FLAMMABLE GASES
e-BALTIC-IOM-2020.12-EN
17
MAINTENANCE AND CALIBRATION
During maintenance, you must perform the calibration and functional test, see below, in addition to the inspection. A fixed
calibration interval is recorded for each sensor type.
For an SC2 sensor, if this interval is exceeded, a digital maintenance message is generated and transmitted. Performing
calibration automatically clears this message.
Calibration procedure with tool or display
•
Open the calibration mode in the dialog box.
•
Wait until the warm-up time (300 s) has elapsed.
Zero-Point Calibration :
•
Connect the display, press ENTER.
•
Press the down arrow to go to "Installation & Calibration", press ENTER.
•
The "service mode" screen appears, press ENTER.
•
Enter the password 1234 with the arrows only and confirm with ENTER.
•
Switch the mode service to ON (ENTER + arrow + ENTER to confirm)
→
The buzzer beeps
•
Use the arrows to go to "calibration", press ENTER.
•
Select in the menu the DP1 or DP2 sensor according to the one you want to calibrate and validate with INPUT.
•
Use the arrows to select "Zero DP 1" and confirm with ENTER.
•
Enter the password 5412 with the arrows and confirm with ENTER.
•
Press ENTER once
•
Wait 5 seconds and press ENTER (SAVE should appear on the display).
•
Press ESC twice to return to the previous menus and deactivate the "service mode".
Calibration:
•
Open the test gas dialog box and enter the concentration of the test gas used (1000 ppm).
•
Open the Calibration dialog box.
•
Enter the gas type. Pressure 1bar ± 10%, flow rate 150 ml / min.
•
Perform calibration.
•
Record the new values after a successful calibration.