669 WARNING Improper installation adjust...

Page 2: ...ructure observe the following While installing or servicing this unit carefully stow all removed panels so that the panels will not cause injury to personnel objects or nearby structures Also take car...

Page 3: ...NCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL FIGURE 3 LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SLAB MOUNTING USIN...

Page 4: ...n lines Oxygen when ex posed to a spark or open flame can cause fire and or an explosion that could result in property damage personal injury or death IMPORTANT Some scroll compressors have an interna...

Page 5: ...Sizes for Horizontal Runs Required Vapor Riser Size 024 180 150 60 60 7 8 5 8 036 180 150 60 60 7 8 3 4 048 180 150 60 60 7 8 7 8 060 180 150 60 60 7 8 7 8 Table 3 Liquid Line Diameter Selection Table...

Page 6: ...id line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET...

Page 7: ...ur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERV...

Page 8: ...water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing w...

Page 9: ...S NUT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring wi...

Page 10: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 11: ...um pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A pos...

Page 12: ...ge as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to pro...

Page 13: ...s PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMPER PLA...

Page 14: ...oise see below Use a wire nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as show...

Page 15: ...cles Charging The XP20 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge should be checked and adjusted using the tables provided on...

Page 16: ...ealer show you the location of the drain line and how to check for ob structions This would also apply to an auxiliary drain if installed S Check the area around the outdoor unit monthly and re move a...

Page 17: ...st debris obstructions leaks or cracks Pour water in pans to confirm proper drain age from the pan through to the outlet of the pipe Clean or replace as necessary E Inspect and clean evaporator indoor...

Page 18: ...G MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Ai...

Reviews: