background image

Page 6

STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device

SENSING

LINE

TEFLON

®

 RING

FIXED ORIFICE

BRASS NUT

LIQUID LINE ASSEMBLY

(INCLUDES STRAINER)

LIQUID LINE ORIFICE HOUSING

DISTRIBUTOR TUBES

DISTRIBUTOR

ASSEMBLY

REMOVE AND DISCARD

WHITE TEFLON

®

 SEAL

(IF PRESENT)

 F.

On fully cased coils, remove the coil access and plumbing panels.

 G.

Remove any shipping clamps from the liquid line and distributor as­
sembly.

 H.

Using two wrenches, disconnect liquid line from liquid line orifice hous­
ing. Take care not to twist or damage distributor tubes during this pro­
cess.

 I.

Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon

®

 washer as illustrated above.

 J.

Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing.

TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE 
(UNCASED COIL SHOWN)

TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)

TWO-PIECE PATCH PLATE

(UNCASED COIL ONLY)

VAPOR

LINE

DISTRIBUTOR

ASSEMBLY

DISTRIBUTOR

TUBES

LIQUID

LINE

MALE EQUALIZER

LINE FITTING

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON®
RING

STUB END

TEFLON

®

RING

SENSING BULB

LIQUID LINE

ORIFICE

HOUSING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

 A.

On fully cased coils, remove the coil access and plumbing panels.

 B.

Remove any shipping clamps from the liquid line and distributor
assembly.

 C.

Disconnect the equalizer line from the expansion valve equalizer
line fitting on the vapor line.

 D.

Remove the vapor line sensing bulb.

 E.

Disconnect the liquid line from the expansion valve at the liquid line
assembly.

 F.

Disconnect the expansion valve from the liquid line orifice housing.
Take care not to twist or damage distributor tubes during this
process.

 G.

Remove and discard expansion valve and the two Teflon

®

 rings.

 H.

Use a field-provided fitting to temporarily reconnect the liquid line to
the indoor unit's liquid line orifice housing.

LOW

HIGH

EXISTING

INDOOR

UNIT

GAUGE

MANIFOLD

CYLINDER CONTAINING
CLEAN HCFC-22* TO BE
USED FOR FLUSHING
(Positioned to deliver liquid
refrigerant)

LIQUID LINE SERVICE

VALVE

INLET

DISCHARGE

TANK
RETURN

CLOSED

OPENED

RECOVERY

CYLINDER

RECOVERY MACHINE

NEW

OUTDOOR

UNIT

VAPOR LINE

SERVICE VALVE

V

APOR

LIQUID

1

 A.

HCFC-22 cylinder with clean refrigerant* (positioned to deliver liquid
refrigerant) to the vapor service valve.

 B.

HCFC-22 gauge set (low side) to the liquid line valve.

 C.

HCFC-22 gauge set center port to inlet on the recovery machine with an
empty recovery tank connected to the gauge set.

 D.

Connect recovery tank to recovery machine per machine instructions.

CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE

A

B

C

D

B

OR

FLUSHING LINE SET

 A.

Set the recovery machine for liquid recovery and start the recovery
machine. Open the gauge set valves to allow the recovery
machine to pull a vacuum on the existing system line set and indoor
unit coil.

 B.

Position the cylinder of clean HCFC-22* for delivery of liquid
refrigerant and open its valve to allow liquid refrigerant to flow into
the system through the vapor line valve. Allow the refrigerant to
pass from the cylinder and through the line set and the indoor unit
coil before it enters the recovery machine.

 C.

After all of the liquid refrigerant has been recovered, switch the
recovery machine to vapor recovery so that all of the HCFC-22
vapor is recovered. Allow the recovery machine to pull the system
down to 0.

 D.

Close the valve on the inverted HCFC-22 drum and the gauge set
valves. Pump the remaining refrigerant out of the recovery
machine and turn the machine off.

The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant* that previously charged the system.
Check the charge in the flushing cylinder before proceeding.

1A

2

3

1B

*IMPORTANT - Clean refrigerant is any refrigerant in a system that has not had compressor burn out. If the system
has experienced burn out, it is recommended that the existing line set and indoor coil be replaced.

FIGURE 6

Summary of Contents for Elite XP20-024-230

Page 1: ...formation consult the Installa tion and Service Procedures manual available as Corp 1408 L10 on DaveNet or through the Technical Support department at 800 453 6669 WARNING Improper installation adjust...

Page 2: ...ructure observe the following While installing or servicing this unit carefully stow all removed panels so that the panels will not cause injury to personnel objects or nearby structures Also take car...

Page 3: ...NCHES PER 5 FEET 50 MM PER 1 5 M AWAY FROM BUILDING STRUCTURE MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL FIGURE 3 LEG DETAIL BASE 2 50 8MM SCH 40 FEMALE THREADED ADAPTER ELEVATED SLAB MOUNTING USIN...

Page 4: ...n lines Oxygen when ex posed to a spark or open flame can cause fire and or an explosion that could result in property damage personal injury or death IMPORTANT Some scroll compressors have an interna...

Page 5: ...Sizes for Horizontal Runs Required Vapor Riser Size 024 180 150 60 60 7 8 5 8 036 180 150 60 60 7 8 3 4 048 180 150 60 60 7 8 7 8 060 180 150 60 60 7 8 7 8 Table 3 Liquid Line Diameter Selection Table...

Page 6: ...id line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD CYLINDER CONTAINING CLEAN HCFC 22 TO BE USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET...

Page 7: ...ur the ends The pipe must remain round Do not crimp end of the line Remove service cap and core from both the suction and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERV...

Page 8: ...water saturated cloths WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing w...

Page 9: ...S NUT DISTRIBUTOR ASSEMBLY C Install one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring wi...

Page 10: ...e cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into...

Page 11: ...um pump and closing the manifold gauge valves F When the absolute pressure requirement above has been met disconnect the manifold hose from the vacuum pump and connect it to a cylinder of HFC 410A pos...

Page 12: ...ge as a result of slugging CAUTION ELECTROSTATIC DISCHARGE ESD Precautions and Procedures Electrostatic discharge can affect electronic components Take care during unit installation and service to pro...

Page 13: ...s PUSH BUTTON 7 SEGMENT DISPLAY PUMP DOWN WHEN UNIT IS IN PUMP DOWN MODE Pd WILL BE DISPLAYED ON 7 SEGMENT TO ACTIVATE PUMP DOWN MODE THE CONTROL MUST BE IN THE IDLE STATE AND THE PUMP DOWN JUMPER PLA...

Page 14: ...oise see below Use a wire nut to bundle the four unused wires at each end of the cable Each bundle should also include an additional wire that should be connected on each end to the C terminal as show...

Page 15: ...cles Charging The XP20 unit is factory charged with enough HFC 410A refrigerant to accommodate a 15 foot length of refrigerant piping Charge should be checked and adjusted using the tables provided on...

Page 16: ...ealer show you the location of the drain line and how to check for ob structions This would also apply to an auxiliary drain if installed S Check the area around the outdoor unit monthly and re move a...

Page 17: ...st debris obstructions leaks or cracks Pour water in pans to confirm proper drain age from the pan through to the outlet of the pipe Clean or replace as necessary E Inspect and clean evaporator indoor...

Page 18: ...G MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Air Temperature HEATING MODE Vapor Pressure Liquid Pressure Supply Air Temperature Ambient Temperature Return Ai...

Reviews: