HEATING OPTION
e-BALTIC-IOM-2020.12-EN
70
ELECTRICAL PREHEATER (D, E, E+ BOX)
WARNING: electric pre-heater is connected heater to main power
–
risk of electrical Shock
–
switch off the unit prior to open
this section
Pre-
heater is running only with high fresh air rate under low outdoor ambient temperature (see setpoint in CLIMATIC™ section).
A metallic filter is installed between air filter & electrical resistance to protect against heat radiations.
WARNING: electric pre-heater metallic filter must not be plugged by dust
Amps per
model size
D BOX
E BOX
E+ BOX
55-65
75-85
95-115
Si
ze
S/
H
S 24 kW
35
S 36 kW
52
52
H 48 kW
69
H 72 kW
104
104