• 68 •
nvi_Watchdog
0
0
32767
nvo_Watchdog
nvo_Alarm_Codes
0
~
999
nvo_Blower_Qv
0
~
32767
nvo_Blower_dP
0
~
1000
nvo_Room_Temp
-99.9
~
99.9
nvo_Outside_Temp
-99.9
~
99.9
nvo_Supply_Temp
-99.9
~
99.9
nvo_Room_Hr
0.0
~
100.0
nvo_Outside_Hr
0.0
~
100.0
nvo_CO2
0
~
2000
nvi_Control_Temp
8.0
20.5
35.0
nvo_Control_Temp
nvo_Control_Cool
8.0
~
35.0
nvo_Control_Heat
8.0
~
35.0
nvi_Cool_BMS
8.0
22.0
35.0
nvo_Cool_BMS
nvi_Heat_BMS
8.0
19.0
35.0
nvo_Heat_BMS
nvi_Cool_D
8.0
35.0
35.0
nvo_Cool_D
nvi_Heat_D
8.0
15.0
35.0
nvo_Heat_D
nvi_Air_Mini_BMS
0.0
20.0
100.0
nvo_Air_Mini_BMS"
nvi_Sends_Room_T
-99.9
-99.9
99.9
nvi_Sends_Out_T
-99.9
-99.9
99.9
nvi_Sends_Room_H
0
0
100
nvi_Sends_Out_H
0
0
100
nvi_Sends_CO2
0
0
2000
nvi_Sends_Speed
0.0
0.0
100.0
nvo_PM_kW
0
~
65536
nvo_PM_kVA
0
~
65536
nvo_PM_Pw_Factor
0
~
65536
nvo_PM_kWh_LSB
0
~
65536
nvo_PM_kWh_MSB
0
~
65536
nvo_PM_kVAh_LSB
0
~
65536
nvo_PM_kVAh_MSB
0
~
65536
nvi_PM_Reset
0
0
65536
nvo_Fresh_Air
0.0
~
100.0
nvo_Compressor
0.0
~
100.0
nvo_Heaters_1
0.0
~
100.0
nvo_Heaters_2
0.0
~
100.0
nvo_Custom_T_1
-99.9
~
99.9
nvo_Custom_T_2
-99.9
~
99.9
nvo_Custom_T_3
-99.9
~
99.9
nvo_Custom_T_4
-99.9
~
99.9
CLIMATIC RT_UNITARY-IOM-1508-E
BMS
NV_Name
DESCRIPTION
MIN
FACT.
MAX
bms, watchdog counter
alarm, codes
blower, calculated value of air
fl
ow
blower, value of differential pressure sensor on air
fl
ow
control, value of the room temperature
control, value of the outside temperature
control, value of the supply temperature
control, value of the room humidity
control, value of the outside humidity
economizer, value of air quality sensor
control, customer (DC/DM) set point
control, set value of cooling mode
control, set value of heating mode
control, bms day, set point of cooling mode
control, bms day, set point of heating mode
control, bms night, set point of cooling mode
control, bms night, set point of heating mode
economizer, bms day, set point of minimum fresh air
emulation, value of the room temperature send by bms
emulation, value of the outside temperature send by bms
emulation, value of the room humidity send by bms
emulation, value of the outside humidity send by bms
emulation, value of the air quality send by bms
emulation, value of the speed blower send by bms
power meter, value of the active power
power meter, value of the reactive power
power meter, value of the power factor
power meter, value (weight low) of the active energy
power meter, value (weight high) of the real energy
power meter, value (weight low) of the reactive energy
power meter, value (weight high) of the reactive energy
power meter, value for reset memory
economizer, opening percentage send to the actuator
circuit, power percentage calculated
1st heaters, power percentage calculated
2nd heaters, power percentage calculated
remote control, value of the signal, be-1 b1, temperature
remote control, value of the signal, be-1 b2, temperature
remote control, value of the signal, be-1 b3, temperature
remote control, value of the signal, be-1 b4, temperature
APPENDIX 2